Mitsubishi Electric MELSEC iQ-R Series User Manual

Mitsubishi Electric MELSEC iQ-R Series User Manual

Channel isolated thermocouple input module/channel isolated rtd input module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents
MELSEC iQ-R Channel Isolated Thermocouple
Input Module/Channel Isolated RTD Input Module
User's Manual (Application)
-R60TD8-G
-R60RD8-G
Table of Contents
loading

Summary of Contents for Mitsubishi Electric MELSEC iQ-R Series

  • Page 1 MELSEC iQ-R Channel Isolated Thermocouple Input Module/Channel Isolated RTD Input Module User's Manual (Application) -R60TD8-G -R60RD8-G...
  • Page 3: Safety Precautions

    SAFETY PRECAUTIONS (Read these precautions before using this product.) Before using this product, please read this manual and the relevant manuals carefully and pay full attention to safety to handle the product correctly. The precautions given in this manual are concerned with this product only. For the safety precautions of the programmable controller system, refer to the MELSEC iQ-R Module Configuration Manual.
  • Page 4 [Design Precautions] WARNING ● Configure safety circuits external to the programmable controller to ensure that the entire system operates safely even when a fault occurs in the external power supply or the programmable controller. Failure to do so may result in an accident due to an incorrect output or malfunction. (1) Emergency stop circuits, protection circuits, and protective interlock circuits for conflicting operations (such as forward/reverse rotations or upper/lower limit positioning) must be configured external to the programmable controller.
  • Page 5 [Design Precautions] WARNING ● When connecting an external device with a CPU module or intelligent function module to modify data of a running programmable controller, configure an interlock circuit in the program to ensure that the entire system will always operate safely. For other forms of control (such as program modification, parameter change, forced output, or operating status change) of a running programmable controller, read the relevant manuals carefully and ensure that the operation is safe before proceeding.
  • Page 6 [Design Precautions] CAUTION ● Do not install the control lines or communication cables together with the main circuit lines or power cables. Doing so may result in malfunction due to electromagnetic interference. Keep a distance of 100mm or more between those cables. ●...
  • Page 7 [Installation Precautions] CAUTION ● Use the programmable controller in an environment that meets the general specifications in the Safety Guidelines included with the base unit. Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of the product. ●...
  • Page 8 [Wiring Precautions] CAUTION ● Individually ground the FG and LG terminals of the programmable controller with a ground resistance of 100 ohms or less. Failure to do so may result in electric shock or malfunction. ● Use applicable solderless terminals and tighten them within the specified torque range. If any spade solderless terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure.
  • Page 9 [Startup and Maintenance Precautions] WARNING ● Do not touch any terminal while power is on. Doing so will cause electric shock or malfunction. ● Correctly connect the battery connector. Do not charge, disassemble, heat, short-circuit, solder, or throw the battery into the fire. Also, do not expose it to liquid or strong shock. Doing so will cause the battery to produce heat, explode, ignite, or leak, resulting in injury and fire.
  • Page 10 [Startup and Maintenance Precautions] CAUTION ● When connecting an external device with a CPU module or intelligent function module to modify data of a running programmable controller, configure an interlock circuit in the program to ensure that the entire system will always operate safely. For other forms of control (such as program modification, parameter change, forced output, or operating status change) of a running programmable controller, read the relevant manuals carefully and ensure that the operation is safe before proceeding.
  • Page 11 [Operating Precautions] CAUTION ● When changing data and operating status, and modifying program of the running programmable controller from an external device such as a personal computer connected to an intelligent function module, read relevant manuals carefully and ensure the safety before operation. Incorrect change or modification may cause system malfunction, damage to the machines, or accidents.
  • Page 12: Conditions Of Use For The Product

    Before using this product, please read this manual and the relevant manuals carefully and develop familiarity with the functions and performance of the MELSEC iQ-R series programmable controller to handle the product correctly. When applying the program examples provided in this manual to an actual system, ensure the applicability and confirm that it will not cause system control problems.
  • Page 13: Table Of Contents

    CONTENTS SAFETY PRECAUTIONS ..............1 CONDITIONS OF USE FOR THE PRODUCT .
  • Page 14 The ALM LED turns on or flashes ............80 A measured temperature value cannot be read .
  • Page 15: Relevant Manuals

    The online module change, which allows a module to be changed Print book [SH-081501ENG] without stopping the system for MELSEC iQ-R series e-Manual programmable controllers e-Manual refers to the Mitsubishi FA electronic book manuals that can be browsed using a dedicated tool.
  • Page 16: Terms

    The abbreviation for the RJ72GF15-T2 CC-Link IE Field Network remote head module RTD input module The abbreviation for the MELSEC iQ-R series channel isolated RTD input module Temperature input module A generic term for the thermocouple input module and the RTD input module...
  • Page 17: Chapter 1 Functions

    FUNCTIONS This chapter describes the functions of a temperature input module and the setting procedures for those functions. For details on the I/O signals and the buffer memory, refer to the following. Page 90 I/O Signals Page 99 Buffer Memory Areas •...
  • Page 18: Input Range Setting Function

    Input Range Setting Function This function allows to select the thermocouple type or resistance temperature detector type to be used as well as the measuring range for each channel. Available input range Set an input range using buffer memory. The following tables list available input range by each module. •...
  • Page 19 Setting procedure ■For the thermocouple input module When using the thermocouple input module, set "Thermocouple type setting". [Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Thermocouple type selection function] Set "Offset/gain setting" to "Factory default setting" or "User range setting". ■For the RTD input module When using the RTD input module, set "RTD type setting".
  • Page 20: Conversion Enable/Disable Setting Function

    Conversion Enable/Disable Setting Function This function sets whether to enable or disable the temperature conversion for each channel. Disabling the conversion on unused channels reduces the conversion cycles. Setting procedure Set "Conversion enable/disable setting" to "Conversion enable". [Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Conversion enable/disable setting function] 1 FUNCTIONS 1.3 Conversion Enable/Disable Setting Function...
  • Page 21: Temperature Conversion Method

    Temperature Conversion Method This function sets a temperature conversion method for each channel. Sampling processing A temperature input module executes the conversion of temperature input values sequentially and stores the converted values in buffer memory areas as measured temperature values. The sampling cycle is "Conversion speed ...
  • Page 22 ■Count average A temperature input module executes the conversion for a set number of times and averages the total value excluding the maximum value and the minimum value. The calculated value is stored in the buffer memory area. The time taken to store the average value obtained by the processing in the buffer memory area varies depending on the number of channels where the conversion is enabled.
  • Page 23 Primary delay filter A temperature input module performs the conversion where the transient noise of temperature input is smoothed depending on the set time constant. The smoothed measured temperature value is stored in the buffer memory area. Time constant is the time taken for the measured temperature value to reach 63.2% of the steady-state value. The degree of smoothing changes depending on the setting of a time constant.
  • Page 24 Setting procedure ■Sampling processing Set "Average processing setting" to "Sampling processing". [Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Temperature conversion system] ■Averaging processing and primary delay filter Set "Average processing setting" to "Time average", "Count average", "Moving average", or "Primary delay filter". [Navigation window] ...
  • Page 25: Scaling Function

    Scaling Function A temperature input module performs scale conversion from a measured temperature value to a value calculated using the ratio (%) of the set scaling width to the set scaling range. The converted value is stored in the buffer memory area. The calculation of a value is performed using a scaling range upper limit value, scaling range lower limit value, scaling width upper limit value, and scaling width lower limit value, all of which are set arbitrarily.
  • Page 26 Calculating the scaling value The scale conversion is based on the following formulae. (In scale conversion, values are rounded off to the nearest whole number.) The calculation formula for a scaling value varies depending on the relationship of a scaling range upper limit value and scaling range lower limit value.
  • Page 27 Setting example ■Example 1 This example assumes that the thermocouple input module is used with the following settings for the channel where a K thermocouple (-270 to 1370) is connected. • "Scaling enable/disable setting": "Enable" • "Scaling range upper limit value": 5000 •...
  • Page 28 ■Example 2 This example assumes that the thermocouple input module is used with the following settings for the channel where a K thermocouple (-270 to 1370) is connected. • "Scaling enable/disable setting": "Enable" • "Scaling range upper limit value": -1000 •...
  • Page 29: Alert Output Function

    Alert Output Function This section describes process alarms and rate alarms used for the alert output function. Process alarm This function outputs an alert when a measured temperature value enters the preset alert output range. Measured temperature value Alert output range Out of alert output range Included Alert...
  • Page 30 In addition, when Normal (0) is stored in all the bits of 'Alert output flag (Process alarm upper limit)' (Un\G36) and 'Alert output flag (Process alarm lower limit)' (Un\G37), 'Alert output signal' (XD) turns off and the ALM LED turns off. However, the alarm code stored in 'Latest alarm code' (Un\G2) is not cleared.
  • Page 31: Rate Alarm

    Rate alarm This function outputs an alert when the change of a measured temperature value is equal to or greater than the rate alarm upper limit value, or equal to or smaller than the rate alarm lower limit value. 'CH1 Measured temperature Rate alarm alert value' (Un\G400)
  • Page 32 Operation ■Operation performed when an alert is output Measured temperature values are monitored on the rate alarm alert detection cycle. When a change rate of a measured temperature value (from a previous value) is equal to or more than the rate alarm upper limit value, or the rate is equal to or less than the rate alarm lower limit value, an alert is output as follows.
  • Page 33 Judgment of rate alarm A change rate is judged with the following formulae every rate alarm alert detection cycle. • For alert outputting of rate alarm upper limit Measured temperature value of this time - Measured temperature value of previous detection cycle  Rate alarm upper limit value •...
  • Page 34 Application examples of rate alarms A rate alarm serves to monitor the change of a measured temperature value in a limited range as shown below. To monitor that an increase rate of a measured temperature value is within the specified range Change of the measured Rate alarm upper limit value temperature value (­)
  • Page 35 Operation performed when disconnection is detected • At disconnection detection, a rate alarm may occurs as well because 'CH1 Measured temperature value' (Un\G400) changes according to 'CH1 Conversion setting at disconnection detection' (Un\G531). • At recovery time from disconnection, previous information (value) of rate alarm is cleared. Therefore, at the restart of temperature conversion, even if the change rate of the measured temperature value (from before restart to after restart) is out of the limit range, an alert is not output.
  • Page 36: Disconnection Detection Function

    Disconnection Detection Function This function detects disconnection of a thermocouple, compensation lead wire, or resistance temperature detector. Notification of disconnection • Disconnection detection (1) is stored in a bit position corresponding to the channel number of 'Disconnection detection flag' (Un\G41). •...
  • Page 37 ■Measured temperature value after the recovery A correct measured temperature value is stored in the buffer memory area at the next temperature conversion after Normal (0) is stored in 'Disconnection detection flag' (Un\G41). For averaging processing, a correct measured temperature value is stored in the buffer memory area after Normal (0) is stored in 'Disconnection detection flag' (Un\G41) and the averaging process cycle has elapsed.
  • Page 38 ■Any value At the time of the disconnection detection, a value set in 'CH1 Conversion setting value at disconnection detection' (Un\G532) is stored in 'CH1 Measured temperature value' (Un\G400). The default value of 'CH1 Conversion setting value at disconnection detection' (Un\G532) is 0. The value can be changed to any value although using 0 is no problem. When the scaling function is used, a value according to the setting of 'CH1 Conversion setting at disconnection detection' (Un\G531) is scale converted and then stored as a scaling value.
  • Page 39: Cold Junction Compensation Setting Function

    Cold Junction Compensation Setting Function This function enables two types of cold junction compensation (using a cold junction compensation resistor or an external method (cooling bath)) by setting whether to use a cold junction compensation resistor. Only the thermocouple input module can use the function.
  • Page 40 Setting procedure Set "Cold junction temperature compensation with/without setting" to "With cold junction temperature compensation" or "Without cold junction temperature compensation". [Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Cold junction temperature compensation with/without setting function] 1 FUNCTIONS 1.8 Cold Junction Compensation Setting Function...
  • Page 41: Cold Junction Compensation Resistor Disconnection Detection Function

    Cold Junction Compensation Resistor Disconnection Detection Function This function outputs an error when disconnection of a cold junction compensation resistor (RTD) is detected. Only the thermocouple input module can use the function. Notification of disconnection • 'Error flag' (XF) turns on. •...
  • Page 42: Logging Function

    1.10 Logging Function This function stores 1000 points of measured temperature values or scaling values per channel in the buffer memory area. In addition, the data collection can be stopped by using the status change of the data as a trigger. This function also helps the error analysis since the data before and after the occurrence of an error is held.
  • Page 43 Operation of logging ■Starting logging data collection Logging data collection starts when Enable (0) is set in 'CH1 Logging enable/disable setting' (Un\G535)' and 'Operating condition setting request' (Y9) is turned on and off. The data in 'CH1 Measured temperature value' (Un\G400) or 'CH1 Scaling value' (Un\G402) is stored in CH1 Logging data (Un\G10000 to Un\G10999) on the set logging cycle.
  • Page 44 Logging cycle ■Logging cycle setting Set the logging cycle with 'CH1 Logging cycle setting value' (Un\G537) and 'CH1 Logging cycle unit setting' (Un\G538). The following table lists the setting range for each cycle. Setting value of 'CH1 Logging cycle unit setting' (Un\G538) Setting range of 'CH1 Logging cycle setting value' (Un\G537) ms (1) •...
  • Page 45 ■Number of logging data With 'CH1 Number of logging data' (Un\G436), the number of valid data in 'CH1 Logging data' (Un\G10000 to Un\G10999) can be checked. • When the number of collected data points is less than 1000 Address 0 Valid data Address 1 Address 2...
  • Page 46 ■Head pointer and latest pointer The storage location of the oldest data and the latest data in CH1 Logging data (Un\G10000 to Un\G10999) can be checked with the following buffer memory areas. Buffer memory area Description CH1 Head pointer (Un\G434) The buffer memory address of the oldest data in CH1 Logging data (Un\G10000 to Un\G10999) can be checked with this buffer memory area.
  • Page 47: Stopping The Logging Operation

    Stopping the logging operation Logging operation stops (holds) when the preset trigger condition is satisfied and the set points of the data are collected. A trigger that is generated when the condition is satisfied is called a hold trigger. To generate a hold trigger, the following two methods are available. Page 48 Logging hold request Page 49 Level trigger When a hold trigger is detected during data collection, the logging operation stops after the points of the data set in 'CH1 Post-...
  • Page 48 ■Checking the trigger generation time The trigger generation time can be checked with 'CH1 Trigger generation time' (Un\G444 to Un\G448). When 'CH1 Trigger generation time' (Un\G444 to Un\G448) is monitored b8 b7 First two digits of the year Last two digits of the year 'CH1 Trigger generation time (First/Last two digits of the year)' (Un\G444) Month 'CH1 Trigger generation time (Month/Day)' (Un\G445)
  • Page 49 Resuming the logging It may take time until ON (1) is stored in 'CH1 Logging hold flag' (Un\G409) after 'CH1 Logging hold request' (Un\G471) is changed from off to on. To resume logging, check that ON (1) is stored in 'CH1 Logging hold flag' (Un\G409) and change 'CH1 Logging hold request' (Un\G471) from on to off.
  • Page 50: Logging Hold Request

    Logging hold request A hold trigger is generated from a program at any timing. After ON (1) is set to 'CH1 Logging hold request' (Un\G471), a preset number of data is collected and then the logging stops. Controlled by the temperature input module 'CH1 Logging hold request' OFF(0) ON(1)
  • Page 51: Level Trigger

    Level trigger When a value in the monitored buffer memory area of a temperature input module satisfies a preset condition, a hold trigger is generated. A level trigger is monitored on the refreshing cycle of the measured temperature value or the scaling value. Initial setting of a level trigger ■Setting a target to be monitored As a condition to generate a hold trigger, set the buffer memory address to be monitored to 'CH1 Trigger data' (Un\G541).
  • Page 52 ■Setting the monitoring condition • Set a condition to generate a hold trigger in 'CH1 Level trigger condition setting' (Un\G540). Setting value Description Level trigger (condition: A hold trigger is generated under the condition (a). Stored value of a buffer memory area to be monitored Rise) (1) Level trigger (condition: A hold trigger is generated under the condition (b).
  • Page 53 Operation of a level trigger To use a level trigger, set ON (1) to 'CH1 Logging hold request' (Un\G471) in advance. At the point where ON (1) has been set to 'CH1 Logging hold request' (Un\G471), the module becomes the trigger condition wait status. After the trigger condition has been satisfied, and the set points of the data have been collected from that point, the logging stops.
  • Page 54: Initial Settings Of The Logging Function

    Initial settings of the logging function The following describes the initial setting procedure to use the logging function. Setting procedure Set "Conversion enable/disable setting" to "Conversion enable". [Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting]  [Conversion enable/disable setting function] Set "Logging enable/disable setting"...
  • Page 55: Logging Read Function

    Logging read function More than 1000 points of logging data can be stored by transferring the device data to the file register of the CPU module without stopping logging. This function reduces the takt time in a test demanding high-speed conversion. Overview of the logging read function After logging starts, an interrupt request is sent to the CPU module and an interrupt program is executed every time the preset number of data to be read is logged.
  • Page 56 The values to be stored in each pointer at every detection interrupt when the logging read detection starts with 'CH1 Logging read points setting value' (Un\G545) being set to 1000 Occurrence of read pointer Previous logging read pointer Current logging read pointer Latest pointer detection interrupts Default value...
  • Page 57 Setting procedure To use the logging read function, both the logging read function and the interrupt setting must be set. Set "Condition target setting" to "Logging read". [Navigation window]  [Parameter]  [Module Information]  Module model name  [Interrupt setting] Set "Conversion enable/disable setting"...
  • Page 58 • Program example Enable only the interrupt pointer I50. Initialize CH1 Logging read points monitor value and the write position of the save destination file register. Set the maximum number of stored points of save destination file registers. Clear Interrupt factor mask [0]. (109) Store CH1 Current logging read pointer in the index register.
  • Page 59: Saving To A Csv File

    Saving to a CSV file The logging data stored in the buffer memory areas can be saved to a CSV file by using module function blocks. The save data is sorted in a time series, where the logging data can be easily checked. However, module function blocks can be executed only when the logging operation is stopped.
  • Page 60: Displaying Logging Data

    Displaying logging data The CSV file output with the logging function can be displayed graphically by reading the file through GX LogViewer. For how to display the logging data with GX LogViewer, refer to the following.  GX LogViewer Version 1 Operating Manual 1 FUNCTIONS 1.10 Logging Function...
  • Page 61: Interrupt Function

    1.11 Interrupt Function This function executes an interrupt program of the CPU module when an interrupt factor such as alert output or disconnection is detected. For a temperature input module, the maximum number of interrupt pointers available is 16 per module. Operation ■Detecting an interrupt factor When an interrupt factor occurs, an interrupt request is sent to the CPU module at the same time as 'Interrupt factor detection...
  • Page 62 ■Interrupt pointer Specify the number of an interrupt pointer that is initiated at the detection of an interrupt factor. For details on the interrupt pointers, refer to the following.  MELSEC iQ-R CPU Module User's Manual (Application) Precautions • If 'Condition target setting [n]' (Un\G232 to Un\G247) is Disable (0), an interrupt request is not sent to the CPU module. •...
  • Page 63 Setting example To execute the interrupt program (I51) at the disconnection detection in any channel of the thermocouple input module • Parameter setting Set "Interrupt setting" of [Module Parameter] as follows. Condition target setting Condition target channel setting Interrupt pointer Disconnection detection flag All CH specification •...
  • Page 64: Error History Function

    1.12 Error History Function This function records up to 16 errors and alarms that occurred in a temperature input module to store them in the buffer memory areas. Operation of the error history function When an error occurs, the error code and the error time are stored from Error history 1 (Un\G3600 to Un\G3605) in order. When an alarm occurs, the alarm code and the alarm time are stored from Alarm history 1 (Un\G3760 to Un\G3765) in order.
  • Page 65 Checking The start address of Error history where the latest error is stored can be checked in 'Latest address of error history' (Un\G1). The start address of Alarm history where the latest alarm is stored can be checked in 'Latest address of alarm history' (Un\G3).
  • Page 66 The figure below shows the example of when the 17th error has occurred. The 17th error is stored in Error history 1, and 'Latest address of error history' (Un\G1) is overwritten with the value 3600 (start address of Error history 1). Latest address of error history (Un\G3600) Un/G3600...
  • Page 67: Event History Function

    1.13 Event History Function This function collects occurred errors and alarms, and performed operations in a temperature input module, and stores them as event information into the CPU module. The CPU module collects the event information occurred in a temperature input module and keeps them in the data memory inside of the CPU module.
  • Page 68: Backing Up, Saving, And Restoring Offset/Gain Values

    1.14 Backing up, Saving, and Restoring Offset/Gain Values The offset/gain values of the user range setting of a temperature input module can be backed up, saved, and restored. • Backup: Creates a module-specific backup parameter and saves offset/gain values in it. •...
  • Page 69 Creating and refreshing a module-specific backup parameter A module-specific backup parameter is created or refreshed at the refresh timing of offset/gain values stored in the non- volatile memory of a temperature input module. Timing of creating or refreshing the Description backup data Completion of offset/gain setting using "Offset/ A module-specific backup parameter is created or refreshed at the completion of "Offset/gain setting"...
  • Page 70 Restrictions on a module-specific backup parameter The data cannot be backed up and restored with a module-specific backup parameter under the following conditions. • A module other than a Process CPU is used as a control CPU. • A temperature input module is replaced with the programmable controller being powered off. •...
  • Page 71: When A Module-Specific Backup Parameter Is Not Used

    When a module-specific backup parameter is not used When not using a module-specific backup parameter, save and restore offset/gain values with the following methods. • Saving and restoring by dedicated instructions • Saving and restoring by reading from and writing to the buffer memory Using the above methods, restoration of offset/gain values to a new module or application of offset/gain values set in one module to the other modules in the same system is also possible.
  • Page 72 • To apply the offset/gain values set in one module to the other modules in the same system: When the offset/gain values in module No.1 are applied to modules No.2 to No.4 Save the offset/gain values of module No.1. Apply the offset/gain values to modules No.2 to No.4. Saving and restoring by dedicated instructions Use the dedicated instruction G(P).OGLOAD to temporarily save the offset/gain values of the source temperature input module to the internal device of the CPU module, then use G(P).OGSTOR to write the values to the destination temperature...
  • Page 73 Saving and restoring by reading from and writing to the buffer memory Use buffer memory areas of CH1 Factory default setting offset value (L) to CH8 User range setting gain value (H), and 'User range write request' (YA) to read the offset/gain values from the source temperature input module. Use the buffer memory areas again to write the values to the destination temperature input module.
  • Page 74: Q Compatible Mode Function

    This compatibility enables the reuse of programs that have proven performance on MELSEC-Q series temperature input modules. The following table lists the compatible modules of the MELSEC-Q series. Temperature input module of the MELSEC iQ-R series Compatible temperature input module R60TD8-G...
  • Page 75: Chapter 2 Parameter Settings

    PARAMETER SETTINGS Set the parameters of each channel. Setting parameters here eliminates the need to program them. Basic Setting Setting procedure Open "Basic setting" of the engineering tool. Start Module parameter. [Navigation window]  [Parameter]  [Module Information]  Module model name  [Basic setting] Click the item to be changed to enter the setting value.
  • Page 76: Application Setting

    Application Setting Setting procedure Open "Application setting" of the engineering tool. Start Module parameter. [Navigation window]  [Parameter]  [Module Information]  Module model name  [Application setting] Click the item to be changed to enter the setting value. • Item where a value is selected from the pull-down list Click [] button of the item to be set, and from the pull-down list that appears, select the value.
  • Page 77: Interrupt Setting

    Interrupt Setting Setting procedure Open "Interrupt setting" of the engineering tool. Start Module parameter. [Navigation window]  [Parameter]  [Module Information]  Module model name  [Interrupt setting] Click the interrupt setting number (No.1 to 16) to be changed to enter the setting value. •...
  • Page 78: Refresh Setting

    Refresh Setting Setting procedure Set the buffer memory area of a temperature input module to be refreshed. This refresh setting eliminates the need for reading/writing data by programming. Start Module parameter. [Navigation window]  [Parameter]  [Module Information]  Module model name  [Refresh settings] Click "Target", and set the refresh destination.
  • Page 79: Refresh Processing Time

    Refresh processing time A refresh processing time [s] is a constituent of the scan time of the CPU module. For details on the scan time, refer to the following.  MELSEC iQ-R CPU Module User's Manual (Application) The refresh processing time [s], which is taken for refresh, is given by: •...
  • Page 80: Chapter 3 Troubleshooting

    TROUBLESHOOTING This chapter describes errors that may occur in the use of a temperature input module and those troubleshooting. Troubleshooting with the LEDs Check the state of the LEDs to narrow down the possible causes of the trouble. This step is the first diagnostics before using the engineering tool.
  • Page 81 Alarm codes, error history, alarm history can be checked with the event history window of the engineering tool. [Diagnostics]  [System Monitor]  [Event History] button 3 TROUBLESHOOTING 3.2 Checking the State of the Module...
  • Page 82: Troubleshooting By Symptom

    Troubleshooting by Symptom The RUN LED flashes or turns off When flashing Check item Cause Action Check whether the module is in offset/gain setting The programmable controller has been powered In the module parameter setting of the engineering mode. off and on, or the CPU module has been reset tool, set the operation mode to normal mode and when the operation mode is set to offset/gain power off and on the programmable controller, or...
  • Page 83: A Measured Temperature Value Cannot Be Read

    A measured temperature value cannot be read Check item Action Check whether an analog signal line is disconnected from the temperature Visually check signal lines and correctly connect analog signal lines. input module. Check whether a thermocouple and compensation lead wire are correctly Correctly connect a thermocouple or compensation lead wire to the connected to the thermocouple input module.
  • Page 84: A Measured Temperature Value Is Not Converted To An Expected Value

    A measured temperature value is not converted to an expected value Check item Action Check whether the input range setting is correct. Check that the set input range is corresponding to the connected thermocouple or connected resistance temperature detector using the following buffer memory areas.
  • Page 85: List Of Error Codes

    List of Error Codes If an error occurs during operation, a temperature input module stores the error code into 'Latest error code' (Un\G0) of the buffer memory. In addition, 'Error flag' (XF) turns on. Turning on 'Error clear request' (YF) clears the error code in 'Latest error code' (Un\G0) and turns off 'Error flag' (XF).
  • Page 86 Error code Error name Description and cause Action 190H Range setting range error ■For the thermocouple input module ■For the thermocouple input module • A value out of the range is set in CH Range • Set a value of 0 to 7 in CH Range setting setting (Thermocouple type).
  • Page 87 Error code Error name Description and cause Action 1BH Process alarm upper lower The values not satisfying the following condition are Set CH Process alarm upper upper limit value to limit value setting range error set in CH Process alarm upper upper limit value to CH...
  • Page 88 Error code Error name Description and cause Action 1E6H User range data invalid (CH An invalid value is set for the offset/gain setting of Perform the offset/gain setting again for the identification enabled, the CH. channels where the error has occurred. range setting of the CH If the error occurs again, the possible cause is a where the error occurred is...
  • Page 89: List Of Alarm Codes

    List of Alarm Codes If an alarm occurs during operation, a temperature input module stores the alarm code into 'Latest alarm code' (Un\G2) of the buffer memory. Turning on Error clear request (YF) clears the alarm code in 'Latest alarm code' (Un\G2). The following table lists the alarm codes that may be stored.
  • Page 90: Appendices

    APPENDICES Appendix 1 Module Label The functions of the temperature input module can be set by using module labels. Module labels of I/O signals The module label name of an I/O signal is defined with the following structure: "Module name"_"Module number".b"Label name" or "Module name"_"Module number".b"Label name"_D R60TDG_1.bModuleREADY ■Module name The character string of a module model name is given.
  • Page 91 ■Data format The string that represents the data size of a buffer memory area is given. Each data format is as follows: Data format Description Word [Unsigned]/Bit string [16-bit] Word [Signed] ■Label name The label identifier unique to a module is given. ■_D This string indicates that the module label is for the direct access.
  • Page 92: Appendix 2 I/O Signals

    Appendix 2 I/O Signals List of I/O signals The following table lists the I/O signals of a temperature input module. For details on the I/O signals, refer to the following. Page 91 Details of input signals Page 97 Details of output signals •...
  • Page 93: Details Of Input Signals

    Details of input signals The following describes the details of the input signals for a temperature input module which are assigned to the CPU module. The I/O numbers (X/Y) described in this section are for the case when the start I/O number of a temperature input module is set to 0.
  • Page 94 Offset/gain setting mode status flag ■In the offset/gain setting mode When registering the value, which has been adjusted with the offset/gain setting, use Offset/gain setting mode status flag (XA) as an interlock condition to turn on and off 'User range write request' (YA). When the offset/gain setting is configured from the offset/gain setting window of an engineering tool, the setting is performed properly on the window.
  • Page 95 Channel change completed flag When changing a channel to perform the offset/gain setting, use Channel change completed flag (XB) as an interlock condition to turn on and off 'Channel change request' (YB). When the offset/gain setting is configured from the offset/gain setting window of an engineering tool, the setting is performed properly on the window.
  • Page 96 Disconnection detection signal ■Turning on Disconnection detection signal (XC) Disconnection detection signal (XC) turns on when disconnection is detected for the channel where Enable (0) is set in 'CH1 Disconnection detection enable/disable setting' (Un\G530) and the temperature conversion is enabled. When 'Disconnection detection signal' (XC) turns on, the following operations are performed.
  • Page 97 Alert output signal Alert output signal (XD) turns on when the process alarm or rate alarm has been detected. When the alert output function is disabled for all channels, 'Alert output signal' (XD) is always off. ■Process alarm • Alert output signal (XD) turns on when the measured temperature value exceeds the range set for 'CH1 Process alarm upper upper limit value' (Un\G514) to 'CH1 Process alarm lower lower limit value' (Un\G520).
  • Page 98 Error flag Error flag (XF) turns on when an error has occurred. Controlled by the temperature input module Controlled by the program 'Latest error code' (Un\G0), Error or alarm 'Latest alarm code' (Un\G2) 'Error flag' (XF) 'Error clear request' (YF) or 'Operating condition setting request' (Y9) ■Turning off 'Error flag' (XF)
  • Page 99: Details Of Output Signals

    Details of output signals The following describes the details of the output signals for a temperature input module which are assigned to the CPU module. The I/O numbers (X/Y) described in this section are for the case when the start I/O number of a temperature input module is set to 0.
  • Page 100 Error clear request Turn on and off Error clear request (YF) to clear 'Error flag' (XF), 'Disconnection detection signal' (XC), 'Latest error code' (Un\G0), and 'Latest alarm code' (Un\G2). For the timing of turning the signal on and off, refer to the following. •...
  • Page 101: Appendix 3 Buffer Memory Areas

    Appendix 3 Buffer Memory Areas List of buffer memory areas This section lists the buffer memory areas of the temperature input module. For details on the buffer memory, refer to the following. Page 114 Details of buffer memory addresses The buffer memory areas of the temperature input module are classified into the data types described below. Data type Description Setting data...
  • Page 102 In R mode ■Un\G0 to Un\G399 Address Address Name Default value Data type Auto refresh (decimal) (hexadecimal)  Latest error code Monitor  Latest address of error history Monitor  Latest alarm code Monitor  Latest address of alarm history Monitor ...
  • Page 103 ■Un\G400 to Un\G3599 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  1000 1200 1400 1600 1800 CH Measured temperature value Monitor (190H) (258H) (320H) (3E8H) (4B0H) (578H) (640H) (708H) 1001 1201 1401 1601 1801 System area  ...
  • Page 104 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  1048 1248 1448 1648 1848 CH Trigger generation time Monitor (1C0H) (288H) (350H) (418H) (4E0H) (5A8H) (670H) (738H) (Millisecond)    449 to 649 to 849 to 1049 to 1249 to 1449 to 1649 to...
  • Page 105 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  1130 1330 1530 1730 1930 CH Disconnection detection Setting (212H) (2DAH) (3A2H) (46AH) (532H) (5FAH) (6C2H) (78AH) enable/disable setting 1131 1331 1531 1731 1931 CH Conversion setting at Setting ...
  • Page 106 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  1164 1364 1564 1764 1964 CH Gain temperature setting Setting (234H) (2FCH) (3C4H) (48CH) (554H) (61CH) (6E4H) (7ACH) value    565 to 765 to 965 to 1165 to 1365 to 1565 to 1765 to...
  • Page 107 ■Error history (Un\G3600 to Un\G3759) Address Address Name Default Data type Auto (decimal) (hexadecimal) value refresh 3600 E10H Error history 1 Error code Monitor  3601 E11H Error time First two Last two digits of the digits of the year year 3602 E12H...
  • Page 108 ■Alarm history (Un\G3760 to Un\G3999) Address Address Name Default Data type Auto (decimal) (hexadecimal) value refresh  3760 EB0H Alarm history 1 Alarm code Monitor 3761 EB1H Alarm time First two Last two digits of the digits of the year year 3762 EB2H...
  • Page 109 ■Offset/gain setting (Un\G4000 to Un\G9999) Address Name Default Data Auto Decimal (hexadecimal) value type refresh    4000 to 4003 System area (FA0H to FA3H) 4004 4016 4028 4040 4052 4064 4076 4088 CH Factory default setting User  (FA4H) (FB0H) (FBCH)
  • Page 110 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  4132 4134 4136 4138 4140 4142 4144 4146 CH Offset/gain setting mode Setting (1024H) (1026H) (1028H) (102AH) (102CH) (102EH) (1030H) (1032H) (offset specification)  4133 4135 4137 4139 4141 4143 4145 4147...
  • Page 111 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  46 (2EH) Alert output setting (Process FFFFH Setting alarm) Alert output setting (Rate alarm)  47 (2FH) Alert output flag (Process alarm) Monitor  48 (30H) Alert output flag (Rate alarm) Monitor 49 (31H) Disconnection detection flag...
  • Page 112 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  CH User range setting offset User (C2H) (CEH) (DAH) (E6H) (F2H) (FEH) (10AH) (116H) value (L) range setting  CH User range setting offset User (C3H) (CFH) (DBH) (E7H) (F3H) (FFH) (10BH)
  • Page 113 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  1016 1017 1018 1019 1020 1021 1022 1023 CH Logging hold flag Monitor (3F8H) (3F9H) (3FAH) (3FBH) (3FCH) (3FDH) (3FEH) (3FFH) 1024 1025 1026 1027 1028 1029 1030 1031 CH...
  • Page 114 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  1820 to 1829 (71CH to 725H) Error history 2 Monitor 1830 to 1839 (726H to 72FH) Error history 3 Monitor   1840 to 1849 (730H to 739H) Error history 4 Monitor ...
  • Page 115 Address Name Default Data Auto Decimal (hexadecimal) value type refresh  6000 to 6999 (1770H to 1B57H) CH2 Logging data Monitor 7000 to 7999 (1B58H to 1F3FH) CH3 Logging data Monitor   8000 to 8999 (1F40H to 2327H) CH4 Logging data Monitor 9000 to 9999 (2328H to 270FH) CH5 Logging data...
  • Page 116: Details Of Buffer Memory Addresses

    Details of buffer memory addresses This section describes the details on the buffer memory addresses of the temperature input module. This section describes buffer memory addresses for CH1. Latest error code The latest error code detected in the temperature input module is stored. For details on the error codes, refer to the following. Page 83 List of Error Codes ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 117 Interrupt factor detection flag [n] The detection status of the interrupt factor is stored. Monitor value Description No interrupt factor Interrupt factor When an interrupt factor occurs, an interrupt request is sent to the CPU module at the same time as 'Interrupt factor detection flag [n]' (Un\G4 to Un\G19) turns to Interrupt factor (1).
  • Page 118 Alert output flag (Process alarm lower limit) The lower limit alarm of the process alarm can be checked for each channel. b15 b14 b13 b12 b11 b10 b9 (1) 0: Normal, 1: Alarm ON (2) The values of b8 to b15 are fixed to 0. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 119 Alert output flag (Rate alarm upper limit) The upper limit alarm of the rate alarm can be checked for each channel. b15 b14 b13 b12 b11 b10 b9 (1) 0: Normal, 1: Alarm ON (2) The values of b8 to b15 are fixed to 0. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 120 Alert output flag (Rate alarm) [Q compatible mode] When the Q compatible mode function is used, the upper/lower limit alarm of the rate alarm can be checked. b15 b14 b13 b12 b11 b10 b9 CH8 CH8 CH6 CH5 CH4 CH4 CH2 CH1 (1) 0: Normal, 1: Alarm ON ■Buffer memory address...
  • Page 121 Disconnection detection flag The status of disconnection can be checked for each channel. b15 b14 b13 b12 b11 b10 b9 (1) 0: Normal, 1 Disconnection detection (2) The values of b8 to b15 are fixed to 0. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 122 Cold junction compensation setting status The setting of cold junction compensation, which is set in 'Cold junction compensation with/without setting' (Un\G298), can be checked. Monitor value Description With the cold junction compensation setting Without the cold junction compensation setting ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 123 Level data 0 to 9 This area stores data to be monitored when a level trigger of the logging function is used. Ten types of data are available: 'Level data 0' (Un\G90) to 'Level data 9' (Un\G99). These are useful, for example, to generate triggers while monitoring the values of devices other than the temperature input module.
  • Page 124 Interrupt factor reset request [n] An interrupt factor reset request is sent. Setting value Setting content No reset request Reset request When Reset request (1) is set to 'Interrupt factor reset request [n]' (Un\G156 to Un\G171) corresponding to the interrupt factor, the interrupt factor corresponding to the specified interrupt is reset.
  • Page 125 Condition target setting [n] Set an interrupt factor to be detected. Setting value Setting content Disable Error flag (XF) Alert output flag (Process alarm) (CH specification) Alert output flag (Rate alarm) (CH specification) Disconnection detection (CH specification) Conversion completed flag (CH specification) Logging hold flag (CH specification) Logging read (CH specification) Setting a value other than the above causes a condition target setting range error (error code: 181H).
  • Page 126 Condition target channel setting [n] Set a channel where an interrupt is detected. Setting value Setting content All channels When a factor for the channel specification is set to 'Condition target setting [n]' (Un\G232 to Un\G247), an interrupt factor in the channel set by this area is monitored.
  • Page 127 Mode switching setting Set a setting value for the mode to be switched. Switching mode Setting value Buffer memory address Normal mode 5260H 4144H Offset/gain setting mode 4144H 5260H ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name Mode switching setting 296, 297...
  • Page 128 Disconnection detection automatic clear enable/disable setting Set whether to enable or disable an automatic clear of disconnection detection of the disconnection detection function. Setting value Description Enable Disable Setting a value other than in the table above results in operation with Disable (1). ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 129 CH1 Scaling value The value after scale conversion by means of the scaling function is stored in 16-bit signed binary. b15 b14 b13 b12 b11 b10 b9 (1) Data section (2) Sign bit 0: Positive, 1: Negative ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 130 CH1 Range setting monitor (Thermocouple type) The value of thermocouple type set in 'CH1 Range setting (Thermocouple type)' (Un\G598) can be checked. This description is specific to the thermocouple input module. Monitor value Description K thermocouple E thermocouple J thermocouple T thermocouple B thermocouple R thermocouple...
  • Page 131 CH1 Range setting monitor (Resistance temperature detector type) The value of resistance temperature detector type set in 'CH1 Range setting (Resistance temperature detector type)' (Un\G598) can be checked. This description is specific to the RTD input module. Monitor value Description Pt100 (-200 to 850) Pt100 (-20 to 120) JPt100 (-180 to 600)
  • Page 132 CH1 Range setting monitor (offset/gain setting) The offset/gain values set in 'CH1 Range setting (Thermocouple type)' (Un\G598) or 'CH1 Range setting (Resistance temperature detector type)' (Un\G598) can be checked. Monitor value Description Factory default setting User range setting ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 133 CH1 Head pointer The buffer memory address of the oldest data in CH1 Logging data (Un\G10000 to Un\G10999) can be checked with this buffer memory area. The offset value at the start address of CH1 Logging data (Un\G10000 to Un\G10999) is stored. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 134 CH1 Latest pointer The buffer memory address of the latest data in CH1 Logging data (Un\G10000 to Un\G10999) can be checked with this buffer memory area. The offset value at the start address of CH1 Logging data (Un\G10000 to Un\G10999) is stored. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 135 CH1 Trigger pointer Of CH1 Logging data (Un\G10000 to Un\G10999), the buffer memory address where the data at the time of a hold trigger event is stored can be checked. The difference between the buffer memory address where the data at the time of a hold trigger event and the start address in CH1 Logging data (Un\G10000 to Un\G10999) is stored.
  • Page 136 CH1 Logging read points monitor value The number of the actual logging read points is stored. When 'Operating condition setting request' (Y9) is turned on and off, a value is not stored in the channel where the logging read function is disabled. For details on the logging function, refer to the following.
  • Page 137 CH1 Trigger generation time The time when a trigger is generated is recorded. For details on the logging function, refer to the following. Page 40 Logging Function b8 b7 First two digits of the year Last two digits of the year 'CH1 Trigger generation time (First/Last two digits of the year)' (Un\G444) Month 'CH1 Trigger generation time (Month/Day)' (Un\G445)
  • Page 138 CH1 Logging hold request Use this buffer memory area as a trigger to hold (stop) logging at any timing during the logging. For details on the logging function, refer to the following. Page 40 Logging Function Logging hold request Setting value Setting a value other than the above causes a logging hold request range error (error code: 1D7H).
  • Page 139 CH1 Conversion enable/disable setting Set whether to enable or disable the temperature conversion. For details on the conversion enable/disable setting function, refer to the following. Page 18 Conversion Enable/Disable Setting Function Setting value Setting content Conversion enable Conversion disable Setting a value other than the above results in Conversion disable (1). ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 140 Conversion enable/disable setting [Q compatible mode] Set whether to enable or disable the temperature conversion with the Q compatible mode function used. b15 b14 b13 b12 b11 b10 b9 (1) 0: Conversion enable, 1: Conversion disable (2) The values of b8 to b15 are fixed to 0. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 141 Averaging process specification [Q compatible mode] For Q compatible mode, set which processing to use, sampling processing, averaging processing, or filter processing. … b12 b11 … b8 b7 … … … b12 b11 … b8 b7 … … (1) Averaging process specification (Un\G24) (setting range CH1 to CH4) (2) Averaging process specification (Un\G25) (setting range CH5 to CH8) ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 142 • Set a primary delay filter constant for the primary delay filter. The value of the time constant (ms) is the product of the primary delay filter constant and the sampling cycle. • Since the default value is 0, change the setting value according to the processing method. •...
  • Page 143 CH1 Alert output setting (Rate alarm) Set whether to enable or disable the alert output of the rate alarm. For details on the alert output function, refer to the following. Page 27 Alert Output Function Setting value Setting content Enable Disable Setting a value other than the above causes an alert output setting (Rate alarm) range error (error code: 1B8H).
  • Page 144 CH1 Process alarm upper upper limit value Set an upper upper limit value of the alert output function (Process alarm). For details on the alert output function, refer to the following. Page 27 Alert Output Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 145 CH1 Process alarm upper lower limit value Set an upper lower limit value of the alert output function (Process alarm). For details on the alert output function, refer to the following. Page 27 Alert Output Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 146 CH1 Process alarm lower upper limit value Set a lower upper limit value of the alert output function (Process alarm). For details on the alert output function, refer to the following. Page 27 Alert Output Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 147 CH1 Process alarm lower lower limit value Set a lower lower limit value of the alert output function (Process alarm). For details on the alert output function, refer to the following. Page 27 Alert Output Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 148 CH1 Rate alarm alert detection cycle setting Set the cycle at which the change rate of measured temperature values is checked. The value of the cycle to detect a rate alarm alert is the product of the value in 'CH1 Rate alarm alert detection cycle setting' (Un\G522) and the conversion cycle.
  • Page 149 CH1 Rate alarm lower limit value Set a lower limit on the change rate of measured temperature values for rate alarm detection. For details on the alert output function, refer to the following. Page 27 Alert Output Function ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 150 Disconnection detection enable/disable setting [Q compatible mode] Set whether to enable or disable the disconnection detection function with the Q compatible mode function used. b15 b14 b13 b12 b11 b10 b9 (1) 0: Disconnection detection enable, 1: Disconnection detection disable (2) The values of b8 to b15 are fixed to 0.
  • Page 151 Conversion setting at disconnection detection [Q compatible mode] Set what value is to be stored in 'CH1 Measured temperature value' (Un\G11) at the time of disconnection detection with the Q compatible mode function used. … b12 b11 … b8 b7 …...
  • Page 152 CH1 Logging enable/disable setting Set whether to enable or disable the logging function. For details on the logging function, refer to the following. Page 40 Logging Function Setting value Setting content Enable Disable Setting a value other than the above causes a logging enable/disable setting range error (error code: 1D0H). ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 153 CH1 Logging cycle setting value Set a cycle for storing the logging data. For details on the logging function, refer to the following. Page 40 Logging Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 154 CH1 Post-trigger logging points Set a number of data points collected for the time period from the occurrence of a hold trigger to the logging stop. For details on the logging function, refer to the following. Page 40 Logging Function ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 155 CH1 Trigger data Set a buffer memory address to be monitored using a level trigger. Set the buffer memory address where the target data for monitoring is stored. For details on the logging function, refer to the following. Page 40 Logging Function ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 156 CH1 Trigger setting value Set a level at which a level trigger is generated. For details on the logging function, refer to the following. Page 40 Logging Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 157 CH1 Logging read points setting value An interrupt is generated to the CPU module each time the number of data logging reaches a predetermined number of points. For details on the logging function, refer to the following. Page 40 Logging Function ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 158 Scaling enable/disable setting [Q compatible mode] When the Q compatible mode function is used, set whether to enable or disable the scaling. b15 b14 b13 b12 b11 b10 b9 (1) 0: Scaling enabled, 1: Scaling disabled (2) The values of b8 to b15 are fixed to 0. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 159 CH1 Scaling range lower limit value Set a lower limit value for the range of the scale conversion. For details on the scaling function, refer to the following. Page 23 Scaling Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 160 CH1 Scaling width lower limit value Set a lower limit on the width of scale conversion. For details on the scaling function, refer to the following. Page 23 Scaling Function ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH...
  • Page 161 CH1 Offset temperature setting value As Channel change request (YB) is turned on and off in offset/gain setting mode, the measured temperature value is corrected by a value written in this area. Specify the value of a 16-bit signed binary number. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 162 CH1 Gain temperature setting value As Channel change request (YB) is turned on and off in offset/gain setting mode, the measured temperature value is corrected by a value written in this area. Specify the value of a 16-bit signed binary number. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 163 CH1 Range setting (Thermocouple type) This area is used to set up the type of thermocouple. Set up the type according to the thermocouple in use. This description is specific to the thermocouple input module. Setting value Description K thermocouple E thermocouple J thermocouple T thermocouple...
  • Page 164 CH1 Range setting (Resistance temperature detector type) This area is used to set up the type of resistance temperature detector. Set up the type according to the resistance temperature detector in use. This description is specific to the RTD input module. Setting value Description Pt100 (-200 to 850)
  • Page 165 CH1 Range setting (offset/gain setting) This area is used to set up the offset/gain setting. Setting value Description Factory default setting User range setting Setting a value other than the above causes a range setting range error (error code: 190H). ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 166 Error history Up to 16 errors that occurred in the module are recorded. b8 b7 Error code Un\G3600 First two digits of the year Last two digits of the year Un\G3601 Month Un\G3602 Hour Minute Un\G3603 Second Day of the week Un\G3604 Millisecond (higher-order digits) Millisecond (lower-order digits)
  • Page 167 Alarm history Up to 16 alarms that occurred in the module are recorded. b8 b7 Un\G3760 Alarm code First two digits of the year Last two digits of the year Un\G3761 Month Un\G3762 Hour Minute Un\G3763 Second Day of the week Un\G3764 Millisecond (higher-order digits) Millisecond (lower-order digits)
  • Page 168 CH1 User range setting This area restores the offset/gain setting value in user range setting. ■Buffer memory address The following shows the buffer memory address of this area. Buffer memory name CH Factory default setting offset value (L) 4004 4016 4028 4040 4052...
  • Page 169 Buffer memory name CH User range setting thermoelectromotive force offset value (H) (in Q compatible mode) (for the thermocouple input module) CH User range setting offset resistance value (H) (in Q compatible mode) (for the RTD input module) CH User range setting thermoelectromotive force gain value (L) (in Q compatible mode) (for the thermocouple input module) CH...
  • Page 170 CH1 Offset/gain setting mode Specify the channel where the offset/gain setting is adjusted. • Offset/gain setting mode (offset specification): Channel to adjust the offset • Offset/gain setting mode (gain specification): Channel to adjust the gain Setting Setting content Disable Setting channel Set either the offset specification or the gain specification to Setting channel (1), and the other to Disable (0).
  • Page 171 Offset/gain setting mode [Q compatible mode] When the Q compatible mode function is used, specify the channel where the offset/gain setting is adjusted. b15 b14 b13 b12 b11 b10 b9 (1) 0: Disable, 1: Setting channel (2) The values of b8 to b15 are fixed to 0. ■Buffer memory address The following shows the buffer memory address of this area.
  • Page 172 CH1 Logging data This area stores the data logged by the logging function. Up to 1000 points of data can be stored per channel. After the number of stored data points reaches 1000, data collection continues with the data overwritten from the head. For details on the logging function, refer to the following.
  • Page 173: Appendix 4 Dedicated Instructions

    Appendix 4 Dedicated Instructions Instruction list The following table lists the dedicated instructions that can be used in a temperature input module. Instruction Description G(P).OFFGAN Switches normal mode to offset/gain setting mode. Switches offset/gain setting mode to normal mode. G(P).OGLOAD Reads out the offset/gain setting value in the user range setting to write it into the CPU module.
  • Page 174 MEMO APPX Appendix 4 Dedicated Instructions...
  • Page 175: Appendix 5 Operation Examples Of When The Remote Head Module Is Mounted

    Appendix 5 Operation Examples of When the Remote Head Module Is Mounted This section describes operation examples of when the remote head module is mounted System configuration example The following system configuration is used to explain an example of operation. (1) Master station (Network number 1, station number 0) •...
  • Page 176: Setting In The Master Station

    Setting in the master station Connect the engineering tool to the CPU module of the master station and set parameters. Create the project with the following settings. [Project]  [New] Click the [Setting Change] button and set the module to use the module label. Click the [OK] button in the following window to add the module labels of the CPU module.
  • Page 177 Add the master/local module with the following settings. [Navigation window]  [Parameter]  [Module Information]  Right-click  [Add New Module] Click the [OK] button in the following window to add the module labels of the master/local module. Set "Required Settings" of the module parameter of the master/local module as shown below. [Navigation window] ...
  • Page 178 Set "Network Configuration Settings" of the module parameter of the master/local module as shown below. [Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Basic Settings]  [Network Configuration Settings] Set "Refresh Setting" of the module parameter of the master/local module as shown below. [Navigation window] ...
  • Page 179: Setting In The Intelligent Device Station

    Setting in the intelligent device station Connect the engineering tool to the remote head module of the intelligent device station and set parameters. Create the project with the following settings. [Project]  [New] Set "Network Required Setting" of "CPU Parameter" of the remote head module as shown below. [Navigation window] ...
  • Page 180 Configure the setting not to use the module labels. Set "Basic setting" of the module parameter of the temperature input module as shown below. [Navigation window]  [Parameter]  [Module Information]  [R60TD8-G]  [Basic setting] APPX Appendix 5 Operation Examples of When the Remote Head Module Is Mounted...
  • Page 181 Set "Application setting" of the module parameter of the temperature input module as shown below. [Navigation window]  [Parameter]  [Module Information]  [R60TD8-G]  [Application setting] APPX Appendix 5 Operation Examples of When the Remote Head Module Is Mounted...
  • Page 182 Set "Refresh settings" of the module parameter of the temperature input module as shown below. [Navigation window]  [Parameter]  [Module Information]  [R60TD8-G]  [Refresh settings] Write the set parameters to the remote head module on the intelligent device station. Then reset the remote head module or power off and on the system.
  • Page 183: Checking The Network Status

    Checking the network status After setting parameters to the master station and the intelligent device station, check whether data link is normally performed between the master station and the intelligent device station. Check the network status using the CC-Link IE Field Network diagnostics of the engineering tool.
  • Page 184 Common program The following figure shows an example of the program to check the data link status of the remote head module (station number 1). Checks the data link status of the remote head module (station number 1). Add the MCR instruction shown below to the last of the program. Program example 1 The following figure shows an example of the program to read measured temperature values of CH1, CH3, and CH7 and scaling values of CH5 and save them.
  • Page 185 Program example 4 The following figure shows an example of the program to clear Disconnection detection flag, Error flag, and Latest error code if disconnection is detected in CH7 or an error occurs in any of the channels. (156) Performs a processing of when disconnection was detected in CH7. (171) Turns on 'Error clear request' (Y100F).
  • Page 186: Appendix 6 Using The Module In The Redundant System With Redundant Extension Base Unit

    Appendix 6 Using the Module in the Redundant System with Redundant Extension Base Unit This chapter describes restrictions and precautions for using a temperature input module that is mounted on the extension base unit in the redundant system. Restrictions on functions and specifications Functions Function Restriction...
  • Page 187: Precautions

    Precautions When configuring the offset/gain setting Connect the engineering tool to the CPU module of the control system. The engineering tool cannot recognize a temperature input module if it is connected to the CPU module of the standby system. Program examples Unless otherwise specified, program examples provided in this manual and the following manual are for when the module is used in the single CPU system or in the multiple CPU system.
  • Page 188: Index

    INDEX . .130 CH1 Range setting monitor (offset/gain setting) CH1 Range setting monitor (Resistance temperature ......165 Alarm history .
  • Page 189 ... . . 114 Latest address of alarm history ... . . 114 Latest address of error history ..... . 114 Latest alarm code .
  • Page 190: Revisions

    Japanese manual number: SH-081494-C This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
  • Page 191: Warranty

    WARRANTY Please confirm the following product warranty details before using this product. 1. Gratis Warranty Term and Gratis Warranty Range If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company.
  • Page 192: Trademarks

    TRADEMARKS The company names, system names and product names mentioned in this manual are either registered trademarks or trademarks of their respective companies.   In some cases, trademark symbols such as ' ' or ' ' are not specified in this manual. SH(NA)-081495ENG-C...
  • Page 194 SH(NA)-081495ENG-C(2010)MEE MODEL: R60TDG-R60RDG-U-OU-E MODEL CODE: 13JX34 HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN NAGOYA WORKS : 1-14 , YADA-MINAMI 5-CHOME , HIGASHI-KU, NAGOYA , JAPAN When exported from Japan, this manual does not require application to the Ministry of Economy, Trade and Industry for service transaction permission.