1 > TAbLE C550 Hex : Main measurements allocated from CT (current transformer) and VT (voltage
transformer) values
Decimal
Hex.
No. of
Description
address
address
words
50512
C550
2
hour meter
50514
C552
2
phase to phase voltage U12
50516
C554
2
phase to phase voltage U23
50518
C556
2
phase to phase voltage U31
50520
C558
2
phase to neutral voltage phase 1
50522
C55A
2
phase to neutral voltage phase 2
50524
C55C
2
phase to neutral voltage phase 3
50526
C55E
2
frequency
50528
C560
2
phase current 1
50530
C562
2
phase current 2
50532
C564
2
phase current 3
50534
C566
2
neutral current
50536
C568
2
Σ active power +/-
50538
C56A
2
Σ reactive power +/-
50540
C56C
2
Σ apparent power
50542
C56E
2
Σ power factor -: leading and + : lagging
50544
C570
2
active power phase 1 +/-
50546
C572
2
active power phase 2 +/-
50548
C574
2
active power phase 3 +/-
50550
C576
2
reactive power phase 1 +/-
50552
C578
2
reactive power phase 2 +/-
50554
C57A
2
reactive power phase 3 +/-
50556
C57C
2
apparent power phase 1
50558
C57E
2
apparent power phase 2
50560
C580
2
apparent power phase 3
50562
C582
2
power factor phase 1 -: leading and + : lagging
50564
C584
2
power factor phase 2 -: leading and + : lagging
50566
C586
2
power factor phase 3 -: leading and + : lagging
50568
C588
2
Reserved for manufacturer
50570
C58A
2
Reserved for manufacturer
50572
C58C
2
Reserved for manufacturer
10
DIRIS A40/A41 - Ref.: 536 103 B GB
®
Unit
JBUS function
available
1/100 h
V/100
V/100
V/100
V/100
V/100
V/100
Hz/100
mA
mA
mA
mA
kW/100
kvar/100
kVA/100
0,001
kW/100
kW/100
kW/100
kvar/100
kvar/100
kvar/100
kVA/100
kVA/100
kVA/100
0,001
0,001
0,001
-
-
-
a : new COmmuniCatiOn taBle frOm 01/2009
2 > TAbLE C650 Hex : Energy monitoring
Decimal
Hex.
address
address
50768
C650
50770
C652
50772
C654
50774
C656
50776
C658
3
50778
C65A
3
50770
C652
3
50772
C654
3
50774
C656
3
50776
C658
3
50778
C65A
3
50780
C65C
3
50782
C65E
3
50784
C660
3
50786
C662
3
50788
C664
3
50790
C666
3
50792
C668
3
50794
C66A
3
50796
C66C
3
50798
C66E
3
50800
C670
3
50802
C672
3
50804
C674
3
50806
C676
3
50808
C678
3
50810
C67A
3
50812
C67C
3
50814
C67E
3
50816
C680
3
50816
C680
3
50817
C681
3
3 > TAbLE C750 Hex : Additional measurements allocated from CT values (current transformer) and VT
3
(voltage transformer) values
3
3
Decimal
Hex.
address
address
51024
C750
51026
C752
51028
C754
51030
C756
51032
C758
51034
C75A
51036
C75C
51038
C75E
51040
C760
51042
C762
51044
C764
51046
C766
51048
C768
51050
C76A
51052
C76C
51054
C76E
51056
C770
DIRIS A40/A41 - RS485 - JBUS/MODBUS
No. of
Description
words
2
hour meter
2
Reserved for manufacturer
2
Reserved for manufacturer
2
Reserved for manufacturer
2
Reserved for manufacturer
2
Reserved for manufacturer
2
active energy +
2
reactive energy +
2
apparent apparente
2
active energy -
2
active energy +
2
No. Compteurs d'Impulsions
2
pulse meter 1
2
pulse meter 2
2
pulse meter 3
2
pulse meter 4
2
pulse meter 5
2
pulse meter 6
2
Reserved for manufacturer
2
Reserved for manufacturer
2
Reserved for manufacturer
2
Reserved for manufacturer
2
S Predicted active power
2
S Predicted reactive power
2
S Predicted apparent power
2
Ea+ between 2 tops
2
Ea- between 2 tops
2
Er+ between 2 tops
2
Er- between 2 tops
2
Reserved for manufacturer
1
Reserved for manufacturer
1
Reserved for manufacturer
No. of
Description
words
2
avg U12
2
avg U23
2
avg U31
2
avg V1
2
avg V2
2
avg V3
2
avg F
2
avg I1
2
avg I2
2
avg I3
2
avg In
2
avg Σ active power +
2
avg Σ active power -
2
avg Σ reactive power +
2
avg Σ reactive power -
2
avg Σ apparent power
2
max/avg U12
®
COmmuniCatiOn
Unit
JBUS function
available
1/100 h
3
-
3
-
3
-
3
-
3
-
3
kWh
3
kvarh
3
kVAh
3
kWh
3
kWh
3
-
3
-
3
-
3
-
3
-
3
-
3
-
3
-
3
-
3
-
3
-
3
kW/100
3
kvar/100
3
kVA/100
3
0,1 Ws
3
0,1 Ws
3
0,1 vars
3
0,1 vars
3
-
3
-
3
-
3
Unit
JBUS function
available
V/100
3
V/100
3
V/100
3
V/100
3
V/100
3
V/100
3
Hz/100
3
mA
3
mA
3
mA
3
mA
3
kW/100
3
kW/100
3
kvar/100
3
kvar/100
3
kVA/100
3
V/100
3
DIRIS A40/A41 - Ref.: 536 103 B GB