Emerson NELSON CM-GP Installation Instructions Manual
Emerson NELSON CM-GP Installation Instructions Manual

Emerson NELSON CM-GP Installation Instructions Manual

General purpose temperature controller

Quick Links

NELSON
CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS
AXPC100-CM-GP Pipe Mounted Option
CM-GP Wall Mounted Option
CM-GP Stand-Alone Option
CM-GP CONTROLLER CONTENTS
QTY
ITEM
DESCRIPTION
1
1
LID
1
2
WIRE COVER
1
3
BOX WITH ELECTRONICS
OPTIONAL INSTALLATION MATERIAL
 Pipe Clamp – PC03, PC12 or PC20 (included)
 Fiberglass Tape – GT6 or GT60
 HC-SPA Small Pipe Adapter – For 1.0"
 RTD (Types RTD-1, RTD-7, or RTD-A)
DESCRIPTION
The CM-GP/AXPC100-CM-GP is an electronic
temperature controller with 30-mA ground-fault protection.
It is ideal for all heat tracing applications requiring accurate
temperature monitoring. The controller can be
programmed to maintain temperatures up to 215°C
(419°F) at voltages from 100 to 277 V and can switch
current up to 30 Amperes for the CM-GP or 25 Amperes
for the AXPC100-CM-GP. The CM-GP/AXPC100-CM-GP
is complete with a temperature sensor and is housed in a
NEMA 4X rated enclosure. The controller features an
AC/DC dry alarm contact relay for monitoring critical
applications such as fire protection piping.
These instructions are to be used together with the
installation and maintenance instructions for any heating
cable or power connection kits utilized with this controller.
ADDED FOR
AXPC100-CM-GP
TEL 800-621-1506
AXPC100-CM-GP KIT CONTENTS
QTY
ITEM
DESCRIPTION
1
1
LID
1
2
WIRE COVER
1
3
BOX WITH ELECTRONICS
1
4
TERMINATION PWR LONG
SILICONE
2
5
GUIDE TUBE
1
6
SEAL END
1
7
TUBE OF SILICONE
1
8
1" NPT ADAPTER
1
9
CABLE RETAINER
1
10
STANDOFF
1
11
LOCK NUT
1
12
3/8" SHRINK TUBE
1
13
CABLE TIE
RECOMMENDED TOOLS
 Large Cross Blade (Philips) Screwdriver
 Small Cross Blade (Philips) Screwdriver
 Wire Cutters
 Adjustable Wrench (52mm [2.1"] size)
 Needle Nose Pliers
 Large Slotted Screwdriver
www.nelsonheaters.com
INSTALLATION
14251-001 Rev. 0
Sheet 1 of 10
November 2020
Table of Contents
loading

Summary of Contents for Emerson NELSON CM-GP

  • Page 1 NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS DESCRIPTION The CM-GP/AXPC100-CM-GP is an electronic temperature controller with 30-mA ground-fault protection. It is ideal for all heat tracing applications requiring accurate temperature monitoring. The controller can be AXPC100-CM-GP Pipe Mounted Option programmed to maintain temperatures up to 215°C (419°F) at voltages from 100 to 277 V and can switch current up to 30 Amperes for the CM-GP or 25 Amperes...
  • Page 2: Installation

    NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS WALL MOUNTING THE CM-GP/AXPC100-CM-GP Max Screw size: #10, 0.19in (5mm) Counterbore size: 0.36in (9mm) Left side entry: ½” NPT (0.87in) Right side entry: ¾” NPT (1.10in) Bottom entry: 1” NPT (1.31in ...
  • Page 3 NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS AXPC100-CM-GP STANDOFF INSTALLATION STEP 1 STEP 2 1 ½” (38 mm)  Allow 1 ½” (3.81 cm) of heating cable  Pull excess heating cable to remain above top of standoff body. back through standoff.
  • Page 4 NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS STEP 6 STEP 5 Flex Conduit Conduit Drain  Install enclosure and secure to enclosure  Install flex conduit and drain as shown. adapter with supplied locknut.  Terminate power and ground wires to terminal ...
  • Page 5: Connecting Temperature Sensor

    NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS CONNECTING INCOMING POWER  Install conduit, fittings, and wires according to local standards.  Wire size limits: 18 AWG – 6 AWG (See installation and maintenance instructions for self-regulating heater cable for further detail (GA-1765)).
  • Page 6: Wiring Verification

    NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS WIRING VERIFICATION FINISHING INSTALLATION  Install wire cover by attaching it to the plastic standoffs, and ensuring that it snaps in place.  Program the Controller, see MENU SETTINGS section for details. ...
  • Page 7: Menu Settings

    NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS MENU SETTINGS The following chart:  Shows how the items will appear on the Controller  Lists the parameters in order of appearance on the Controller.  Lists the default, min. and max values for each parameter. Menu Items Parameter Default...
  • Page 8: Error Displays

    NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS ERROR DISPLAYS The Controller will display the following upon detecting an error state:  Low Temerature Alarm When Actual temperature(AT) is less than or equal to the low temperature alarm value (LTAV), Alarm LED (Red) will start flashing and the display will flash as follows: “Lo”, “ALr”,”LtSp”, LTAV,”Act”, AT...
  • Page 9: General Conditions Of Safe Use

    NELSON ™ INSTALLATION CM-GP/AXPC100-CM-GP General Purpose Temperature Controller INSTRUCTIONS GENERAL CONDITIONS OF SAFE USE  To prevent electrical arcing and fire hazard, all cable connections and electrical wiring connections should be sealed against moisture. This includes the use of proper cable sealing kits and the moisture proofing of all wire connections.
  • Page 10 Nelson Heat Tracing Systems products are supplied with a limited warranty. Complete Terms and Conditions may be found on Nelson's website at www.nelsonheaters.com. Nelson is a trademark of the Appleton Group LLC (Heating Cable Systems), 2 Connecticut South Dr, East Granby, CT, 06026. A division of Emerson Automation Solutions.

This manual is also suitable for:

Nelson axpc100-cm-gp

Table of Contents