Emerson Rosemount 644 HART Reference Manual page 27

Temperature transmitter, for product shipped before september 2012
Table of Contents
Reference Manual
00809-0100-4728, Rev MB
Using a Field Communicator
The Configure Sensors method will guide you through the configuration of all necessary settings
associated with configuring a sensor including:
For a full list of Sensor Types available with the Rosemount 644 and their associated levels of accuracy,
see
Table A-2 on page
From the HOME screen, enter the Fast Key sequence
Device Dashboard Fast Keys
Using AMS Device Manager
Right click on the device and select Configure.
1. In the left navigation pane choose Manual Setup and choose the Sensor 1 or Sensor 2 tab
depending on the need.
2. Individually select the Sensor Type, Connection, Units and other sensor related information as desired
from the drop down menus on the screen.
3. Click Apply when complete.
Using Local Operator Interface
Reference the below image for guidance on where to find Sensor Configuration in the LOI menu.
Figure 2-6. Configuring Sensors with LOI
VIEW CONFIG
SENSOR CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
* Available only if option code (S) is ordered.
Contact a Emerson Process Management representative for information on the temperature sensors,
thermowells, and accessory mounting hardware that is available through Emerson Process
Management.
2-wire RTD offset
The 2-wire Offset feature allows the measured lead wire resistance to be input and corrected for, which
results in the transmitter adjusting its temperature measurement for the error caused by this added
resistance. Because of a lack of lead wire compensation within the RTD, temperature measurements
made with a 2-wire RTD are often inaccurate.
This feature can be configured as a subset of the Sensor Configuration process in the Field
Communicator, AMS Device Manager, and the Local Operator Interface.
To utilize this feature properly perform the following steps:
Configuration
110.
VIEW SENSOR
VIEW SENSOR
SENSOR CONFIG
SENSOR CONFIG
BACK TO MENU
EXIT MENU
Configuration
2, 1, 1
VIEW S1 CONFIG
VIEW S2 CONFIG*
BACK TO MENU
EXIT MENU
SENSOR 1 CONFIG
SENSOR 2 CONFIG*
BACK TO MENU
EXIT MENU
July 2016
17