Section 1: Introduction; Application; Responses; Input Power Requirements - Honeywell FS10-R Installation Manual And Operating Manual

Multi-spectral digital infrared electro-optical fire detector
Table of Contents

SECTION 1: INTRODUCTION

1.1
1.2
1.3
1.4
HONEYWELL

Application

The Honeywell Analytics Models FS10-R  (relay output) are
unitized (stand-alone) Flame Detectors designed specifically for
detecting and alarming to fires in electrostatic powder or paint spray
booths and paint spray lines in industrial and automotive
applications. These multi-spectral, digital, electro-optical, patented
Flame Detectors are housed in explosion proof enclosures and
feature automatic "through-the-lens" self-test. The Detectors may
be ordered with dry contact relays for interfacing to approved
control panels, and either latching or non-latching outputs. FS10-R
Detectors each contain a built-in controller and are unitized
versions of the proven, large installed base FS10 Flame Detectors
with Card Controllers and FS10 Flame Detectors with Wall-
Mounted Controllers.
The FS10 line of Detectors is designed primarily for indoor
fire detection applications where combustible materials exist.
Typical applications include:
-Automotive Paint Lines
-Paint Kitchens
-Curing Ovens
-Powder Coating Booths
-Compressor Modules
-Diesel Generators

Responses

The FS10-R type Detectors contain Alert / Fire Early Warning,
Fire Alarm and Fault signal relays. The Alert/Fire Early Warning
and Alarm relays are de-energized, and the Fault relay is energized
during normal operation. If a fire occurs, a Fire Alarm is declared
in less than 5.0 seconds.

Input Power Requirements

TM
FS10-R
: The total electrical input power requirement during
normal operation for the Flame Detector is 85 milli-Amps (0.085
Amps) at 24 Volt DC (+/-15%). The maximum current required
during Alarm is 120 milli-Amps.
TM
FirePic
FirePic stores the sensor data of the last six fire events in the
Detector's non-volatile digital memory. FirePic provides the
OPERATOR MANUAL // SECTION 1: INTRODUCTION
-Aerosol Filling
-General Finishing
-Paint Mixing Rooms
-Warehouse Storage
-Liquid Paint Spray Lines
-Internal Storage Tanks