Parameters - Honeywell Krom Schroder BCU 580 Technical Information

Burner control unit
Table of Contents

Parameters

10 Parameters
Any changes to parameters will be saved to the parameter chip card.
Name
Burner 1 FS1 flame signal switch-off
threshold
Burner 2 flame signal switch-off
threshold FS2
Flame control
High temperature operation
Burner 1 start-up attempts
Burner 2 start-up attempts
Restart
Safety time during operation
BCU 580 · Edition 11.15l
Parameter
Value range
01
0 – 20
02
0 – 20
0
1
2
3
04
4
5
6
7
8
0
06
2
3
1
07
2
3
1
08
2
3
0
1
2
09
3
4
5
6
19
0; 1; 2
Description
Burner 1 FS1 flame signal switch-off threshold in µA
Burner 2 FS2 flame signal switch-off threshold in µA
Ionization
UVS
UVD
Ionization1 and UVS 2
Ionization1 and UVD 2
UVS 1 and ionization 2
UVD 1 and UVD 2
UVD 1 and ionization 2
UVD 1 and UVS 2
Off
Intermittent operation with UVS
Continuous operation with ionization/UVD
1 start-up attempt
2 start-up attempts
3 start-up attempts
1 start-up attempt
2 start-up attempts
3 start-up attempts
Off
Burner 1
Burner 2
Burner 1 and burner 2
Max. 5 × in 15 min. for burner 1
Max. 5 × in 15 min. for burner 2
Max. 5 × in 15 min. for burner 1 and burner 2
Time in seconds
Factory default
settings
2
(5 when P04 = 1)
2
(5 when P04 = 1)
0
0
1
1
0
1
54
Table of Contents
loading