Sliding Waveguide On Anaerobic Digesters - Siemens SITRANS LR200 7ML5422 Operating Instructions Manual

Radar transmitter with ma/hart
Table of Contents
6.2.2.3

Sliding waveguide on anaerobic digesters

Note
• Minimum distance from the flange face to the target is limited by Far range (2.8.2.)
(Page 111).
• We recommend adjusting Auto False Echo Suppression parameters with an empty or
almost empty vessel.
This application is to obtain a level measurement and corresponding 4 to 20 mA output
proportional to the sludge level on a digester.
● The raised position is for installation and maintenance.
● The lowered position is for operation.
● Program the instrument for operation in the lowered position.
● Low Cal. Pt. is the bottom of the digester (10 m/33 ft from sensor reference point when
the instrument is lowered to its normal operating position).
● High Cal.Pt. is 2 m (6.56 ft) from sensor reference point.
● The maximum rate of filling or emptying is about 0.1 m (4")/min.
Parameter type Parameter name (number)
Quick start
wizard parame-
ters
SITRANS LR200 with mA/HART
Operating Instructions, 05/2019, A5E32337676-AE
Sensor reference point
2 m
Horn
Material (1.2.)
Response Rate (1.3.)
Units (1.4.)
Operating Mode (1.5.)
Low Calibration Point (1.6.)
High Calibration Point (1.7.)
High calibration point
10 m
Low calibration point
Value
LIQUID
MED
M
LEVEL
10
2
Function
1 m/min. (3.28 ft/min.)
meters
Level
10 m/33 ft)
2 m (6.56 ft)