Honeywell TR21-WS Installation Instructions Manual

Honeywell TR21-WS Installation Instructions Manual

Quick Links

TR21-WS, TR23-WS, TR21-WK,
TR23-WK, WRECVR
APPLICATION
The WRECVR receiver and TR21-WS, TR23-WS, TR21-WK,
and TR23-WK are a family of wireless wall modules and
receiver for use with:
— Spyder Unitary Controllers: PUL, PVL, etc.
— Excel 10 W7750, W7751, W7752, and W7753
controllers
— T7350, T7351, and TB8575 low-voltage SuitePRO™
thermostats
— Will not work with TB7220, TB8220 or TB line voltage
thermostats, XL15s, W7762, W7763 or certain other
XL controllers,
— Will work with WEBs-AX™ I/O Module products if
using a separate transformer
— Compatibility with various other non-Honeywell con-
trollers that accept 10K type2 NTC temperature inputs
NOTE: Refer to the TR21 and TR23 Wall Modules –
Specification Data, form 63-1332, for specific model
features and additional information.
Model No.
TR21-WS
TR21-WK
TR23-WS
TR23-WK
TR21-WSU
TR23-WSU
WRECVR
WRECVRU
Agência Nacional de Telecomunicações
2969-10-6617
(01) 07898911288524
FCC/IC ID's
FCC ID: HS9WLKFWM
IC: 573R-WLKF
FCC ID: HS9WLKFRV
IC: 573R-WLKF
Agência Nacional de Telecomunicações
2969-10-6617
(01) 07898911288517
INSTALLATION INSTRUCTIONS
FEATURES
• Wall module to Receiver (point to point) wireless kits
can replace any standard wired sensor
• Wireless Kits (wall module and receiver) are pre-bound
at the factory for quick installation
• Signal Strength LED built into the wall module
• Low battery indication
• Optional dip switches available to bind any wall
module to any receiver
• Approximate 5 year battery life with AA Alkaline
(included), 7.5 year with Lithium
• Locking screw discourages tampering and battery
theft.
SPECIFICATIONS
Models: For specific model information, see Specification
Data, form 63-1332.
Environmental Ratings:
• Wall Module Operating Temperature: 45° to 99°F
(7° to 37°C).
• Receiver Operating Temperature: -40° to 150°F
(-40° to 65.5°C).
• Storage Temperature: -40° to 150°F (-40° to 65.5°C).
• Operating Humidity: 5% to 95% RH (non-condensing)
Accuracy: +/- 1ºF (+/- 0.5ºC) across 12ºC to 30ºC
Setpoint Range for TR23: 56° to 84°F (13° to 29°C)
Accessories: 50007298-001 (pack of 12) medium, cover
plate; 6-7/8 x 5 in. (175 x 127 mm).
Power:
Receiver Voltage: 20 – 30VAC/DC, 50/60Hz; 24VAC typical
Housing:
• Wall Module: UL94-HB
• Receiver: UL94-5VA
Radio Frequency 2.4 GHz (IEEE Std 802.15.4-2003
compliant)
• Open Range: 3000 feet
• Typical Range: 100 feet
• Output power: 16dBm
• Receiver power consumption: <1.5 VA@24VAC
"Este equipamento opera em caráter
secundário, isto é, não tem direito à proteção
contra interferência prejudicial, mesmo de
estações do mesmo tipo, e não pode causar
interferência a sistemas operando em caráter
primário."
62-0291-09
loading

Summary of Contents for Honeywell TR21-WS

  • Page 1 • Locking screw discourages tampering and battery theft. APPLICATION SPECIFICATIONS The WRECVR receiver and TR21-WS, TR23-WS, TR21-WK, and TR23-WK are a family of wireless wall modules and Models: For specific model information, see Specification receiver for use with: Data, form 63-1332.
  • Page 2: Installation

    TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR INSTALLATION Approximate battery life under normal operating conditions: • 5 years with two AA Alkaline batteries (included) • 7.5 years with two AA Lithium Batteries CAUTION Transmission interval: 30 seconds Erratic System Operation Hazard. Pressing override button or signal strength button will force an Failure to follow proper wiring practices can immediate transmission.
  • Page 3 TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR Mounting the Wall Module If desired, insert the two red end stoppers into temperature scale to set the desired temperature range limit. See Fig. 3. Mount the wall module on an inside wall approximately 54 in.
  • Page 4 TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR W7751H MICROBRIDGE DP SENSOR TRIAC EQUIVALENT NOT EARTH GROUND CIRCUIT E-BUS WALL MODULE POWER M29051 Fig. 5. Wiring receiver to Excel 10. 2 2 2 2 2 2 2 2 3 1 2 3 4 5 6 7 8 0...
  • Page 5 TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR SUBBASE NOTE 1. WHEN USING THE WIRELESS TR23 SENSOR WITH THE T7350 BE SURE TO USE THE RELATIVE SCALE SETPOINT KNOB. POWER NOTE 2. WHEN USING THE WIRELESS TR21 SENSOR WITH THE T7350, DO NOT WIRE TERMINAL 5 AND TERMINAL 6.
  • Page 6 DIP switches S2/S3 are provided for two reasons: LOCKING SIGNAL LED SIGNAL STRENGTH BUTTON • If the wall module needs to be replaced, a TR21-WS or SCREW SLOT M29048 TR23-WS wall module can be purchased. To bind any wall Fig. 9. Wall module features (TR23 shown).
  • Page 7: Low Battery Signal

    TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR Table 3. Controller Descriptions. Controller Description Spyder/ComfortPoint Default setting. For use with Spyder and Comfort Point 20K ohm controllers 20Kohm, XL 10 For use with XL10 VAV, W7750, W7751, etc. Honeywell Other For use with XL600/500/100.
  • Page 8 However, because of the variability of various environments, Honeywell cannot guarantee that these wireless kits will work successfully in every application, even when a green signal strength is indicated on initial installation. Although no...

This manual is also suitable for:

Tr21-wkTr23-wsTr23-wkTr21-wsuTr23-wsuWrecvr ... Show all