SPLIT-TYPE, AIR TO WATER HEAT PUMP April 2019 No. OCH439 REVISED EDITION-M SERVICE MANUAL R410A [Model Name] Revision: PUHZ-W50VHA-BS PUHZ-W50VHA • Added PUHZ-HW112YHA2R7, PUHZ-W85VHA-BS PUHZ-HW112YHA2R7-BS, PUHZ-W85VHA PUHZ-HW140VHA2R7, PUHZ-HW140VHA2R7-BS, PUHZ-HW112YHA PUHZ-HW112YHA-BS PUHZ-HW140YHA2R7 and PUHZ-HW140YHA2R7-BS in PUHZ-HW112YHA2-BS PUHZ-HW112YHA2 REVISED EDITION-M. • Some descriptions have been...
HW112Y : ANB33FJFMT → ANB33FJJMT HW140Y : ANB42FJFMT → ANB42FJJMT HW140V : ANB42FJGMT → ANB42FJKMT PUHZ-HW112YHA2(-BS) PUHZ-HW112YHA2R1(-BS) PUHZ-HW140YHA2(-BS) PUHZ-HW140YHA2R1(-BS) PUHZ-HW140VHA2 PUHZ-HW140VHA2R1 PUHZ-HW140VHA2R1-BS PUHZ-HW140VHA2R2-BS 1. Plate heat exchanger has been changed. PUHZ-W50VHA(-BS) PUHZ-W50VHAR1(-BS) 1. Heat exchanger has been changed. PUHZ-HW140VHA2-BS PUHZ-HW140VHA2R1-BS 1. Controller circuit board (C.B.) has been changed. (S/W version up) OCH439M...
Page 4
PUHZ-HW112YHA(-BS) PUHZ-HW112YHA2(-BS) PUHZ-HW140VHA(-BS) PUHZ-HW140VHA2(-BS) PUHZ-HW140YHA(-BS) PUHZ-HW140YHA2(-BS) 1. Heat exchanger has been changed. 2. Compressor has been changed. (only HW140) HW140V : ANB33FJGMT → ANB42FJGMT HW140Y : ANB33FJFMT → ANB42FJFMT 3. Refrigerant charge has been changed. (only HW140) 4.0 kg → 4.3 kg 4. Plate heat exchanger has been changed. ACH50 → ACH70 5. Muffler has been deleted. 6.
SAFETY PRECAUTION 2-1. ALWAYS OBSERVE FOR SAFETY Before obtaining access to terminal, all supply circuits must be disconnected. Preparation before the repair service. • Prepare the proper tools. • Prepare the proper protectors. • Provide adequate ventilation. • After stopping the operation of the air conditioner, turn off the power-supply breaker. •...
[1] Cautions for service (1) Perform service after recovering the refrigerant left in the unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. [2] Additional refrigerant charge When charging directly from cylinder ·...
Page 7
2-3. CAUTIONS FOR REFRIGERANT PIPING WORK Tools for R410A (The following table shows whether conventional tools can be used or not.) Can R22 tools be Tools and materials R410A tools Can R407C tools be used? used? × × Gauge manifold Tool exclusive for R410A Air purge, refrigerant charge and operation check...
SPECIFICATIONS 3-1. SPECIFICATIONS PUHZ-W50VHA PUHZ-W50VHA-BS PUHZ-W50VHAR1 PUHZ-W50VHAR1-BS 1[ , 230 V, 50 Hz Nominal water flow rate (Heating mode) L/min 14.3 Heating(A7/W35) Heating y t i 5.00 °C 4.10 (A7/W35) °C 1.22 l n i °C Heating y t i 5.00...
Page 9
PUHZ-W50VHAR2 PUHZ-W50VHAR2-BS PUHZ-W50VHAR3 PUHZ-W50VHAR3-BS 1[ , 230 V, 50 Hz Nominal water flow rate (Heating mode) L/min 14.3 Heating(A7/W35) Heating y t i 5.00 °C 4.10 (A7/W35) °C 1.22 l n i °C Heating y t i 5.00 Heating(A2/W35) 3.13 (A2/W35) °C 1.60...
Page 10
PUHZ-W85VHA PUHZ-W85VHA-BS PUHZ-W85VHAR1 PUHZ-W85VHAR1-BS 1φ, 230 V, 50 Hz Nominal water flow rate (Heating mode) L/min 25.8 Heating(A7/W35) Heating y t i 9.00 ℃ 3.85 (A7/W35) ℃ 2.34 l n i ℃ Heating y t i 8.50 Heating(A2/W35) 2.95 (A2/W35) ℃...
Page 11
PUHZ-HW112YHA PUHZ-HW112YHA-BS 3φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 32.1 Heating(A7/W35) Heating y t i 11.20 ℃ 4.24 (A7/W35) ℃ 2.64 l n i ℃ Heating y t i 11.20 Heating(A2/W35) 3.01 (A2/W35) ℃ 3.72 ℃...
Page 12
PUHZ-HW140VHA PUHZ-HW140VHA-BS 1φ , 230 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) 14.00 Heating y t i ℃ (A7/W35) 4.19 ℃ 3.34 l n i ℃ Heating y t i 14.00 Heating(A2/W35) 2.69 (A2/W35) ℃ 5.21 ℃...
Page 13
PUHZ-HW140YHA PUHZ-HW140YHA-BS 3φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) 14.00 Heating y t i ℃ (A7/W35) 4.19 ℃ 3.34 l n i ℃ Heating y t i 14.00 Heating(A2/W35) 2.69 (A2/W35) ℃ 5.21 ℃...
Page 14
PUHZ-HW112YHA2 PUHZ-HW112YHA2-BS 3 φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 32.1 Heating(A7/W35) Heating y t i 11.20 ℃ (A7/W35) 4.42 ℃ l n i 2.53 ℃ Heating y t i Heating(A2/W35) 11.20 (A2/W35) 3.11 ℃ 3.60 ℃...
Page 15
PUHZ-HW140VHA2 PUHZ-HW140VHA2-BS PUHZ-HW140VHA2R1-BS 1φ, 230 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃ 4.50 ℃...
Page 16
PUHZ-HW140YHA2 PUHZ-HW140YHA2-BS 3φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ Heating y t i 14.00 Heating(A2/W35) 3.11 (A2/W35) ℃ 4.50 ℃...
Page 17
PUHZ-HW112YHA2R1 PUHZ-HW112YHA2R1-BS 3 φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 32.1 Heating(A7/W35) Heating y t i 11.20 ℃ (A7/W35) 4.42 ℃ l n i 2.53 ℃ Heating y t i 11.20 Heating(A2/W35) (A2/W35) 3.11 ℃ 3.60 ℃...
Page 18
PUHZ-HW112YHA2R3 PUHZ-HW112YHA2R3-BS PUHZ-HW112YHA2R4 PUHZ-HW112YHA2R4-BS 3 φ, 400V, 50Hz Nominal water flow rate (Heating mode) L/min 32.1 Heating(A7/W35) Heating y t i 11.20 ℃ (A7/W35) 4.42 ℃ l n i 2.53 ℃ Heating y t i 11.20 Heating(A2/W35) (A2/W35) 3.11 ℃ 3.60 ℃...
Page 19
PUHZ-HW112YHA2R5 PPUHZ-HW112YHA2R6 UHZ-HW112YHA2R5-BS PUHZ-HW112YHA2R6-BS 3 φ, 400 V, 50Hz Nominal water flow rate (Heating mode) L/min 32.1 Heating(A7/W35) Heating y t i 11.20 ℃ (A7/W35) 4.43 ℃ l n i 2.53 ℃ Heating y t i 11.20 Heating(A2/W35) (A2/W35) 3.11 ℃...
Page 20
PUHZ-HW112YHA2R7 PUHZ-HW112YHA2R7-BS 3 φ, 400 V, 50Hz Nominal water flow rate (Heating mode) L/min 32.1 Heating(A7/W35) Heating y t i 11.20 ℃ (A7/W35) 4.43 ℃ l n i 2.53 ℃ Heating y t i 11.20 Heating(A2/W35) (A2/W35) 3.11 ℃ 3.60 ℃...
Page 21
PUHZ-HW140VHA2R1 PUHZ-HW140VHA2R2-BS 1φ, 230V, 50Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ 4.25 (A7/W35) ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) (A2/W35) 3.11 ℃ 4.50 ℃ Pressure difference (water circuit) l n i ...
Page 22
PUHZ-HW140VHA2R3 PUHZ-HW140VHA2R3-BS PUHZ-HW140VHA2R4 PUHZ-HW140VHA2R4-BS 1φ, 230V, 50Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃ 4.50 ℃...
Page 23
PUHZ-HW140VHA2R5 PUHZ-HW140VHA2R6 PUHZ-HW140VHA2R5-BS PUHZ-HW140VHA2R6-BS 1φ, 230 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃...
Page 24
PUHZ-HW140VHA2R7 PUHZ-HW140VHA2R7-BS 1φ, 230 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃ 4.50 ℃...
Page 25
PUHZ-HW140YHA2R1 PUHZ-HW140YHA2R1-BS 3φ, 400V, 50Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃ 4.50 ℃ Pressure difference (water circuit) l n i ...
Page 26
PUHZ-HW140YHA2R3 PUHZ-HW140YHA2R3-BS PUHZ-HW140YHA2R4 PUHZ-HW140YHA2R4-BS 3φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃...
Page 27
PUHZ-HW140YHA2R5 PUHZ-HW140YHA2R6 PUHZ-HW140YHA2R5-BS PUHZ-HW140YHA2R6-BS 3φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ (A7/W35) 4.25 ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃...
Page 28
PUHZ-HW140YHA2R7 PUHZ-HW140YHA2R7-BS 3φ, 400 V, 50 Hz Nominal water flow rate (Heating mode) L/min 40.1 Heating(A7/W35) Heating y t i 14.00 ℃ 4.25 (A7/W35) ℃ 3.29 l n i ℃ 14.00 Heating y t i Heating(A2/W35) 3.11 (A2/W35) ℃ 4.50 ℃...
3-2. AVAILABLE RANGE (WATER FLOW RATE, RETURN WATER TEMP.) Note: If using the unit out of the available range, the parts of unit might be damaged. • PUHZ-W50VHA(-BS) 19.0 Available range • PUHZ-W50VHAR1(-BS) 17.0 • PUHZ-W50VHAR2(-BS) 15.0 •...
Page 30 • PUHZ-W50VHA(-BS) 19.0 • PUHZ-W50VHAR1(-BS) Available range 17.0 • PUHZ-W50VHAR2(-BS) 15.0 • PUHZ-W50VHAR3(-BS) 13.0 11.0 10.0 11.0 12.0 13.0 14.0 Water flow rate [L/min] Table 4 15.0 • PUHZ-W85VHA(-BS) 14.0 • PUHZ-W85VHAR1(-BS) Available range 13.0 12.0...
WIRING DIAGRAM PUHZ-W50VHA(-BS) PUHZ-W50VHAR1(-BS) SYMBOL NAME SYMBOL NAME Terminal Block PFC/IPM Power Module Motor for Compressor N.F. Noise Filter Circuit Board Fan Motor Connection Terminal LI,LO 21S4 Solenoid Valve...
Page 38
PUHZ-W50VHAR2(-BS) PUHZ-W50VHAR3(-BS) SYMBOL NAME SYMBOL NAME CB1, CB2, CB3 Main Smocthing Capacitor Terminal Block PFC/IPM Power Module Motor for Compressor N. F. Noise Filter Circuit Board Fan Motor Connection Terminal LI, LO 21S4 Solenoid Valve(Four-Way Valve) NI, NO Connection Terminal...
Page 39
PUHZ-W85VHA(-BS) SYMBOL NAME SYMBOL NAME TABN1/N2 Connection Terminal Terminal Block DS2, DS3 Diode bridge Motor for Compressor Power Module Fan Motor N.F. Noise Filter Circuit Board 21S4 Solenoid Valve LI,LO Connection Terminal ...
Page 40
PUHZ-W85VHAR1(-BS) SYMBOL NAME SYMBOL NAME Terminal Block Flow temp. controller> TABN1/N2 Connection Terminal < DC Voltage> Motor for Compressor DS2, DS3 Diode bridge Fan Motor Power Module 21S4 Solenoid Valve N.F.
PUHZ-HW140VHA(-BS) SYMBOL NAME P.B. Power Circuit Board Terminal Block Flow Temp. controller-Outdoor> Connection Terminal Motor for Compressor Connection Terminal MF1,MF2 Fan Motor DCL1,DCL2 Connection Terminal 21S4 Solenoid Valve Power Module IGBT High Pressure Switch Connection Terminal...
Page 42
PUHZ-HW112YHA(-BS) PUHZ-HW140YHA(-BS) SYMBOL NAME SYMBOL NAME Terminal Block N.F. Noise Filter Circuit Board Terminal Block LI1/LI2/LI3/NI controller-Outdoor> LO1/LO2/LO3/NO Connection Terminal Motor for Compressor GD1,GD3 Connection Terminal MF1,MF2 Fan Motor CONV.B. Converter Circuit Board 21S4 Solenoid Valve...
Page 43
PUHZ-HW112YHA2(-BS) PUHZ-HW140YHA2R1(-BS) PUHZ-HW112YHA2R1(-BS) PUHZ-HW140YHA2(-BS) SYMBOL NAME SYMBOL NAME N.F. Noise Filter Circuit Board Terminal Block < Power Supply> Terminal Block < Interface unit /Flow Temp. Connection Terminal LI1/LI2/LI3/NI controller-Outdoor> LO1/LO2/LO3/NO Connection Terminal Motor for Compressor GD1,GD3 Connection Terminal ...
Page 44
PUHZ-HW112YHA2R3(-BS) PUHZ-HW140YHA2R3(-BS) PUHZ-HW112YHA2R4(-BS) PUHZ-HW140YHA2R4(-BS) 1 MODEL SELECT SYMBOL NAME SYMBOL NAME The black square ( ) indicates a switch position. Terminal Block N. F. Noise Filter Circuit Board MODEL SW5-6 Terminal Block Connection Terminal LI1, LI2, LI3, NI 112Y Motor for Compressor LO1, LO2, LO3, NO...
Page 45
PUHZ-HW112YHA2R5(-BS) PUHZ-HW140YHA2R5(-BS) PUHZ-HW112YHA2R6(-BS) PUHZ-HW140YHA2R6(-BS) PUHZ-HW112YHA2R7(-BS) PUHZ-HW140YHA2R7(-BS) SYMBOL NAME SYMBOL NAME Terminal Block Rush Current Protect Resistor Terminal Block P. B. Power Circuit Board MODEL Motor for Compressor N. F. Noise Filter Circuit Board 112Y MF1, MF2 Fan Motor CONV. B. Converter Circuit Board 1 2 3 4 5 6 7 8 1 2 3 4 5 6...
Page 46
PUHZ-HW140VHA2(-BS) PUHZ-HW140VHA2R1(-BS) PUHZ-HW140VHA2R2-BS SYMBOL NAME SYMBOL NAME Terminal Block Flow Temp. controller-Outdoor> DCL1,DCL2 Connection Terminal < Reactor > Motor for Compressor IGBT Power Module MF1,MF2 Fan Motor Connection Terminal < Ground > EI,E2,E3,E4 21S4 Solenoid Valve ...
Page 47
PUHZ-HW140VHA2R3(-BS) PUHZ-HW140VHA2R4(-BS) 1 MODEL SELECT SYMBOL NAME SYMBOL NAME The black square ( ) indicates a switch position. Terminal Block Connection Terminal MODEL SW5-6 Motor for Compressor Connection Terminal DCL1, DCL2 140V MF1, MF2 Fan Motor IGBT Power Module 1 2 3 4 5 6 7 8 1 2 3 4 5 6 21S4...
Page 48
PUHZ-HW140VHA2R5(-BS) PUHZ-HW140VHA2R6(-BS) PUHZ-HW140VHA2R7(-BS) SYMBOL NAME SYMBOL NAME 1 MODEL SELECT Terminal Block CY1, CY2 Capacitor MODEL SW5-6 Motor for Compressor P. B. Power Circuit Board 140V MF1, MF2 Fan Motor C. B. Controller Circuit Board 1 2 3 4 5 6 7 8 1 2 3 4 5 6 21S4 Solenoid Valve(4-Way Valve)
WIRING SPECIFICATIONS FIELD ELECTRICAL WIRING (power wiring specifications) 140V t i n 112Y, 140Y Outdoor unit power supply ~/N (single), 50 Hz, 230 V ~/N (single), 50 Hz, 230 V ~/N (single), 50 Hz, 230 V 3N~ (3phase), 50 Hz, 400 V t i n c r i t i u...
Refrigerant flow in cooling Refrigerant flow in heating Detail Symbol Part name COMP Compressor DC inverter twin rotary compressor (Mitsubishi Electric Corporation) H/P SW High pressure switch (63H) For protection (OFF: 4.15 MPa) Plate HEX Plate Heat Exchanger ACH30-30 (ALFA LAVAL)
Refrigerant flow in cooling Refrigerant flow in heating Symbol Part name Detail COMP Compressor DC inverter scroll compressor (Mitsubishi Electric Corporation) H/P SW High pressure switch (63H) For protection (OFF: 4.15MPa) L/P SW Low pressure switch (63L) For protection (OFF: -0.03MPa)
TROUBLESHOOTING 9-1. TROUBLESHOOTING Present and past check codes are logged, and they can be displayed on the control board of outdoor unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summarized in the table below. Check the contents below before investigating details.
Page 53
9-3. SELF-DIAGNOSIS ACTION TABLE Check Code Abnormal point and detection method Cause Judgment and action 1 Check following items. 1 No voltage is supplied to terminal block (TB1) of outdoor unit. a) Power supply breaker a) Power supply breaker is b) Connection of power supply terminal block turned off.
Page 54
Check Code Abnormal point and detection method Cause Judgment and action 63H connector open 1 Disconnection or contact fail- 1 Check connection of 63H connector on Abnormal if 63H connector circuit is open ure of 63H connector on out- outdoor controller circuit board. for 3 minutes continuously from being door controller circuit board Refer to "9-6.
Page 55 Check Code Abnormal point and detection method Cause Judgment and action High pressure (High pressure switch 1 Decreased water flow 1–5 Check water circuit and repair the defect. 63H operated) 2 Clogged filter of water pipe Abnormal if high pressure switch 63H 3 Dirt of plate heat exchanger operated (*) during compressor operation.
Page 56
Check Code Abnormal point and detection method Cause Judgment and action Open/short of outdoor unit thermistors 1 Check connection of connector (TH3, TH32, 1 Disconnection or contact failure (TH3, TH32, TH33, TH6, TH7, and TH8) TH33, TH6/TH7) on the outdoor controller of connectors circuit board.
Page 57
Check Code Abnormal point and detection method Cause Judgment and action To find out the details about U9 error, turn ON SW2-1, 2-2, 2-3, 2-4, 2-5 and 2-6 when U9 error occurs. Detailed To find out the detail history (latest) about U9 error, turn ON SW2-1, 2-2 and 2-6. codes Refer to "9-7.
Page 58
Check Code Abnormal point and detection method Cause Judgment and action Abnormal power synchronous 1 Check the field facility for the power supply. 1 Distortion of power source Detailed codes signal voltage, noise superimposition 2 Check earth wiring. • No input of power 2 Disconnection or loose con- synchronous signal to power nection of earth wiring...
Page 59
Check Code Abnormal point and detection method Cause Judgment and action Current sensor error or input current error 1 Disconnection of compressor 1 Correct the wiring (U W phase) to compres- • • · A bnormal if current sensor detects −1.0 A wiring sor. Refer to "9-6. TEST POINT DIAGRAM" to 1.0 A during compressor operation.
Page 60
Check Code Abnormal point and detection method Cause Judgment and action Remote controller transmission error 1 Refer to the indoor unit's 1 Refer to the indoor unit's Installation Manual Installation Manual for remote for remote controller connection. (E3)/signal receiving error (E5) controller connection.
Page 61
Check Code Abnormal point and detection method Cause Judgment and action Freezing/overheating protection is working (1) Freezing protection (1) Freezing protection (1) Freezing protection 1 Reduced water flow 12 Check water piping. · Clogged filter Abnormal if plate heat exchanger pipe ·...
Page 62
9-4. HOW TO CHECK THE PARTS PUHZ-W50VHA(-BS) PUHZ-W85VHA(-BS) PUHZ-HW112YHA(-BS) PUHZ-HW140VHA(-BS) PUHZ-HW140YHA(-BS) PUHZ-W50VHAR1(-BS) PUHZ-W85VHAR1(-BS) PUHZ-HW112YHA2(-BS) PUHZ-HW140VHA2(-BS) PUHZ-HW140YHA2(-BS) PUHZ-W50VHAR2(-BS) PUHZ-HW112YHA2R1(-BS) PUHZ-HW140YHA2R1(-BS) PUHZ-HW140YHA2R1(-BS) PUHZ-W50VHAR3(-BS) PUHZ-HW112YHA2R3(-BS) PUHZ-HW140VHA2R2-BS PUHZ-HW140YHA2R3(-BS) PUHZ-HW112YHA2R4(-BS) PUHZ-HW140VHA2R3(-BS) PUHZ-HW140YHA2R4(-BS) PUHZ-HW112YHA2R5(-BS) PUHZ-HW140VHA2R4(-BS) PUHZ-HW140YHA2R5(-BS) PUHZ-HW112YHA2R6(-BS) PUHZ-HW140VHA2R5(-BS) PUHZ-HW140YHA2R6(-BS) PUHZ-HW112YHA2R7(-BS) PUHZ-HW140VHA2R6(-BS) PUHZ-HW140YHA2R7(-BS) PUHZ-HW140VHA2R7(-BS) Parts name Checkpoints TH3: Liquid pipe temp.
Page 63
Check method of DC fan motor (fan motor/outdoor multi controller circuit board) 1 Notes · High voltage is applied to the connector (CNF1, 2) for the fan motor. Pay attention to the service. · Do not pull out the connector (CNF1, 2) for the motor with the power supply on. (It may damage the outdoor controller circuit board and fan motor.) 2 Self check Symptom: The outdoor fan cannot rotate.
Page 64
9-5. HOW TO CHECK THE COMPONENTS Low temperature thermistors • Thermistor (TH3) • Thermistor (TH6) • Thermistor (TH7) • Thermistor (TH33 for HW112,140) Thermistor R0 = 15 k" ± 3% B constant = 3480 ± 2% =15exp{3480( 273+t –...
Page 66
Linear expansion valve (1) Operation summary of the linear expansion valve • Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the outdoor controller board. • Valve position can be changed in proportion to the number of pulse signal. ...
Page 67
(3) How to attach and detach the coil of linear expansion valve Linear expansion valve is separable into the main body and the coil as shown in the diagram below. Main body Stopper Coil Lead wire Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward.
9-6. TEST POINT DIAGRAM Outdoor controller circuit board TEST POINT 1 is high voltage. PUHZ-W50VHA(-BS) PUHZ-W85VHA(-BS) PUHZ-W50VHAR1(-BS) PUHZ-W85VHAR1(-BS) PUHZ-W50VHAR2(-BS) (TEST POINT 2) CNDC PUHZ-W50VHAR3(-BS) (voltage between pins of 280–380 V DC High pres- C6B): 15 V DC Connect from outdoor sure switch power circuit board.
Page 69 TEST POINT 1 is high voltage. Outdoor controller circuit board PUHZ-HW112YHA(-BS) PUHZ-HW140VHA(-BS) PUHZ-HW140YHA(-BS) PUHZ-HW112YHA2(-BS) PUHZ-HW140VHA2(-BS) PUHZ-HW140YHA2(-BS) PUHZ-HW112YHA2R1(-BS) PUHZ-HW140VHA2R1(-BS) PUHZ-HW140YHA2R1(-BS) Operation monitor function Manual defrost, detect history record reset CNDM Function switch 1–2: Input of low-level (HW·HA2 only) sound priority mode Model select CN52C Connect to the power...
Page 70
Outdoor controller circuit board TEST POINT 1 is high voltage. PUHZ-HW112YHA2R3(-BS) PUHZ-HW140VHA2R3(-BS) PUHZ-HW140YHA2R3(-BS) PUHZ-HW112YHA2R4(-BS) PUHZ-HW140VHA2R4(-BS) PUHZ-HW140YHA2R4(-BS) Manual defrost, detect Function switch Operation monitor history record reset function Function switch (HW·HA2 only) CNDM 1–2: Input of low-level sound priority mode CN52C Model select Connect to the power...
Page 71 TEST POINT 1 is high voltage. Outdoor controller circuit board PUHZ-HW112YHA2R5(-BS) PUHZ-HW140YHA2R5(-BS) PUHZ-HW140VHA2R5(-BS) PUHZ-HW112YHA2R6(-BS) PUHZ-HW140YHA2R6(-BS) PUHZ-HW140VHA2R6(-BS) PUHZ-HW112YHA2R7(-BS) PUHZ-HW140YHA2R7(-BS) PUHZ-HW140VHA2R7(-BS) CN52C CNDM Connect to the power Manual defrost, 1–2: circuit board (CN52C) detect history Input of low-level Operation record reset sound priority mode (HW140V) monitor function...
Page 72
Outdoor noise filter circuit board PUHZ-W50VHA(-BS) PUHZ-W50VHAR1(-BS) PUHZ-W50VHAR2(-BS) PUHZ-W50VHAR3(-BS) EI, E2 Connect to the earth Connect to the earth CNAC1, CNAC2 230 V AC (Connect to the out- door controller cir- cuit board (CNAC)) Primary current (Connect to the outdoor power...
Page 73
Outdoor noise filter circuit board LO, NO PUHZ-W85VHA(-BS) Voltage of 230 V AC is output. Connect to the outdoor power PUHZ-W85VHAR1(-BS) circuit board (TABS, TABT). CNAC1, CNAC2 230 V AC Connect to the out- door controller cir- cuit board (CNAC). Connect to the earth.
Page 74
Outdoor noise filter circuit board PUHZ-HW112YHA(-BS) PUHZ-HW140YHA(-BS) PUHZ-HW112YHA2(-BS) PUHZ-HW140YHA2(-BS) PUHZ-HW112YHA2R1(-BS) PUHZ-HW140YHA2R1(-BS) LI1, LI2, LI3, NI POWER SUPPLY LI1-LI2/LI-LI3/LI3-LI1: 400 V AC input LI1-NI/LI2-NI/LI3-NI: 230 V AC input (Connect to the terminal block (TB1)) Connect to the earth CNAC1, CNAC2 230 V AC (Connect to the outdoor controller Connect to the earth...
Page 75
Outdoor noise filter circuit board PUHZ-HW112YHA2R3(-BS) PUHZ-HW140YHA2R3(-BS) PUHZ-HW112YHA2R4(-BS) PUHZ-HW140YHA2R4(-BS) LI1, LI2, LI3, NI POWER SUPPLY LI1-LI2/LI-LI3/LI3-LI1: 400 V AC input LI1-NI/LI2-NI/LI3-NI: 230 V AC input (Connect to the terminal block (TB1)) Connect to the earth CNAC1, CNAC2 230 V AC Connect to the earth (Connect to the outdoor controller...
Page 76
Outdoor noise filter circuit board PUHZ-HW112YHA2R5(-BS) PUHZ-HW140YHA2R5(-BS) PUHZ-HW112YHA2R6(-BS) PUHZ-HW140YHA2R6(-BS) PUHZ-HW112YHA2R7(-BS) PUHZ-HW140YHA2R7(-BS) LI1, LI2, LI3, NI POWER SUPPLY LI1-LI2/LI-LI3/LI3-LI1: 400 V AC input LI1-NI/LI2-NI/LI3-NI: 230 V AC input (Connect to the terminal block (TB1)) Connect to the earth CNAC1, CNAC2 230 V AC (Connect to the Connect to the earth outdoor controller...
Page 77
Outdoor power circuit board Brief Check of DIP-IPM and DIP-PFC PUHZ-W50VHA(-BS) If they are short-circuited, it means that they are broken. Measure the resistance in the following points (connectors, etc.). PUHZ-W50VHAR1(-BS) PUHZ-W50VHAR2(-BS) 1. Check of DIP-IPM PUHZ-W50VHAR3(-BS) P2 - U , P2 - V , P2 - W , N2 - U , N2 - V , N2 - W 2.
Page 78
Outdoor power circuit board Brief Check of POWER MODULE If they are short-circuited, it means that they are broken. PUHZ-W85VHA(-BS) Measure the resistance in the following points (connectors, etc.). PUHZ-W85VHAR1(-BS) 1. Check of diode bridge TABP1-TABS, TABN1-TABS, TABP1-TABT, TABN1-TABT 2. Check of DIP-IPM P - U , P - V , P - W , N - U , N - V , N - W Connect to the outdoor controller circuit board (CN2)
Page 79
Outdoor power circuit board PUHZ-HW140VHA(-BS) PUHZ-HW140VHA2(-BS) PUHZ-HW140VHA2R1(-BS) PUHZ-HW140VHA2R2-BS PUHZ-HW140VHA2R3(-BS) PUHZ-HW140VHA2R4(-BS) Connect to the outdoor controller circuit board (CN2) 1–5: Transmitting signal to outdoor controller circuit board (0–5 V DC) 2–5: Zero cross signal (0–5 V DC) Connect to the outdoor 3–4: 18 V DC controller circuit board (CN4) 6–5: 16 V DC...
Page 80
Outdoor power circuit board Brief Check of POWER MODULE PUHZ-HW140VHA2R5(-BS) If they are short-circuited, it means that they are broken. Measure the resistance in the following points (connectors, etc.). PUHZ-HW140VHA2R6(-BS) 1. Check of POWER MODULE PUHZ-HW140VHA2R7(-BS) 1 Check of DIODE circuit R - L1 , S - L1 , R - N1 , S - N1 2 Check of IGBT circuit L2 - N1...
Page 81
Outdoor power circuit board Brief Check of POWER MODULE If they are short-circuited, it means that they are broken. PUHZ-HW112YHA(-BS) Measure the resistance in the following points (connectors, etc.). PUHZ-HW112YHA2(-BS) 1. Check of POWER MODULE PUHZ-HW112YHA2R1(-BS) 1.Check of DIODE circuit PUHZ-HW112YHA2R3(-BS) L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1 2.Check of IGBT circuit...
Page 82
Outdoor power circuit board Brief Check of POWER MODULE If they are short-circuited, it means that they are broken. PUHZ-HW112YHA2R5(-BS) Measure the resistance in the following points (connectors, etc.). PUHZ-HW112YHA2R6(-BS) 1. Check of POWER MODULE PUHZ-HW140YHA2R5(-BS) 1.Check of DIODE circuit L1 - P1 , L2 - P1 , L3 - P1 , L1 - N1 , L2 - N1 , L3 - N1 PUHZ-HW140YHA2R6(-BS) 2.Check of IGBT circuit...
Page 83
Outdoor converter circuit board PUHZ-HW112YHA(-BS) PUHZ-HW140YHA(-BS) PUHZ-HW112YHA2(-BS) PUHZ-HW140YHA2(-BS PUHZ-HW112YHA2R1(-BS) PUHZ-HW140YHA2R1(-BS) PUHZ-HW112YHA2R3(-BS) PUHZ-HW140YHA2R3(-BS) PUHZ-HW112YHA2R4(-BS) PUHZ-HW140YHA2R4(-BS) L1-IN, N-IN L1-A1 CK-OU Connect to the noise filter Connect to the ACL1 Connect to the CK capacitor circuit board (LO1, NO) Connect to the outdoor power circuit board (CN7) L1-A2, L2-A2, L3-A2 L1-OU, L2-OU, L3-OU Connect to the ACL1, ACL2, ACL3...
Page 84
Outdoor converter circuit board PUHZ-HW112YHA2R5(-BS) PUHZ-HW140YHA2R5(-BS) PUHZ-HW112YHA2R6(-BS) PUHZ-HW140YHA2R6(-BS) PUHZ-HW112YHA2R7(-BS) PUHZ-HW140YHA2R7(-BS) L1-IN, N-IN L1-A1 CK-OU Connect to the noise filter Connect to the ACL1 Connect to the CK capacitor circuit board (LO1, NO) Connect to the outdoor power circuit board (CN7) L1-A2, L2-A2, L3-A2 L1-OU, L2-OU, L3-OU Connect to the ACL1, ACL2, ACL3 Connect to the outdoor power circuit board (TB-L1, L2, L3)
Page 85
Active filter module PUHZ-W85VHA(-BS) PUHZ-W85VHAR1(-BS) Connect to the outdoor power circuit board (TABP2) L1, L2 Connect to the Non-connect DCL (Reactor) Upper Lower side side Non-connect Connect to the outdoor power circuit board (TABP1) Connect to the outdoor power circuit board (CNAF) –...
Page 86
9-7. OUTDOOR UNIT OPERATION MONITOR FUNCTION Operation indicator SW2: Indicator change of self-diagnosis ■ The black square ( ) indicates a switch position. Display detail Explanation for display Unit SW2 setting 2 3 4 5 6 (Be sure that the 1 to 6 in the SW2 are set to OFF.) 1 second (1) Display when the power supply is ON.
Page 87
■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Pipe temperature/Liquid (TH3) −40 to 90 −40 to 90 (When the coil thermistor detects 0: or below, “–” and temperature are displayed by turns.) (Example) When −10:; 2 3 4 5 6 0.5 s 0.5 s Discharge temperature (TH4)
Page 88
■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Pipe temperature/Liquid (TH3) when −40 to 90 error occurred (When the coil thermistor detects 0: or below, “–” −40 to 90 and temperature are displayed by turns.) (Example) When −15:;...
■ The black square ( ) indicates a switch position. Explanation for display SW2 setting Display detail Unit Outdoor unit setting information • The tens digit (Total display for applied setting) Setting details Display details H·P/Cooling only 0: H·P 1: Cooling only Single phase/3 phase 0: Single phase 2: 3 phase Code...
Page 90
■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit 0 to 130 Sub cool (SC) (When the SC is 100°C or more, hundreds digit, tens 0 to 130 digit and ones digit are displayed by turns.) Cooling: SC = T −TH3 °C...
Page 91
■ The black square ( ) indicates a switch position. Display detail SW2 setting Explanation for display Unit When no error history, “0” and “– –“ are displayed by Error history (3) (Oldest) turns. Faulty unit number and check code are Code displayed alternately.
Page 92
■ The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Outdoor HEAT SINK temperature (TH8) −40 to 200 when error occurred. (When the temperature is 0°C or less, “–” and temperature are displayed by turns.) −40 to 200 (When the temperature is 100°C or more, hundreds 2 3 4 5 6 digit, tens digit and ones digit are displayed by turns.)
Page 93
■ The black square ( ) indicates a switch position. Explanation for display Unit SW2 setting Display detail 3 to 217 Comp. surface temperature (TH33) (When the temperature is 100: or more, the (for W50VHA(R1,R2,R3)/W85VHAR1) hundreds digit, tens digit and ones digit are Comp.
Page 95
9-8. FUNCTION OF SWITCHES PUHZ-W50VHA(-BS) PUHZ-W85VHA(-BS) PUHZ-W50VHAR1(-BS) PUHZ-W85VHAR1(-BS) PUHZ-W50VHAR2(-BS) PUHZ-W50VHAR3(-BS) Switch Selection Effective timing Default Function Function details (SW1, 8)/ setting Mark No. ON (with) OFF (without) Note (SW6) Switch ON to force defrosting When compressor Manual ON to start...
Page 96
PUHZ-HW140VHA(-BS) PUHZ-HW140YHA(-BS) PUHZ-HW112YHA(-BS) PUHZ-HW140VHA2(-BS) PUHZ-HW140YHA2(-BS) PUHZ-HW112YHA2(-BS) PUHZ-HW140VHA2R1(-BS) PUHZ-HW140YHA2R1(-BS) PUHZ-HW112YHA2R1(-BS) PUHZ-HW140VHA2R2-BS PUHZ-HW140YHA2R3(-BS) PUHZ-HW112YHA2R3(-BS) PUHZ-HW140VHA2R3(-BS) PUHZ-HW140YHA2R4(-BS) PUHZ-HW112YHA2R4(-BS) PUHZ-HW140VHA2R4(-BS) PUHZ-HW140YHA2R5(-BS) PUHZ-HW112YHA2R5(-BS) PUHZ-HW140VHA2R5(-BS) PUHZ-HW140YHA2R6(-BS) PUHZ-HW112YHA2R6(-BS) PUHZ-HW140VHA2R6(-BS) PUHZ-HW140YHA2R7(-BS) PUHZ-HW112YHA2R7(-BS) PUHZ-HW140VHA2R7(-BS) Switch Selection Effective Function Default setting Function details timing Mark ON (with) OFF (without) Manual defrost ON to start usual setting Switch ON to force defrosting...
Page 97
9-9. Request code list Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed. Refer to indoor unit service manual for how to use the controllers and request codes for indoor unit. Description Request content Unit Remarks (Display range)
Page 98
Description Request content Unit Remarks (Display range) Outdoor unit-Control state – Refer to 9-9-1.Detail Contents in Request Code. Compressor-Frequency control state Refer to 9-9-1.Detail Contents in Request Code. – Outdoor unit-Fan control state Refer to 9-9-1.Detail Contents in Request Code. –...
Page 99
Description Request content Unit Remarks (Display range) Error history 1 (latest) Displays error history. (" --" is displayed if no history is present.) Code Error history 2 (second to last) Displays error history. (" --" is displayed if no history is present.) Code Error history 3 (third to last) Displays error history.
Page 100
9-9-1. Detail Contents in Request Code [Operation state] (Request code : "0") Relay output state Power currently Data display Display Compressor 4-way valve Solenoid valve supplied to compressor – – – – Relay output state Operation mode Operation mode Display Operation mode STOP •...
Page 101
[Actuator output state] (Request code : "54") Data display Actuator output state 1 Actuator output state 2 Actuator output state Actuator output state Compressor is Display 4-way valve Compressor Display warming up [Error content (U9)] (Request code : "55 ") Data display Error content 1 Error content 2...
Page 102
[Outdoor unit – Setting information] (Request code: "71") Setting information 1 Data display Display Defrost mode Setting information 1 Standard Setting information 2 For high humidity Setting information 2 Single-/ Heat pump/ Display cooling only 3-phase Heat pump Single-phase Cooling only Heat pump 3-phase Cooling only...
DISASSEMBLY PROCEDURE PUHZ-W50VHA(-BS) PUHZ-W50VHAR1(-BS) PUHZ-W50VHAR2(-BS) PUHZ-W50VHAR3(-BS) PUHZ-W85VHA(-BS) PUHZ-W85VHAR1(-BS) PHOTO: PUHZ-W85VHA : Indicates the visible parts in the photos/fi gures. OPERATING PROCEDURE PHOTOS/FIGURES Top panel fi xing screws 1. Removing the service panel and top panel Photo 1 Top panel (1) Remove 3 screws (5 × 12) and slide the hook on the right downward to remove the service panel.
OPERATING PROCEDURE PHOTOS/FIGURES Photo 5 4. Removing the thermistor (TH6) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) Thermistor (3) Disconnect the connector TH7/6 (red) on the controller Thermistor Thermistor ...
Page 105
OPERATING PROCEDURE PHOTOS/FIGURES Photo 9 8. Removing the solenoid valve coil <4-way valve> (21S4) 4-way valve 4-way valve 4-way linear expansion valve coil (LEV (A), LEV (B)) and sole- LEV-A LEV-A valve coil (21S4) valve coil (21S4) noid valve coil (SV) LEV-B (1) Remove the service panel.
Page 106
OPERATING PROCEDURE PHOTOS/FIGURES Photo 11 11. Removing the bypass valve (1) Remove the service panel. (See Photo 1) Solenoid 4-way valve 4-way valve LEV-A LEV-B (2) Remove the top panel. (See Photo 1) valve coil (21S4) valve coil (21S4) (3) Remove the electrical parts box. (See Photo 4) (4) Remove 3 right side panel fixing screws (5 ×...
Page 107
OPERATING PROCEDURE PHOTOS/FIGURES Terminal cover Photo 12 14. Removing the compressor (MC) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) Lead wire for (3) Remove 2 screws (5 × 12) and remove the front cover panel. compressor (4) Remove 2 screws (5 ×...
Page 108
No.17 to 22 for PUHZ-W85VHA(-BS) PUHZ-W85VHAR1(-BS) OPERATING PROCEDURE PHOTOS/FIGURES Figure 1 17. Removing the controller circuit board (C.B.): Figure 1 Active fi lter module (ACTM) (1) Remove all lead wire connectors on controller circuit board (C.B.). CNF1, CNDC, CNAC, CN2, CN4, CN52C, Electrical Power circuit board (P.B.) Power circuit board (P.B.)
Page 109
No.23 to 27 for PUHZ-W50VHA(-BS), PUHZ-W50VHAR1(-BS), PUHZ-W50VHAR2(-BS), PUHZ-W50VHAR3(-BS) OPERATING PROCEDURE PHOTOS/FIGURES 23. Removing the controller circuit board (C.B.): Figure 3, Photo 17 Figure 3 Power circuit board (P.B.) (1) Remove all lead wire connectors on controller circuit board (C.B.). Controller circuit board (P.B.) Controller circuit board (P.B.)
Page 110
No.17 to 22 for PUHZ-W85VHA(-BS) PUHZ-W85VHAR1(-BS) OPERATING PROCEDURE PHOTOS/FIGURES Figure 1 17. Removing the controller circuit board (C.B.): Figure 1 Active fi lter module (ACTM) Active fi lter module (ACTM) (1) Remove all lead wire connectors on controller circuit board (C.B.). CNF1, CNDC, CNAC, CN2, CN4, CN52C, Electrical Power circuit board (P.B.) parts box...
Page 111
No.23 to 27 for PUHZ-W50VHA(-BS), PUHZ-W50VHAR1(-BS), PUHZ-W50VHAR2(-BS), PUHZ-W50VHAR3(-BS) OPERATING PROCEDURE PHOTOS/FIGURES 23. Removing the controller circuit board (C.B.): Figure 3, Photo 17 Figure 3 Power circuit board (P.B.) Power circuit board (P.B.) (1) Remove all lead wire connectors on controller circuit board (C.B.).
Page 112
PUHZ-HW112YHA(-BS) PUHZ-HW140VHA(-BS) PUHZ-HW140YHA(-BS) PUHZ-HW112YHA2(-BS) PUHZ-HW140VHA2(-BS) PUHZ-HW140YHA2(-BS) PUHZ-HW112YHA2R1(-BS) PUHZ-HW140VHA2R1(-BS) PUHZ-HW140YHA2R1(-BS) PUHZ-HW112YHA2R3(-BS) PUHZ-HW140VHA2R2-BS PUHZ-HW140YHA2R3(-BS) PUHZ-HW112YHA2R4(-BS) PUHZ-HW140VHA2R3(-BS) PUHZ-HW140YHA2R4(-BS) PUHZ-HW112YHA2R5(-BS) PUHZ-HW140VHA2R4(-BS) PUHZ-HW140YHA2R5(-BS) PUHZ-HW112YHA2R6(-BS) PUHZ-HW140VHA2R5(-BS) PUHZ-HW140YHA2R6(-BS) PUHZ-HW112YHA2R7(-BS) PUHZ-HW140VHA2R6(-BS) PUHZ-HW140YHA2R7(-BS) PUHZ-HW140VHA2R7(-BS) : Indicates the visible parts in the photos/fi gures. OPERATING PROCEDURE PHOTOS/FIGURES 1. Removing the service panel and top panel Photo 1 Top panel fi xing screws (1) Remove 3 service panel fixing screws (5 ×...
Page 113
OPERATING PROCEDURE PHOTOS/FIGURES Photo 4 (PUHZ-HW112/140Y) 3. Removing the electrical parts box (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) Controller circuit (3) Disconnect the indoor/outdoor connecting wire and board (C.B.) board (C.B.) board (C.B.) Noise fi lter circuit power supply wire from terminal block.
Page 114
OPERATING PROCEDURE PHOTOS/FIGURES 4. Disassembling the electrical parts box Photo 6 (PUHZ-HW112/140Y) Electrical (1) Disconnect all the connectors on the controller circuit board. parts box parts box (2) Remove the 3 screws, screw 1, 2 and 3, that fix the plate equipped with the outdoor controller circuit board, and the electrical parts box, screw 1 from the front and the screw 2 and 3 from the bottom of the electrical parts...
Page 116
OPERATING PROCEDURE PHOTOS/FIGURES 8. Removing the 4-way valve coil (21S4), and LEV coil (LEV-A, LEV-B, LEV-C) Photo 15 High pressure switch (63H) High pressure switch (63H) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) [Removing the 4-way valve coil] (See Photo 15) (3) Remove 4-way valve coil fixing screw (M4 ×...
Page 117
OPERATING PROCEDURE PHOTOS/FIGURES Photo 18 12. Removing high pressure sensor (63HS) Low pressure switch (63L) Low pressure switch (63L) Low pressure switch (63L) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical parts box. (See Photo 4, 5) (4) Remove 3 valve bed fixing screws (4 ×...
Page 118
OPERATING PROCEDURE PHOTOS/FIGURES Photo 20 14. Removing the reactors (ACL1, ACL2, ACL3) Electrical parts box Electrical parts box (PUHZ-HW112/140Y) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the 6 screws, that fix the front panel and remove the front panel.
Page 119
OPERATING PROCEDURE PHOTOS/FIGURES Photo 23 15. Removing the compressor (MC) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) Compressor (MC) Compressor (MC) Compressor (MC) Terminal cover (3) Remove the electrical parts box. (See Photo 4, 5) Pipes of power receiver (4) Remove 3 valve bed fixing screws (4 ×...