Door Width Self-Learning - Emerson EV3200-2S0002S Manual

Hide thumbs Also See for EV3200-2S0002S:
A
Terminal
PA1, PC1
PA2, PC2
PA3, PB3, PC3
 
5. Door Width Self‐learning 
1. Do the wiring
2. Switch on the inverter, set F9.18 to 3 to restore the factory settings.
3. Set F0.01 to 1, set F4.01 and F4.02 (0: forward, 1: reverse) correctly. After exiting the
programming status, press
adjust F4.02 setting according to the actual operating conditions. If over current or over load
occurs, or the output current exceeds the motor rated current, adjust the setting of F4.02 to ensure
correct PG parameter settings, and restart the inverter. F4.11Asynchronous single/dual motor
selection (F4.11=1 dual motor)
4. Switch off the inverter, connect the elevator door mechanical system and switch on the inverter
again.
5. Set F0.02 to 1 (keypad control mode), select auto-learning speed properly via F4.04, set F4.05
to 1, press
to start door-width auto learning, and the motor operates according to the
procedures of CD→OD→CD. The inverter stops after the last motor catching. The door width
information will be saved automatically after auto-learning.
Terminal function
When F9.22 is 0: normally closed
contact output
When F9.22 is 1: normally open
contact output
When F9.22 is 0: normally closed
contact output
When F9.22 is 1: normally open
contact output
PA3, PB3: Normally closed
contact output
PA3, PC3: Normally open
contact output
(or
) to start the operation in keypad control mode, and
EV3200
Contact rating
AC: 250V/1A (cosΦ=0.4), 250V/2A
(cosΦ=1)
DC: 30V/1A
‐ 9 ‐ 
PA1 PC1
PA2
PC2
PA3
PB3
A amplified view
Specifications
PC3
loading

This manual is also suitable for:

Ev3200-2s0002aEv3200-2s0004sEv3200-2s0004a