Siemens PXC00-PE96.A Installation Instructions

Siemens PXC00-PE96.A Installation Instructions

Modbus driver for pxc-modular and pxc-36

Quick Links

Modbus Driver for PXC-Modular and PXC-36
These installation instructions cover the connection of
the Modbus and Modbus 250/500/1000 Driver to the
vendor's Modbus system only.
For hardware installation of the PXC Modular, see
PXC Modular Series Installation Instructions
the
(553-638).
For hardware installation of the PXC-36, see the
PXC Compact 36 Installation Instructions
504).
Product Description
The Modbus and Modbus 250/500/1000 Driver
enables communication between the APOGEE®
Automation System and the Modbus system.
Product Numbers
PXC Modular
PXC00-PE96.A
PXC Modular, Ethernet or RS-485
ALN, 96 FLN nodes
PXC00-E96.A
PXC Modular, BACnet/IP or MS/TP
ALN, 96 FLN nodes
PXC100-PE96.A
PXC Modular, Ethernet or RS-485
ALN, 96 FLN nodes, TX-I/O module
support
PXC100-E96.A
PXC Modular, BACnet/IP or MS/TP
ALN, 96 FLN nodes, TX-I/O module
support
PXX-485.3
Expansion Module, three RS-485
FLN connections
PXC-36
PXC36-PE.A
PXC Compact, 36 point, Ethernet/IP
or RS-485 ALN
PXC36-E.A
PXC Compact, 36 point, BACnet/IP
or MS/TP ALN
PXC36-PEF.A
PXC Compact, 36 point, Ethernet/IP
or RS-485 ALN. Includes licenses
for TX-I/O module and P1 FLN
support.
PXC36-EF.A
PXC Compact, 36 point, BACnet/IP
or MS/TP ALN. Includes licenses
for TX-I/O module and P1 FLN
support.
Siemens Industry, Inc.
Licenses
LSM-INT-MDBS
LSM-INT-
MDBS1000
LSM-INT-
MDBS500
(553-
LSM-INT-
MDBS250
Accessories
538-670
538-675
538-755
538-760
536-004
Caution Notation
Expected Installation Time
The expected installation time is 7 minutes if no cable
must be made and the driver does not use a Trunk
Interface (see Figure 2), or 30 minutes if a cable must
be made or if the driver uses a Trunk Interface (see
Figure 1 and Figure 2).
Required Tools and Materials
Flat-blade screwdriver (1/8-inch blade width).
Wire strippers.
Cabling and connectors. See the
Driver to the Vendor's Modbus Master or Modbus
Slave Devices
Installation Instructions
Document No. 565-411
License for Modbus Driver on PXC
Modular or PXC-36
License for Modbus 1000 Driver on
PXC Modular or PXC-36
License for Modbus 500 Driver on
PXC Modular or PXC-36
License for Modbus 250 Driver on
PXC Modular or PXC-36
Trunk Interface II, 115V
Trunk Interface II, 230V
Trunk/RS-422 Interface (115V
Power)
Trunk/RS-422 Interface (230V
Power)
RS-232 Cable
CAUTION
Equipment damage or loss of data
may occur if you do not follow a
procedure as specified.
Connecting the
section.
April 2, 2014
1
565-411
loading

Summary of Contents for Siemens PXC00-PE96.A

  • Page 1 PXC Compact, 36 point, BACnet/IP or MS/TP ALN. Includes licenses Connecting the Cabling and connectors. See the  for TX-I/O module and P1 FLN Driver to the Vendor's Modbus Master or Modbus support. Slave Devices section. Siemens Industry, Inc. 565-411...
  • Page 2 4. If applicable, plug in the power supply for the Trunk/RS-422 or Trunk Interface II per the diagram in Figure 1 or Figure 2. NOTE: For Modbus over Ethernet, use IEEE 802.3 standard Ethernet connections and cabling to complete your network infrastructure. Siemens Industry, Inc. 565-411...
  • Page 3 Document No. 565-411 Installation Instructions April 2, 2014 Figure 2: Using a Trunk Interface II to Connect the Driver to the Vendor’s Modbus Master or Modbus Slave Device. Siemens Industry, Inc. 565-411...
  • Page 4 Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. APOGEE and Insight are registered trademarks of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners.

This manual is also suitable for:

Pxc modular seriesPxc-36 seriesPxc00-e96.aPxc100-pe96.aPxc100-e96.aPxc36-e.a ... Show all