Summary of Contents for Honeywell 954 SmartServo FlexLine

  • Page 1 Installation Manual 954 SmartServo FlexLine...
  • Page 2 Head Office - Delft, The Netherlands Honeywell Enraf Delftechpark 39, 2628 XJ Delft PO Box 812, 2600 AV Delft The Netherlands Tel.: +31 (0)15 2701 100 Fax: +31 (0)15 2701 111 E-mail: [email protected] Website: www.honeywellprocess.com Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 3 About this manual This manual provides information related to installation of the 954 SmartServo FlexLine. For servicing of the device refer to the 954 SmartServo FlexLine Service Manual listed below in References. For Safety instructions and procedures refer to the 954 SmartServo FlexLine Safety manual listed below in References.
  • Page 4 4417340 954 Service Manual 4417342 954 Safety Manual Patents The Honeywell 954 SmartServo FlexLine servo-based level gauge is covered by the following patents: US2017307461 (A1) 2017-10-26, US2018058960 (A1) 2018-03-01 WO2017062413 (A1) 2017-04-13, WO2018044518 (A1) 2018-03-18 Part No: 4417341 Revision 10...
  • Page 5: Table Of Contents

    General ................................12 General Precautions .............................. 14 Accordance to Regulations ............................ 15 2.9.1. Explosion Safety ..............................15 PRINCIPAL OF SERVO MEASUREMENT.......................... 17 Principle of Measurement ............................ 17 3.1.1. Level Measurement ............................18 Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 6 Relative Density..............................18 MECHANICAL INSTALLATION ............................19 Preparation for Transportation of the Gauge ....................... 19 Process Connection ............................... 19 Orientation of 954 SmartServo FlexLine Gauge on Tank ..................20 Bolts ..................................21 Mounting a Pressure Gauge Set..........................21 Grounding ................................22 ELECTRICAL INSTALLATION ............................
  • Page 7 Figure 4 Principle of Measurement ............................17 Figure 5 Orientation of the Gauge on a Tank (top view) ...................... 20 Figure 6 Mounting a Pressure Gauge Set on a 954 SmartServo FlexLine Gauge ..............22 Figure 7 Example of Flange Ground ............................22 Figure 8 Optional Blocking Devices ............................
  • Page 8: General

    The 954 SmartServo FlexLine can integrate data from other measurement devices, such as temperature RTD sensors. Data from 954 SmartServo FlexLine and connected sensors can be communicated to host computer systems via a variety of industry standard protocols.
  • Page 9: Safety And Security

    2. SAFETY AND SECURITY General The 954 SmartServo FlexLine is a servo-based level gauge which is used in inventory measurement systems. It can also be used to interface with other systems and sensors such as pressure, density, or temperature sensors.
  • Page 10: Safety Instructions

    NOTE: See EN IEC 60079-14 or NEC (NFPA70). 2.3.5. Additional Information If you require additional information, contact Honeywell or its representative. 2.3.6. Environmental Conditions Observe the environmental conditions for the temperature and the pressure. Ambient Operating Temperature Range from -40°C (-40°F) up to +65°C (149°F).
  • Page 11: Liability

    Neglect of the safety regulations for handling tools and use of electricity. The contents, descriptions and specifications in this Installation Manual are subject to change without notice. Honeywell accepts no responsibility for any errors that may appear in this Installation Manual.
  • Page 12: Personal Safety

    WARNING! Treat the O-ring groove surfaces of the housing with care. Keep the screw threads of the lids free of dirt. Both O-rings must be present and undamaged. Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 13 Required Skills WARNING! The technician must be trained and qualified to safely install equipment in hazardous areas. The technician must work in accordance with national, local and company regulations. Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 14: General Precautions

    During transport of the gauge the motor block should be locked. This is for protection of the weighing system. Motor Locked Motor Unlocked Figure 2 Unlocking the 954 SmartServo FlexLine Motor Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 15: Accordance To Regulations

    CAUTION! The box in which the 954 SmartServo FlexLine arrives also contains the measuring drum. This is a precision measuring device and shall only be installed by a qualified commissioning engineer. Accurate measurement requires an undamaged and clean drum. Figure 3 Measuring Drum Special Tools: Screw driver for Hex Allen-key screws M4 (length min.
  • Page 16 NEMA 4X Certificate no.: FM19US0012  Class I, Division 1, Group C,D Ex db eb h [ia Ga] IIB T6 Ga/Gb Ta = -40°C to +65°C Encl 4 Certificate no.: 70210644 Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 17: Principal Of Servo Measurement

    If a discrepancy exists between measured and desired value, an advanced software control module adjusts the position of the stepper motor. Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 18: Level Measurement

    The software for the density measurement is available as an option. Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 19: Mechanical Installation

    Process Connection The 954 SmartServo FlexLine can be ordered with raised face or flat face flange. Select gasket that is suitable for flange type, maximum pressure and product to be stored. Mount instrument flange horizontally.
  • Page 20: Orientation Of 954 Smartservo Flexline Gauge On Tank

    Orientation of 954 SmartServo FlexLine Gauge on Tank Mount the gauge in one of the following two ways: Figure 5 Orientation of the Gauge on a Tank (top view) On a stilling well or guide pole, the orientation of the gauge may be chosen freely.
  • Page 21: Bolts

    WARNING! Use the Hoisting Eye for lifting up the 954 SmartServo FlexLine versions above 18 kg (see picture Appendix A) Bolts Secure the gauge adapter by using appropriate bolts. *) Flange type Number of bolts Diameter x minimum length NW50, ND6...
  • Page 22: Grounding

    Figure 6 Mounting a Pressure Gauge Set on a 954 SmartServo FlexLine Gauge Grounding WARNING! For proper grounding of the 954 SmartServo FlexLine, install a copper strip under one of the flange bolts for each flange. Place shark rings between flange and strip (Figure 7). Figure 7 Example of Flange Ground...
  • Page 23: Electrical Installation

    WARNING! The instrument may not be opened when an explosion atmosphere may be present. Failure to do so may cause danger to persons or damage the equipment. Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 24: Safety

    After closing the covers, do not forget to place the blocking devices. Safety 5.3.1. General Relative Density WARNING! Make sure the power to the device is switched OFF, before you open the cover of the device. Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 25: Installing The Cable Glands And Stopping Plugs

    Only use Ex e or flameproof certified materials of an appropriate IP value. CAUTION! Improper installation of cable glands or stopping plugs will invalidate the Ex approval of the 954 SmartServo FlexLine. 5.4.1. Cable Glands Use Ex e or Ex d 3/4" NPT cable glands (or where applicable equivalent conduit connections) with an appropriate IP value.
  • Page 26: Installing The Glands, Conduits And Stopping Plugs

    Use explosion proof (Ex d) conduits with an appropriate IP value. See the type plate on the device. WARNING! If the 954 SmartServo FlexLine is installed in a hazardous area: Metal conduits must be used, size 3/4”. Stopper boxes must be installed within 45 cm (18”) of the device to seal the cabling in the conduit.
  • Page 27: Electrical Connections

    CAUTION! Cables must always comply with the defined cable specifications. 5.6.1. Grounding The 954 SmartServo FlexLine housing must be properly grounded to the ground reference (generally the tank), according to local regulations. This is a safety grounding requirement. WARNING! When measuring the ground resistance, use a suitable instrument that is approved for use in hazardous areas.
  • Page 28 Connect the wiring to the terminals with the numbers as shown in the tables in the following sections. 954 SmartServo FlexLine Board Overview CAN-Servo, CAN-PSS, CAN-HART, and CAN-LCD boards are part of each 954 SmartServo FlexLine device. All remaining boards mentioned in this Installation Manual are optional (see Figure 9).
  • Page 29 Figure 9 954 SmartServo FlexLine Board Overview Non-intrinsically Safe Connections The non-intrinsically safe connections are connected to the grey wiring terminal. If local and or national regulations allow, the power supply, Enraf fieldbus, and hardware relay outputs may be combined into one, unshielded, cable.
  • Page 30 Lay-out Terminal Compartment The terminal compartment on top of the 954 SmartServo FlexLine is divided into a non-intrinsically safe and an intrinsically safe part. Cable entries are ¾” NPT. Figure 10 Intrinsically Safe and Non-Intrinsically Safe Cable Entries The non-intrinsically safe cabling may only enter at the two right hand side cable entries (Figure 10).
  • Page 31 Non-intrinsically Safe Cabling Mains cabling: Must be suitable for the 954 SmartServo FlexLine power rating and, moreover, approved for the use in hazardous areas. Honeywell Enraf field bus lines may be interchanged. If local regulations allow, mains and Honeywell Enraf field bus lines may share one cable.
  • Page 32 Cable Specifications Cable specifications Suitable for the 954 SmartServo FlexLine power rating, and approved for Type use in hazardous areas Label Parameters 00.
  • Page 33 Vmax = 125 Vac, Imax = 0.5 A, via double isolated transformer 16. Ry2_a Vmax = 110 Vdc, Imax = 0.3 A, Pmax = 30 W 17. Ry2_b NO/NC by factory jumper (default = NO) Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 34 Vmax = 40 Vdc, Imax = 2 A Pmax = 500 W Vmax = 250 Vac, Imax = 2 A 56. DO2_a 57. DO2_b Vmax = 40 Vdc, Imax = 2 A Pmax = 500 W Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 35 Ensure the end user cannot touch these wires when energized. Uo = 23.1 V Io = 124 mA Po = 0.6 W Co = 1.0 μF Lo = 9 mH Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 36 Li = 16 μH Lo = 9 mH The I/O shall not be accessible or shall be isolated in the end use. Ensure the end user cannot touch these wires when energized. Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 37 VITO is present, can be connected to the HART connection. CAUTION! Before connecting the HART devices: Make sure the sum of the start-up currents fits the parameters. Figure 12 Topology Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 38 RTD, MRT, MPT Temperature Measurement (CAN-RTD) Cable specifications Shielded. R max = 100 Ω / line Type Maximum length 150 meter RTD, 4-Wire Connection RTD, 3-Wire Connection Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 39: Finishing Installation

    Make sure the surface of the O-ring grooves of the housing are clean and the O-rings are not damaged before assembling the lids to the 954 SmartServo FlexLine housing. Make sure that the both lids (used for terminal block and board compartments) do not squeeze any cables during the assembly.
  • Page 40: External Fusing

    NOTE: If the 954 SmartServo FlexLine is installed in a hazardous area, Ex d certified conduit seals must be applied directly at the wall of the 954 SmartServo FlexLine to seal the cabling in the conduit. Depending on the wiring configuration, one to four ¾” NPT threaded cable glands (or rigid conduits) may be required with the 954 SmartServo FlexLine.
  • Page 41: Grounding

    Improper installation of cable glands, conduit or stopping plugs will invalidate the Ex approval of your 954 SmartServo FlexLine. Grounding The 954 SmartServo FlexLine housing should be properly grounded to the ground reference (generally the tank). This is a safety grounding requirement. Grounding can be performed by copper strips across the flanges (refer to section Grounding at mechanical installation), or by a ground wire.
  • Page 42 Appendix A Dimensions 954 SmartServo FlexLine (Medium Pressure and Chemical Version) a. Position of measuring wire with displacer in top position 7/8’’ b. 200 mm (7 ) (space needed to remove cover) 9/16’’ c. 65 mm (2 ) (space needed to remove measuring drum) d.
  • Page 43: Appendix A (Continuation)

    Appendix A (Continuation) Dimensions 954 SmartServo FlexLine (High Pressure Version) a. Position of measuring wire with displacer in top position 7/8’’ b. 200 mm (7 ) (space needed to remove cover) 9/16’’ c. 65 mm (2 ) (space needed to remove measuring drum) d.
  • Page 44 Appendix B Available Adapters & Calibration Chambers Part No: 4417341 Revision 10 Installation Manual 954 SmartServo FlexLine...
  • Page 45 Copyright © 2019 - Honeywell All rights reserved. No part of this manual may be reproduced in any form, by print, photoprint, microfilm or any other means without the written permission from Honeywell. For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com...