Cleaning - Siemens SINAMICS G130 Operating Instructions Manual

Converter built-in units 75 kw-800 kw
Hide thumbs Also See for SINAMICS G130:
Table of Contents
Maintenance and servicing
11.2 Maintenance
11.2.1

Cleaning

Dust deposits
Dust deposits inside the chassis unit must be removed at regular intervals (or at least once a
year) by qualified personnel in line with the relevant safety regulations. The unit must be
cleaned using a brush and vacuum cleaner, and dry compressed air (max. 1 bar) for areas
that cannot be easily reached.
Ventilation
When installing the devices in a cabinet, make sure that the cabinet ventilation slots are not
obstructed. The fan must be checked to make sure that it is functioning correctly.
Cable and screw terminals
Cable and screw terminals must be checked regularly to ensure that they are secure in
position, and if necessary, retightened. Cabling must be checked for defects. Defective parts
must be replaced immediately.
Note
Maintenance intervals
The actual intervals at which maintenance procedures are to be performed depend on the
installation conditions and the operating conditions.
Siemens offers its customers support in the form of a service contract. For further details,
contact your regional office or sales office.
510
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
Table of Contents
loading

Table of Contents