Mechanical Data; Environment; Dimensions - Honeywell Krom Schroder BCU 580 Technical Information

Burner control unit
Table of Contents
Technical data

16 .2 Mechanical data

Weight: 0.7 kg.
Connections
– Screw terminals:
nominal cross-section 0.2 mm²,
wire cross-section rigid min. 0.2 mm²,
wire cross-section rigid max. 2.5 mm²,
wire cross-section AWG/kcmil min. 24,
wire cross-section AWG/kcmil max. 12.
– Spring force terminal:
nominal cross-section 2 x 1.5 mm²,
wire cross-section min. 0.2 mm²,
wire cross-section AWG min. 24,
wire cross-section AWG max. 16,
wire cross-section max. 1.5 mm²,
rated current 10 A (8 A UL), to be observed in case of
daisy chain.

16 .3 Environment

Ambient temperature:
-20 to +60°C (-4 to +140°F),
no condensation permitted.
Enclosure: IP 20 pursuant to IEC 529.
Installation location: min. IP 54 (for installation in a
control cabinet).
BCU 580 · Edition 11.15l

16 .4 Dimensions

100
mm
122