Siemens SINAMICS G130 Operating Instructions Manual
Siemens SINAMICS G130 Operating Instructions Manual

Siemens SINAMICS G130 Operating Instructions Manual

Motor reactors
Hide thumbs Also See for SINAMICS G130:
loading

Summary of Contents for Siemens SINAMICS G130

  • Page 3 ___________________ Safety information ___________________ General ___________________ SINAMICS Mechanical installation ___________________ Electrical installation SINAMICS G130 Motor reactors ___________________ Technical specifications Operating Instructions Firmware version V5.1 11/2017 A5E00409660A...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Table of contents Safety information ........................... 5 General safety instructions ....................... 5 General ..............................11 Mechanical installation .......................... 15 Electrical installation..........................19 Technical specifications ........................21 Motor reactors Operating Instructions, 11/2017, A5E00409660A...
  • Page 6 Table of contents Motor reactors Operating Instructions, 11/2017, A5E00409660A...
  • Page 7: Safety Information

    Safety information General safety instructions WARNING Electric shock and danger to life due to other energy sources Touching live components can result in death or serious injury. • Only work on electrical equipment if you are appropriately qualified. • Always observe the country-specific safety rules for all work. Generally, the following steps apply when establishing safety: 1.
  • Page 8 Safety information 1.1 General safety instructions WARNING Electric shock due to equipment damage Improper handling may cause damage to equipment. For damaged devices, hazardous voltages can be present at the enclosure or at exposed components; if touched, this can result in death or severe injury. •...
  • Page 9 • If you come closer than around 2 m to such components, switch off any radio devices or mobile phones. • Use the "SIEMENS Industry Online Support App" only on equipment that has already been switched off. WARNING Motor fire in the event of insulation overload There is a greater load on the motor insulation as result of a ground fault in an IT system.
  • Page 10 Safety information 1.1 General safety instructions WARNING Fire due to inadequate ventilation clearances Inadequate ventilation clearances can cause overheating of components with subsequent fire and smoke. This can cause severe injury or even death. This can also result in increased downtime and reduced service lives for devices/systems. •...
  • Page 11 Safety information 1.1 General safety instructions Note Important safety instructions for Safety Integrated functions If you want to use Safety Integrated functions, you must observe the safety instructions in the Safety Integrated manuals. Motor reactors Operating Instructions, 11/2017, A5E00409660A...
  • Page 12 Safety information 1.1 General safety instructions Motor reactors Operating Instructions, 11/2017, A5E00409660A...
  • Page 13: General

    General Description Motor reactors reduce the voltage load on the motor windings by reducing the voltage gradients at the motor terminals that occur during converter operation. At the same time, the capacitive charge/discharge currents that occur at the converter output when long motor cables are used are reduced.
  • Page 14 When using components that have not been released, damage or malfunctions can occur at the devices or the system itself. • Only use motor reactors that SIEMENS has released for SINAMICS. NOTICE Risk of damaging the motor reactor by exceeding the maximum output frequency The maximum permissible output frequency when a motor reactor is used is 150 Hz.
  • Page 15 General Assignment of motor reactor and Power Module Table 2- 1 Assignment of motor reactor and Power Module Power Module Unit rating of the Power Module Suitable motor reactor Line voltage 3 AC 380 – 480 V 6SL3310-1GE32-1AA3 110 kW 6SL3000-2BE32-1AA0 6SL3310-1GE32-6AA3 132 kW...
  • Page 16 General Using a motor reactor and dv/dt filter to limit the voltage gradient and transients IGBT converter switching frequencies result in high voltage gradients (dv/dt) at the converter output. If long motor cables are used, this leads to an additional current load on the converter due to capacitive charge/discharge currents.
  • Page 17: Mechanical Installation

    Mechanical installation Dimension drawing Figure 3-1 Dimension drawing, motor reactor Motor reactors Operating Instructions, 11/2017, A5E00409660A...
  • Page 18 Mechanical installation Table 3- 1 Dimensions of motor reactor, 380 V – 480 V 3 AC, part 1 (all specifications in mm) 6SL3000- 2BE32-1AA0 2BE32-6AA0 2BE33-2AA0 2BE33-8AA0 Connection Type 1 Type 1 Type 1 Type 1 type 12.5 12.5 12.5 12.5 Lengths n1 and n2 correspond to the drill hole spacing Table 3- 2...
  • Page 19 Mechanical installation Table 3- 3 Dimensions of motor reactor, 500 V – 600 V 3 AC, part 1 (all specifications in mm) 6SL3000- 2AH31-8AA0 2AH32-4AA0 2AH32-6AA0 2AH33-6AA0 Connection Type 1 Type 1 Type 1 Type 1 type 12.5 12.5 12.5 12.5 Lengths n1 and n2 correspond to the drill hole spacing Table 3- 4...
  • Page 20 Mechanical installation Table 3- 5 Dimensions of motor reactor, 660 V – 690 V 3 AC, part 1 (all specifications in mm) 6SL3000- 2AH31-0AA0 2AH31-5AA0 2AH31-8AA0 2AH32-4AA0 2AH32-6AA0 Connection type Type 1 Type 1 Type 1 Type 1 Type 1 12.5 12.5 12.5...
  • Page 21: Electrical Installation

    Electrical installation Connection When connecting the motor reactor, you must take into account the following conditions to ensure that it functions correctly: ● With analog control cables, connecting the shield at both ends can result in coupled-in noise. To prevent this, the shield must only be connected at one end on the Power Module.
  • Page 22 Electrical installation Motor reactors Operating Instructions, 11/2017, A5E00409660A...
  • Page 23: Technical Specifications

    Technical specifications General technical data Table 5- 1 General technical data Output frequency 0 ... 150 Hz Product standard EN 61800-5-1 Ambient conditions Storage Transport Operation Ambient temperature -25 ... +70 °C -25 ... +70 °C 0 ... +50 °C Relative air humidity (con- 5 ...
  • Page 24 Technical specifications Detailed technical data Table 5- 2 Technical data for motor reactors, 3 AC 380 V ... 480 V, part 1 Article number 6SL3000- 2BE32-1AA0 2BE32-6AA0 2BE33-2AA0 2BE33-8AA0 Suitable for Power Module 6SL3310- 1GE32-1AA3 1GE32-6AA3 1GE33-1AA3 1GE33-8AA3 Rated current Power loss - at 50 Hz 0.436...
  • Page 25 Technical specifications Table 5- 4 Technical data for motor reactors, 3 AC 380 V ... 480 V, part 3 Article number 6SL3000- 2AE41-0AA0 Suitable for Power Module 6SL3310- 1GE41-0AA3 Rated current Power loss - at 50 Hz 0.939 - at 150 Hz 1.062 Connections - to the power module (1U1, 1V1,...
  • Page 26 Technical specifications Table 5- 6 Technical data for motor reactors, 3 AC 500 V ... 600 V, part 2 Article number 6SL3000- 2AH34-5AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0 Suitable for Power Module 6SL3310- 1GF34-1AA03 1GF34-7AA3 1GF35-8AA3 1GF37-4AA3 Rated current Power loss - at 50 Hz 0.481 0.631 0.705...
  • Page 27 Technical specifications Table 5- 8 Technical data for motor reactors, 3 AC 660 V ... 690 V, part 1 Article number 6SL3000- 2AH31-0AA0 2AH31-0AA0 2AH31-5AA0 2AH31-5AA0 Suitable for Power Module 6SL3310- 1GH28-5AA3 1GH31-0AA3 1GH31-2AA3 1GH31-5AA3 Rated current Power loss - at 50 Hz 0.215 0.269 0.237...
  • Page 28 Technical specifications Table 5- 10 Technical data for motor reactors, 3 AC 660 V ... 690 V, part 3 Article number 6SL3000- 2AH34-5AA0 2AH34-7AA0 2AH35-8AA0 2AH38-1AA0 Suitable for Power Module 6SL3310- 1GH34-1AA3 1GH34-7AA3 1GH35-8AA3 1GH37-4AA3 Rated current Power loss - at 50 Hz 0.481 0.631 0.705...
  • Page 29 Motor reactors Operating Instructions, 11/2017, A5E00409660A...