Mitsubishi Electric PUZ-WM50VHA Service Manual page 47

Air to water heat pump units
Table of Contents
Outdoor power circuit board
PUZ-WM85YAA.UK
PUZ-WM85YAA-BS.UK
PUZ-WM112YAA.UK
PUZ-WM112YAA-BS.UK
Diode module
TAB connector
on X52CA
Connect to the
RS resistor
TB-L1,
TB-L2,
TB-L3
Connect to the
outdoor converter
circuit board
(L1-OU, L2-OU,
L3-OU)
400V AC
CN4
Connect to the
outdoor controller
circuit board (CN4)
CN2
Connect to the outdoor controller circuit board (CN2)
1–5: Power circuit board
signal to the controller board (0–5V DC)
2–5: Zero cross signal (0–5 V DC)
3–4: Not used
[ 5 : –
6–5: 16 V DC
7–5: 16 V DC
OCH727
Note: The marks L1 , L2 , L3 , N1 , N2 , P1 , P2 , U , V and W
TB-N
Connect to the CK capacitor
P1
L1
CN5
Detection of primary
current (Connect to
the outdoor noise filter
circuit board (CNCT))
Transmitting
1, 2, 6, 7 : + ]
Brief Check of POWER MODULE
• If they are short-circuited, it means that they are broken.
Measure the resistance in the following points (connectors, etc.).
1. Check of DIODE MODULE
L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1
2. Check of DIP-IPM
P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W
shown in the diagram are not actually printed on the board.
N2
L2
L3
N1
CN7
Connect to the
outdoor converter
circuit board (CN7)
CN6
Thermistor
(TH8)
47
TB-U, TB-V, TB-W
Connect to the compressor (MC)
Voltage among phases:
10V-400V AC
W
V
U
P2
L3OUT-L3IN
Lead connect
DIP-IPM