Siemens SITRANS TS100 Compact Operating Instructions page 49

Temperature sensors
Table of Contents
SITRANS TH100/200/300 and display DVM-LCD
You can find the values of ∆T2G in the tables
Table 8-3 Gas Ex i/nA (Page 50),
Table 8-4 Gas Ex i/nA (Page 51),
Table 8-5 Type 2N (Page 51) and
Table 8-6 Type 2N (Page 52) and
∆T2D in the table Table 8-9 Dust Ex i/tb (Page 53) and
Table 8-10 Type 2N (Page 54).
Table 8- 1
Gas hazardous area Zone 1 / 21 / Div. 1
Permitted electrical supply parameters
U
= 30 V
i
I
= 100 mA
i
P
= 750 mW
i
U
= 27 V
i
I
= 90 mA
i
P
= 610 mW
i
U
= 25,2 V
i
I
= 84 mA
i
P
= 530 mW
i
Table 8- 2
Dust hazardous area Zone 21 / Div. 1
Permitted electrical supply parameters
U
= 30 V
i
I
= 100 mA
i
P
= 750 mW
i
U
= 27 V
i
I
= 90 mA
i
P
= 610 mW
i
U
= 25,2 V
i
I
= 84 mA
i
P
= 530 mW
i
See also
Gas hazardous area: Ex i / IS / Ex nA/ec / NI (Page 50)
Dust hazardous area: Ex i / IS / Ex tb / DIP (Page 53)
TS100/TS200/TS300/TS500/TSinsert/TSthermowell
Compact Operating Instructions, 01/2018, A5E03920348-AE
T
= Permissible ambient temperature
3
Assembly of DVM-LCD
A5E33119275 (HW: 05)
T4: -40 °C ≤ T
≤ +75 °C - ∆T2G
3
T6: -40 °C ≤ T
≤ +45 °C - ∆T2G
3
T4: -40 °C ≤ T
≤ +85 °C - ∆T2G
3
T6: -40 °C ≤ T
≤ +50 °C - ∆T2G
3
T4: -40 °C ≤ T
≤ +85 °C - ∆T2G
3
T6: -40 °C ≤ T
≤ +52 °C - ∆T2G
3
T
= Permissible ambient temperature
3
Assembly of DVM-LCD
A5E33119275 (HW: 05)
T85 °C: -40 °C ≤ T
≤ +53°C - ∆T2D
3
T85 °C: -40 °C ≤ T
≤ +63 °C - ∆T2D
3
T85 °C: -40 °C ≤ T
≤ +63 °C - ∆T2D
3
Technical data
8.1 Rated conditions
Assembly of DVM-LCD
7MF4997-1BS (HW: 03)
T4: -40 °C ≤ T
≤ +67 °C - ∆T2G
3
T4: -40 °C ≤ T
≤ 80 °C - ∆T2G
3
T4: -40 °C ≤ T
≤ +85 °C - ∆T2G
3
Assembly of DVM-LCD
7MF4997-1BS (HW: 03)
T85 °C: -40 °C ≤ T
≤ +45°C - ∆T2D
3
T85 °C: -40 °C ≤ T
≤ +60 °C - ∆T2D
3
T85 °C: -40 °C ≤ T
≤ +63 °C - ∆T2D
3
49