Mitsubishi Electric RJ51AW12AL User Manual page 32

Melsec iq-r anywireaslink master module
Hide thumbs Also See for RJ51AW12AL:
Table of Contents
Precautions
• In the AnyWireASLINK system, signals and power are supplied to a slave module with two transmission cables: DP and
DN. Therefore, use a stranded wire of 1.25 or larger as the main line.
• Wires such as general-purpose wires, cabtyre cables, and flat cables can be used.
• Do not run multiple transmission cables (DP, DN) using a multicore cable. Run multiple transmission cables (DP, DN) are
affected by noise, causing a malfunction.
DP
DN
DP
DN
• The voltage should not fall below the lower limit of the allowable voltage range due to a voltage drop caused by the cable. If
the voltage falls below the lower limit, malfunctions may occur.
• Do not connect soldered cables directly to the terminals. Doing so may loosen the screws, resulting in a poor contact.
• Use bar solderless terminals for the wiring to the terminal block. If inserted as is, a stripped cable cannot be clamped
properly in a wire insertion opening.
• Use a crimping tool to connect a bar solderless terminal to a cable.
• Before inserting a bar solderless terminal, check the shapes of the wire insertion opening and bar solderless terminal.
Then, insert the terminal in the correct orientation. A bar solderless terminal wider than the wire insertion opening may
damage the terminal block. ( Page 31 Solderless terminal)
• Signal names are not printed on the transmission cable terminal block. To avoid incorrect wiring, wire cables to the terminal
block attached to the RJ51AW12AL.
• Do not insert multiple bar solderless terminals into one wire insertion opening. Doing so may cause damage on the terminal
block or cable, or malfunction.
6 WIRING
30
6.2 Wiring Method
DP
DN
DP
DN