Configure the circuit through programming (see Section 9.6).
Maximum voltage drop is 3V per Class A circuit. See Table 4.4.

Class A Notification Wiring

You must use an appliance from the list of compatible appliances in Appendix A.
To install a Class A notification appliance circuit:
1.
Wire the Class A notification appliances as shown in Figure 4.44.
CAUTION:
!
For proper system supervision do not use looped wire under terminals marked + and – of the Flexput connectors. Break wire runs to provide
supervision of connections.
51
All Circuits are Synchronized (Regulated). Rated at
27.4 VDC @ 3A Max.
Figure 4.43 Class B Notification Appliance Circuit Wiring
Current
1.0A
1.5A
2.0A
2.5A
3.0A
Table 4.4 Maximum Impedance Class A
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Max. Impedance: 1.5
Alarm Polarity Shown
4.7 kEOL
Notification Wiring
Supervised
Power Limited
Maximum Impedance
3
2
1.5
1.2
1.0