Pr.
Name
251
Output phase loss
H200
protection selection
872
Input phase loss
*1
protection selection
H201
*1
Available for the three-phase power input model only.
 Output phase loss protection selection (Pr.251)
• When Pr.251 is set to "0", output phase loss protection (E.LF) becomes invalid.
 Input phase loss protection selection (Pr.872)
• When Pr.872 is set to "1", Input phase loss (E.ILF) protection is activated if one of three phases is detected to be lost for
1 second continuously.
NOTE
• When several motors are connected, output phase loss cannot be detected even if the wiring to one motor loses phase.
• In the case of R/L1, S/L2 phase loss, the input phase loss protection does not operate, and the inverter output is shut off.
• If an input phase loss continues for a long time, the lives of converter section and capacitor of the inverter become shorter.
• If the load is light or during a stop, lost phase cannot be detected because detection is performed based on the fluctuation of
bus voltage. Large unbalanced phase-to-phase voltage of the three-phase power supply may also cause input phase loss
protection (E.ILF).
• Phase loss cannot be detected during regeneration load operation.
Parameters referred to
Pr.261 Power failure stop
selectionpage 414
Initial value
Setting range
0
1
1
0
1
1
Description
Output phase loss protection disabled
Output phase loss protection enabled
Input phase loss protection disabled
Input phase loss protection enabled