Emerson Numatics G2-2 Series Quick Start Manual
Emerson Numatics G2-2 Series Quick Start Manual

Emerson Numatics G2-2 Series Quick Start Manual

Hide thumbs Also See for Numatics G2-2 Series:
Table of Contents
Available languages

Available languages

Quick Links

Getting Started
This is a brief document designed to quickly get you started setting up your valve manifold with an integrated
Numatics' G2-2 Series A-B 1771 Remote I/O communication node. Please note that this document is not
intended to replace the G2-2 Series A-B 1771 Remote I/O Technical Manual, which includes more detailed
technical information. The full technical manual can be found on the Numatics website at
www.numatics.com
1) Initial Unpacking and Inspection
1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.
2) Remove wrapped manifold assembly from box.
a) Remove manifold assembly from anti-static packaging
b) Retain documentation for installation and configuration
3) Examine manifold assembly for any shipping damage such as:
a) Bent pins or connectors
b) Report any damage to shipping carrier immediately
4) Examine manifold assembly for proper ordered configuration. (Valves, I/O, Protocol, etc.)
2) G2-2 Introduction
Below is an example of a 2012 series valve manifold. This fieldbus manifold series is capable of addressing a
total of 128 I/O (up to 1 full rack size). The manifold can be viewed as having two sections to it, the
Side
Discrete I/O Side
and the
I/O Side
supports a maximum of 6 modules totaling 110 I/O. The communication module has two
connectors: a 5-pin communication connector and a 4-pin power connector. Pin-outs for these, along with
I/O connectors, and are labeled on the side of the respective modules.
Dual 25 Pin Sub-D
w/Aux Power
Output Module
G2-2 Series A-B 1771 Remote I/O
or may be ordered by calling 248-887-4111.
Valve Side
. The
(Maximum of 6 Modules)
Discrete I/O
Connectors
I/O Point
LED Status
Indicator(s)
19 Pin Round
Connector Module
8 Connector I/O Module
Terminal Strip Module
3835050 TDG22ABQS3-0
Subject to change without notice
www.numatics.com/fieldbus
Quick Start Manual
supports a maximum of 32 solenoid coils and the
Discrete I/O Side
(Maximum of 32 Solenoids)
Module/
Network
Status LED's
COMM. STATUS
A-B
1771 RIO
FUSE 1
+24V VLV/OUT
FUSE 2
+24V NODE/IN
Communications
Module (Node)
Manual Configuration
Module (MCM)
1/07
Valve Side
Chassis Ground
Connection
Valve
End Plates
Valve
Valve Side
Sub-D Output
Module
Manual
Override
Solenoid LED
Status Indicator
Valve
Discrete
Page 1
Table of Contents
loading

Summary of Contents for Emerson Numatics G2-2 Series

  • Page 1 G2-2 Series A-B 1771 Remote I/O Quick Start Manual Getting Started This is a brief document designed to quickly get you started setting up your valve manifold with an integrated Numatics’ G2-2 Series A-B 1771 Remote I/O communication node. Please note that this document is not intended to replace the G2-2 Series A-B 1771 Remote I/O Technical Manual, which includes more detailed technical information.
  • Page 2 G2-2 Series A-B 1771 Remote I/O Quick Start Manual 3) MCM - Manual Configuration Module DIP Switch Rotary Switch (SW2) (SW3) DIP Switch Rotary Switch (SW1) (SW4) 5 6 7 8 5 6 7 8 All DIP switches shown in the "OFF" position The MCM is the module that allows the user to manually set baud rate, rack address and other user definable options.
  • Page 3 G2-2 Series A-B 1771 Remote I/O Quick Start Manual MCM Settings DIP Switch Settings (SW1) Baud Rate: SW1-1 SW1-2 Kbaud Off* Off* 57.6* 115.2 230.4 230.4 Processor Restart/Lockout: Switch Setting Description SW1-5 Off* Processor Restart SW1-5 Processor Lockout Hold Last State: Switch Setting Description...
  • Page 4: Self-Test Mode

    G2-2 Series A-B 1771 Remote I/O Quick Start Manual 4) Self-Test Mode An internal diagnostic tool can also be enabled using the optional MCM module. This tool allows the user to confirm that all of the Inputs and Outputs on the manifold are fully functional without needing a network connection or controller.
  • Page 5 G2-2 Series A-B 1771 Remote I/O Quick Start Manual 5) I/O Mapping Example Example: Assumed Settings - Single Z-Boards used with single solenoid valves - Double Z-Boards used with double solenoid valves - Manifold I/O Size = ½ Rack - Starting Quarter = 1st - Valve Output Configuration = 32 Coils Discrete I/O Configuration Module Type...
  • Page 6 G2-2 Series A-B 1771 Remote I/O Quick Start Manual I/O Mapping Table Example Continued Output Table WORD BYTE Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil Valve Coil No. 8 No. 7 No. 6 No.
  • Page 7: Ground Wiring

    G2-2 Series A-B 1771 Remote I/O Quick Start Manual 6) Output Short Circuit Protection (Status Input Bits) Status Input Bits report the integrity of the load being driven by the output driver. They must be mapped to the scanner as part of the Input Size Value. Please refer to the table below for Status Input Bit action during fault condition: Output Type Output State...
  • Page 8 G2-2 Series A-B 1771 Remote I/O Quick Start Manual 8) Communication Module Connector Pin-Outs Remote I/O Communication Connector Pin-Out Pin No. Function Description Shield Cable shield Clear RIO Line #2 Blue RIO Line #1 Earth Ground Protective Earth Not Used Auxiliary Power Connector Pin-Out Pin No.
  • Page 9: Led Functions

    G2-2 Series A-B 1771 Remote I/O Quick Start Manual 9) LED Functions Upon power up, the LEDs indicate the status of the unit. There are five LEDs on the G2-2 A-B 1771 Remote I/O node; one for Communication Status, two for internal fuse integrity, and two for Aux. Power status. LED Name Color Status...
  • Page 10: Factory Default Settings

    G2-2 Series A-B 1771 Remote I/O Quick Start Manual 10) Factory Default Settings Unless otherwise requested, all standard G2-2 Series A-B 1771 Remote I/O manifolds ship with specific factory default settings. Below is a list of the factory default settings: Description Default Settings Rack Address...
  • Page 11: Pour Commencer

    Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S Pour commencer Ce document décrit le démarrage rapide de votre îlot de distribution à nœud de communication Remote E/S A-B 1771 série G2-2 intégré. Veuillez noter que ce document n'est pas destiné à remplacer le Manuel technique A-B 1771 Remote E/S Série G2-2 qui contient des informations techniques plus détaillées.
  • Page 12 Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S 3) MCM – Module de configuration manuelle (option) DIP Switch Rotary Switch (SW2) (SW3) DIP Switch Rotary Switch (SW1) (SW4) 5 6 7 8 5 6 7 8 All DIP switches shown in the "OFF" position Le MCM (module de configuration manuelle) permet à...
  • Page 13 Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S Réglages du MCM Réglages des DIP switchs (SW1) Taux Baud : SW1-1 SW1-2 Kbaud Off* Off* 57.6* 115.2 230.4 230.4 Redémarrage / blocage de redémarrage du processeur : Switch Réglage Description SW1-5...
  • Page 14 Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S 4) Mode auto-test Un outil diagnostic interne peut également être activé par le module MCM optionnel. Cet outil permet à l'utilisateur de s'assurer que toutes les entrées et sorties sur l'îlot sont complètement opérationnelles, sans besoin de connexion réseau, ni de contrôleur.
  • Page 15 Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S 5) Exemple de mapping des E/S Exemple : Réglages présumés - Cartes Z-Boards simples utilisés avec les électrodistributeurs simples. - Cartes Z-Boards doubles utilisés avec les électrodistributeurs doubles. - Taille des E/S de l'îlot = demi-rack. - Quart de démarrage = 1er - Configuration des sorties électrodistributeur = 32 bobines.
  • Page 16 Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S Exemple de mapping des E/S - continuation Tableau des sorties Octet Bobine no. 8 Bobine no. 7 Bobine no. 6 Bobine no. 5 Bobine no. 4 Bobine no. 3 Bobine no.
  • Page 17: Mise À La Terre

    Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S 6) Protection des sorties contre les courts-circuits (bits d'entrée d'état) Les bits d'entrée d'état signalent l'intégrité de la charge pilotée par le pilote de sortie. Ils doivent être mappés sur le scanner comme partie de la valeur de la taille de l'entrée.
  • Page 18 Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S 8) Affectation des broches du connecteur du module de communication Affectation des broches du connecteur de communication Remote E/S No. de Fonction Description broche Blindage Blindage de câble (effacer) Clear Ligne RIO no.
  • Page 19 Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S 9) Fonction des voyants LED A la mise sous tension, les voyants LED indiquent l'état de l'unité. Le noeud A-B 1771 Remote E/S série G2-2 dispose de cinq voyants LED : un pour l'état de communication, deux pour l'intégrité des fusibles internes, deux pour l'état de l'alimentation auxiliaire.
  • Page 20: Support Technique

    Guide de Démarrage Rapide Série 2-2 - A-B 1771 Remote E/S 10) Réglages par défaut programmés en usine Sauf demande contraire, tous les îlots standard A-B 1771 Remote E/S série G2-2sont fournis d'usine avec les réglages par défaut . Ci-dessous une liste des réglages par défaut. Description Default Settings Adresse du rack...

This manual is also suitable for:

Numatics g2-2 a-b 1771 remote i/o

Table of Contents