INSTALLATION AND MAINTENANCE INSTRUCTIONS
Farenhyt™ Series
IDP-Relay
SPECIFICATIONS
Normal Operating Voltage:
Maximum Current Draw:
Average Operating Current:
EOL Resistance:
Temperature Range:
Humidity:
Dimensions:
Accessories:
RELAY CONTACT RATINGS:
CURRENT RATING
2 A
3 A
2 A
0.46 A
0.7 A
0.9 A
0.5 A
0.3 A
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate Honeywell Farenhyt series control panel installation manual
for detailed system information. If the modules will be installed in an existing
operational system, inform the operator and local authority that the system
will be temporarily out of service. Disconnect power to the control panel be-
fore installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The IDP-Relay is intended for use in intelligent, two-wire systems where
the individual address of each module is selected using the built-in rotary
switches. It allows a compatible control panel to switch discrete contacts
by code command. The relay contains two isolated sets of Form-C contacts,
which operate as a DPDT switch and are rated in accordance with the table in
the manual. Circuit connections to the relay contacts are not supervised by the
module. The module also has a panel controlled LED indicator.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compat-
ible Honeywell Farenhyt series system control panel (list available from
Honeywell).
15 to 32 VDC
6.5 mA (LED on)
230μA direct poll; 255μA group poll
Not used
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Non-condensing
4.675" H x 4.275" W x 1.4" D (Mounts to a 4" square by 2
SMB500 Electrical Box
MAXIMUM VOLTAGE
25 VAC
30 VDC
30 VDC
30 VDC
70.7 VAC
125 VDC
125 VAC
125 VAC
12 Clintonville Road, Northford, CT 06472-1610
1
/
" deep box.)
8
LOAD DESCRIPTION
PF = 0.35
RESISTIVE
RESISTIVE
(L/R = 20MS)
PF = 0.35
RESISTIVE
PF = 0.75
PF = 0.35
FIGURE 1. CONTROLS AND INDICATORS:
MOUNTING
The IDP-Relay mounts directly to 4-inch square electrical boxes (see Figure
2A). The box must have a minimum depth of 2
electrical boxes (SMB500) are available from Honeywell. The module can also
mount to the SK-DUCT or DNR(W) housing.
1
Phone: 203-484-7161 Fax: 203-484-7118
www.Farenhyt.com
APPLICATION
NON-CODED
NON-CODED
CODED
NON-CODED
NON-CODED
NON-CODED
NON-CODED
NON-CODED
C1071-00
1
/
inches. Surface mounted
8
I56-3601-005
04-21
loading

Summary of Contents for Honeywell Farenhyt Series

  • Page 1 Circuit connections to the relay contacts are not supervised by the module. The module also has a panel controlled LED indicator. COMPATIBILITY REQUIREMENTS To ensure proper operation, this module shall be connected to a compat- ible Honeywell Farenhyt series system control panel (list available from Honeywell). C1071-00 MOUNTING The IDP-Relay mounts directly to 4-inch square electrical boxes (see Figure 2A).
  • Page 2 *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE. C0946-00 Farenhyt™ is a trademark of and Honeywell ® is a registered trademark of Honeywell International, Inc. I56-3601-005 ©2017 Honeywell. 04-21...

This manual is also suitable for:

Farenhyt idp-relay