Installation and Maintenance
REPAIR AND ADJUSTMENT PROCEDURES FOR HONEYWELL MP-953B, MP-953D,
OR MP-953F PNEUMATIC OPERATORS USED ON ARMSTRONG HUMIDIFIERS
This bulletin should be used by experienced personnel as a
guide to the repair and adjustment of Honeywell MP-953B, MP-953D,
or MP-953F pneumatic operators for Armstrong humidifiers.
Selection or installation of equipment should always be
accompanied by competent technical assistance.
to contact Armstrong or its local representative if further
information is required.
WARNING:
BE SURE THAT STEAM SUPPLY VALVE FOR THE HUMIDIFIER IS
OPERATOR.
Maintenance procedures for the Honeywell pneumatic operator
include:
removing the operator from the bonnet, installing the
operator on the bonnet, replacing steam seals, changing operator
springs, replacing the diaphragm, replacing the rolling seal, and
replacing the valve and seat.
REMOVING THE PNEUMATIC OPERATOR
I.
Many repair procedures require that the operator be removed
from the bonnet assembly.
the following steps.
locate the parts by item numbers.
Turn oft steam to the humidifier.
1.
Turn off the instrument air and disconnect the line
2.
from the operator.
Loosen the two set screws (27) on both sides of tne
3.
operator base (26).
Remove operator plug (35) from the MP-953D, or open the
4.
access plate on the MP-953B or MP-953F.
Insert a screwdriver into the slot at the top of the
5.
yoke assembly (36).
screwdriver
disengages from the operator.
Lift the operator from the bonnet.
6.
(See Figure 1 on back cover.)
To remove the operator, perform
Refer to Figure 1 (see back cover) to
Hold the operator and turn
clockwise until the yoke assembly
IB-52
We encourage you