Siemens SITRANS LR200 7ML5422 Operating Instructions Manual page 142

Radar transmitter with ma/hart
Table of Contents
Code/
Meaning
Icon
S: 11
Internal temperature sensor failure.
S: 12
Internal temperature of device has exceeded
specifications: it is operating outside its tem-
perature range.
S: 17
Calibration interval as defined in Maintenance
Required Limit has expired.
S: 18
Calibration interval as defined in Maintenance
Demanded Limit has expired.
S: 28
*
Internal device failure caused by a RAM
memory error.
S: 29
*
EEPROM damaged.
S: 31
*
Flash error.
S: 33
*
Factory calibration for the internal temperature
sensor has been lost.
S: 34
*
Factory calibration for the device has been lost. Replacement required: contact your local Siemens repre-
S: 35
*
Factory calibration for the device has been lost. Replacement required: contact your local Siemens repre-
S: 36
*
Unable to start microwave module.
142
Corrective Action
Repair required: contact your local Siemens representa-
tive.
Relocate device and/or lower process temperature
enough to cool device.
Inspect for heat-related damage and contact your
local Siemens representative if repair is required.
Fault code will persist until a manual reset is per-
formed using SIMATIC PDM or the LCD interface.
Perform calibration.
Perform calibration.
Replacement required: contact your local Siemens repre-
sentative.
Replacement required: contact your local Siemens repre-
sentative
Replacement required: contact your local Siemens repre-
sentative
Replacement required: contact your local Siemens repre-
sentative
sentative
sentative
Repair required: contact your local Siemens representa-
tive
Operating Instructions, 05/2019, A5E32337676-AE
SITRANS LR200 with mA/HART