Interfaces and Bus Connections

The Excel 800 System can be connected to the following
devices and systems:
Panel Bus
 For communication with up to 16 Panel Bus I/O modules
 Polarity-insensitive
L
W
Bus
ON
ORKS
 For communication with other L
within the building
 FTT10, link power compatible
 Polarity-insensitive
C-Bus
 For communication with other controllers, e.g., existing
Excel 500 Controllers
HMI
 For connecting an operator interface, e.g., XI582,
XI882A, or a laptop, e.g., for CARE
Modem
 For connecting a modem or an ISDN terminal adapter

Technical Data

System Data
Operating voltage
Max. number of C-Bus
participants
Power consumption
Push-in terminals
Screw-type terminals
Overvoltage protection All inputs and outputs are
Calculated lifetime of
weakest component
under typical operating
conditions
Table 7 System data
EN1B-0375GE51 R0910
W
Bus devices
ON
ORKS
24 VAC, ± 20%, 21 ... 30 VDC
30
Max. 3.57 A
(1 XCL8010 Controller
+ 16 I/O modules)
2
1.5 mm
2
1.5 mm
protected against 24 VAC and
40 VDC overvoltage as well as
against short-circuiting.
MTBF
13.7 years
Standards
Protection class
Product standard EMC EN 60730-2-9
Testing electrical
components
Certification
System transformer
Low-Voltage Device
Safety Assessment
Table 8 Standards
Operational Environment
Ambient operating
temperature
Ambient operating
humidity
Ambient storage
temperature
Ambient storage
humidity
Vibration under
operation
Dust, vibration
RFI, EMI
Table 9 Operational environment
8
Excel 800
IP20
IEC68
CE
The system transformer(s) must
be safety isolating transformers
according to IEC 61558-2-6.
In the U.S.A. and Canada, NEC
Class 2 transformers must be
used.
EN 60730-1
EN 60730-2-9
0 ... 50 °C (32 ... 122 °F)
5 ... 93% relative humidity
(non-condensing)
–20 ... 70 °C (–4 ... +158 °F)
5 ... 95% relative humidity
(non-condensing)
0.024" double amplitude
(2 ... 30 Hz),
0.6 g (30 ... 300 Hz)
According to EN60730-1