Allen-Bradley MicroLogix 1762-IQ8 Installation Instructions Manual
Allen-Bradley MicroLogix 1762-IQ8 Installation Instructions Manual

Allen-Bradley MicroLogix 1762-IQ8 Installation Instructions Manual

Dc input module
Installation Instructions
MicroLogix™ 1762-IQ8 DC Input Module
Inside
Description .......................................................3
Installation........................................................4
Mounting ..........................................................5
System Assembly .............................................7
Field Wiring Connections...................................7
I/O Memory Mapping ......................................10
Specifications .................................................11
Environnements dangereux.............................14
1762-IN004A-US-P
Table of Contents
loading

Summary of Contents for Allen-Bradley MicroLogix 1762-IQ8

  • Page 1: Table Of Contents

    Installation Instructions MicroLogix™ 1762-IQ8 DC Input Module Inside Description ............3 Installation............4 Mounting ............5 System Assembly ..........7 Field Wiring Connections........7 I/O Memory Mapping ........10 Specifications ..........11 Hazardous Location Considerations ....13 Environnements dangereux......14 1762-IN004A-US-P...
  • Page 2 MicroLogix™ 1762-IQ8 DC Input Module For More Information Refer to this Document Pub. No. Information on installing, wiring, and MicroLogix 1200 Programmable 1762-UM001A-US-P operating a MicroLogix 1200 Controllers User Manual Programmable Controller Installation guide for the MicroLogix MicroLogix 1200 Programmable 1762-IN006A-ML-P 1200 Programmable Controller.
  • Page 3: Description

    MicroLogix™ 1762-IQ8 DC Input Module Description Item Description upper panel mounting tab lower panel mounting tab I/O diagnostic LEDs module door with terminal identification label bus connector with male pins bus connector cover flat ribbon cable with bus connector (female pins) terminal block DIN rail latch pull loop...
  • Page 4: Installation

    MicroLogix™ 1762-IQ8 DC Input Module Installation 1762 I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2 ) and to circuits not exceeding Over Voltage Category II (IEC 60664-1).
  • Page 5: Mounting

    MicroLogix™ 1762-IQ8 DC Input Module Mounting ATTENTION: Do not remove protective debris strip until after the module and all other equipment near the module is mounted and wiring is complete. Once wiring is complete and the module is free of debris, carefully remove protective debris strip. Failure to remove strip before operating can cause overheating.
  • Page 6 Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN rail mounting area of the module against the DIN rail. The latch will momentarily open and lock into place. Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35) for vibration or shock environments. End Anchor...
  • Page 7: System Assembly

    Additional grounding connections from the module’s mounting tabs or DIN rail (if used) are not required unless the mounting surface cannot be grounded. Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information. 1762-IN004A-US-P...
  • Page 8 MicroLogix™ 1762-IQ8 DC Input Module Input Wiring Basic wiring of input devices to the 1762-IQ8 is shown below. +DC (sinking) -DC (sourcing) IN 0 IN 1 IN 2 IN 3 24V dc IN 4 IN 5 IN 6 IN 7 Commons are connected internally.
  • Page 9 MicroLogix™ 1762-IQ8 DC Input Module Note: Finger-safe cover not shown. Wiring the Finger-Safe Terminal Block When wiring the terminal block, keep the finger-safe cover in place. 1. Route the wire under the terminal pressure plate. You can use the stripped end of the wire or a spade lug.
  • Page 10: I/O Memory Mapping

    MicroLogix™ 1762-IQ8 DC Input Module I/O Memory Mapping Input Data File For each input module, the input data file contains the current state of the field input points. Bit positions 0 through 7 correspond to input terminals 0 through 7. Bit Position r = read only, 0 = always at a 0 or OFF state Addressing...
  • Page 11: Specifications

    MicroLogix™ 1762-IQ8 DC Input Module Specifications General Specifications Specification Value Dimensions 90 mm (height) x 87 mm (depth) x 40 mm (width) height including mounting tabs is 110 mm 3.543 in. (height) x 3.425 in. (depth) x 1.575 in. (width) height including mounting tabs is 4.33 in.
  • Page 12 MicroLogix™ 1762-IQ8 DC Input Module Input Specifications Specification 1762-IQ8 Voltage Category 24V dc (sink/source) Operating Voltage Range 10 to 30V dc at 30°C (86°F) 10 to 26.4V dc at 55°C (131°F) Number of Inputs Bus Current Draw (max.) 50 mA at 5V dc (0.25W) Heat Dissipation (max.) 3.7 Total Watts Signal Delay (max.)
  • Page 13: Hazardous Location Considerations

    MicroLogix™ 1762-IQ8 DC Input Module Hazardous Location Considerations This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following ATTENTION statement applies to use in hazardous locations. ATTENTION: EXPLOSION HAZARD •...
  • Page 14: Environnements Dangereux

    MicroLogix™ 1762-IQ8 DC Input Module Environnements dangereux Cet équipement est conçu pour être utilisé dans des environnements de Classe I, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux. ATTENTION: DANGER D’EXPLOSION •...
  • Page 15 MicroLogix™ 1762-IQ8 DC Input Module 1762-IN004A-US-P...
  • Page 16 MicroLogix is a trademark of Rockwell Automation. Publication 1762-IN004A-US-P September 1999 PN 40071-071-01(A) © (1999) Rockwell International Corporation. Printed in the U.S.A. ´H'*g!¶Ai¨...