Coin Cell Battery

The coin cell battery is present on all PXC-36 Compact Series and on Version 2 or
later of PXC-16 and PXC-24. The hardware version is indicated in the Product Number
as follows:
PXC16
The number after
PXC24.2-PE.A is Version 2.
PXC16
No number after
PE.A is Version 1.
CAUTION
Batteries
Failure to change a DEAD lithium coin cell battery will result in loss of current time-
date, which may cause loss of data or building control.
Establish a preventative maintenance schedule based on expected battery usage and
life cycle.
The coin cell battery maintains the current time-date in the Real Time Clock (RTC)
when power to the field panel is off.
There is no physical status on the field panel for a dead coin cell battery.
If the coin cell battery is dead or missing when power is off, then RTC time-date is
reset as follows:
If the field panel resides on an ALN with an Insight workstation, the Insight
workstation sets the time-date when the field panel returns to the network.
If the field panel resides on an ALN without an Insight workstation, the time-
date is synchronized with the network time during the next automatic daily time
update.
When the PXC Compact is operating in P1 mode, if the coin cell battery is dead or
missing when power is off, RTC time-date is reset to the factory default. RTC time-
date and must be set manually or by PPCL to ensure time-date based applications
operate as expected.
For more information on time synchronization, see the APOGEE P2 ALN Field Panel
User's Manual (125-3019) or the APOGEE BACnet ALN Field Panel User's Manual
(125-3020) (125-3019 or 125-3020).