GE Lumination LDXB Series Installation Manual

Led luminaire

Quick Links

Lumination
LDXB Series
BEFORE YOU BEGIN
Read these instructions completely and carefully.
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input / output connections. Minimum
size 18 AWG or 14 AWG for continuous runs.
Save These Instructions
Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer.
This device complies with Part 15 of the FCC Rules. Operation is subject
tothe following two conditions: (1) This device may not cause harmful
interference,and (2) this device must accept any interference received,
including interference that may cause undesired operation.
CAN ICE-005(A)/NMB-005(A)
Note: This equipment has been tested and found to comply with the
limits for a Class Adigital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
LED Luminaire
®
WARNING / AVERTISSEMENT
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l'alimentation avant d'inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d'alimentation électrique.
RISQUES D'INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N'utilisez que des fils approuvés par UL pour les entrées/sorties de connexion. Taille
minimum 18 AWGou 14 AWG pour les rangées continues.
Prepare Electrical Wiring
Electrical Requirements
• The LED driver must be uspplied with 120V to
277V for LDXBxx0xxxxxxx fixtures and 347V for
LDXBxxDxxxxxxx fixtures. 50/60 Hz and connected
to an individual properly grounded branch circuit,
protected by a 20 ampere circuit breaker. Use min.
90
o
C supply conductor.
Grounding Instructions
• The grounding and bonding of the overall system
shall be done in accordance to local electric code of
the country where the luminire is installed.
Installation Guide
IND544 | A-1026317
loading

Summary of Contents for GE Lumination LDXB Series

  • Page 1 Installation Guide IND544 | A-1026317 Lumination LED Luminaire ® LDXB Series BEFORE YOU BEGIN Read these instructions completely and carefully. WARNING / AVERTISSEMENT RISK OF ELECTRIC SHOCK RISQUES DE DÉCHARGES ÉLECTRIQUES • Turn power off before inspection, installation or removal. •...
  • Page 2: Unit Installation

    Lumination LDXB Series Installation Guide ® Unit Installation Fixture Hole Size 4 in. round fixture 5 in. (126mm) diameter hole See Note 6 in. round fixture in. (165mm) diameter hole 4 in. square fixture in. x 5 in. (140mm x 140mm) 6 in.
  • Page 3 Lumination LDXB Series Installation Guide ® Trimless Option Appendix for Drywall Application Ensure that muddy frame is lined Plaster onto the muddy frame and Dust off any particles that may up with rig frame and secure it to ceiling. Repeat plastering process have adhered to the light module.
  • Page 4 Lumination LDXB Series Installation Guide ® Replacing the LED Module Turn off power. Remove reflector from fixture. Reach inside and push LED module Move LED module inside Save for future re-installation. upward and then counterclockwise the room. to disengage 3 clips. Open quick disconnect J-box Disconnect DC connection.
  • Page 5: Driver Replacement

    Lumination LDXB Series Installation Guide ® Driver Replacement Turn off power and remove reflector. Driver Clip Driver Driver Clip Clip Remove LED module by and Disengage driver by pulling on Bring driver inside the room and pushing upward and then clip.
  • Page 6 Lumination LDXB Series Installation Guide ® Extension Tray Replacement Remove LED module by pushing up, then turning counterclockwise to disengage 3 clips. Remove LED module by pushing Remove LED module from frame, Open quick disconnect J-box up, then counterclockwise to bringing below the ceiling plane.
  • Page 7 Lumination LDXB Series Installation Guide ® Extension Tray Replacement Bring all connections from the JBox to the Disconnect AC connections, dimming and test downlight opening. button. Pull out the extension tray. NOTE: Some parts in the illustraition are hidden for clarity. Re-install replacement tray by reversing steps 1-9.
  • Page 8: Electrical Connections

    Lumination LDXB Series Installation Guide ® Electrical Connections For Standard (VQ): For Options (TQ and TS): Connect the black (line) of the AC line to the black 120V, Connect the black (line) of the AC line to the black 120V, 277V, or 347V wire.
  • Page 9 Lumination LDXB Series Installation Guide ®...
  • Page 10 Lumination LDXB Series Installation Guide ®...
  • Page 11: Troubleshooting

    Fixture intended for commercial use only. Use only in non-insulated applications. www.gecurrent.com © 2020 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the General Electric Company and are used under license. Information provided is subject to change without notice.