Specifications & Dimensions; Technical Data - Allen-Bradley Bulletin 161 B Series User Manual

0.2-3.7kw (0.3 to 5 hp)
Table of Contents
Chapter 5 – Specifications & Dimensions

Technical Data

Series
Type
Drive rating kW (HP)
115V Input rated current (A)
230V 1F Input rated current (A)
230V 3F Input rated current (A)
Output rated current (A)
Power Dissipation (W)
Mass (kg)
Input voltage (V)
Output voltage
Type of protection
PWM carrier frequency
V/Hz characteristics
Type of control
Output frequency
Accuracy of frequency
command
Frequency resolution
Overload capacity
Starting torque
DC brake
Analog inputs
Digital inputs
Analog outputs
Digital outputs
Relay output
Protection functions
Other functions
Ambient temperature
Relative humidity
Vibration/Shock
Max. installation altitude
Options
Standards
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
A01
A02
A03
0.2 (0.3) 0.4 (0.5) .55 (.75) 0.75 (1) 1.1 (1.5) 1.5 (2)
5.5
10.0
N/A
3.1
5.8
6.7
1.8
3.4
3.9
1.4
2.6
3.0
17
29
33
See dimension drawings on following page.
200 V -10% to 240 V + 5%, 50/60 Hz +/- 5%; 100V -5% to 120V +5%
3 Φ adjustable from 0 to 230V
IP20
0.5 - 16 kHz
Programmable V/Hz ratio, V/Hz control (constant torque, variable torque)
Voltage-driven, PWM sine weighted, IGBT-Power module
0.5 - 360 Hz
Digital:
+/- 0.01% of max. frequency
Analog: +/- 0.2% of max. frequency
Digital: 0.1 Hz, analog: 0.01% of max. frequency
Software: 150% for 60 s (once in a period of 10 min.), Hardware: 220%
min. 150% at frequencies >3 Hz
Starting frequency, braking torque, running times are variable.
0 -10 V, input impedance 10 kΩ
4 - 20 mA, input impedance 250 Ω PTC input
5 programmable level triggered inputs, 24V PNP logic, NO or NC contacts
1 programmable output. 0-10V, 1mA, Accuracy: +/- 5% for frequency, +20% for
current.
2 open collector outputs. 27VDC, 50mA
1 fault indication relay (change-over contact)
Resistive rating: 2.5A at 250VAC – 3A at 30VDC
Inductive rating: 0.2A at 250VAC – .7A at 30VDC
Over-current, over-voltage, under-voltage, electronic motor protection, over-
temperature, ground fault, overload etc. (see Chap.4).
15 preset speeds, PID control, unintentional start protection, RS422 serial interface,
skip frequencies etc.
-10 - +40 °C (up to +50 °C by removing top cover, reducing carrier frequency to
2kHz, and derating output current by 20%)
20 - 90% relative humidity, no condensation
Vibration: 0.6G operational / Shock: 10.0G operational
1000 m (3300 ft.) above sea level
Line filter modules
EN 61800-3 EMC guidelines in connection with optional line filter modules
in line with installation guidelines, EN 50178 Low-Voltage guideline,
Bulletin 161
A04
A05
A07
16.0
N/A
N/A
9.0
11.2
16.0
5.2
6.5
9.3
4.0
5.0
7.1
41
53
70
A10
A15
2.2 (3)
3.7 (5)
N/A
N/A
22.5
N/A
13.0
20.0
10.0
15.9
101
169
39
Table of Contents