Table B-21. Configuration (Other) Block - Emerson Vilter MicroVission Operation And Service Manual

Hide thumbs Also See for Vilter MicroVission:
Table of Contents
Appendix B • Communication Tables
Ethernet IP
Modbus
Configuration
Address
Address
No. of Cylin-
N67:0
40610
ders
No. of Un-
N67:1
40611
loaders
Suction Pres-
N67:2
40612
sure Control
Available
Suction Pres-
N67:3
40613
sure Control #
of Setpoints
Process Con-
N67:4
40614
trol Available
Process
N67:5
40615
Control # of
Setpoints
B - 16

Table B-21. Configuration (Other) Block

Data Type
(Other)
0 = 2 cyl
1 = 3 cyl
2 = 4 cyl
3 = 5 cyl
ENUM
4 = 6 cyl
5 = 7 cyl
6 = 8 cyl
7 = 12 cyl
8 = 16 cyl
0 = No Unloader
1 = 1 Unloader, 33%
2 = 1 Unloader, 50%
3 = 2 Unloaders, 25, 50%
4 = 2 Unloaders, 25, 50, 75%
5 = 2 Unloaders, 29, 57%
6 = 2 Unloaders, 33, 66%
7 = 2 Unloaders, 40, 60%
8 = 2 Unloaders, 50, 100%
ENUM
9 = 3 Unloaders, 13, 38, 63%
10 = 3 Unloaders, 14, 29, 43, 57%
11 = 3 Unloaders, 17, 33, 50, 66%
12 = 3 Unloaders, 17, 33, 50, 66, 83%
13 = 3 Unloaders, 25, 50, 75%
14 = 3 Unloaders, 33, 50, 66%
15 = 3 Unloaders, 33, 66, 100%
16 = 4 Unloaders, 13, 25, 38, 50, 63, 75%
17 = 4 Unloaders, 25, 50, 75, 100%
INT
0 = No, 1 = Yes
INT
INT
0 = No, 1 = Yes
INT
MicroVission Controller • Operation and Service Manual • Emerson • 2017VM-16 1.0
Value
Lower
Higher
Mode
Range
Range
Read
NA
NA
Read
NA
NA
Read
NA
NA
Read
NA
NA
Read
NA
NA
Read
NA
NA
Table of Contents