Installation Instructions Compact 1769-OF8C Analog Output Module Inside Module Description ..................2 Module Installation...................3 System Assembly..................4 Mounting Expansion I/O ................5 Replacing a Single Module within a System ...........7 Module Spare/Replacement Parts ............8 Field Wiring Connections................8 I/O Memory Mapping ................12 Specifications ..................23 Hazardous Location Considerations ............26...
Compact 1769-OF8C Analog Output Module Module Description Analog Item Description DANGER Do Not Remove RTB Under Power Unless Area is Non-Hazardous bus lever ANLG I out 0 + ANLG (with locking function) I out 1 + ANLG I out 2 +...
Compact 1769-OF8C Analog Output Module Module Installation Compact I/O is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution degree 2 ) and to circuits not exceeding Over Voltage Category II (IEC 60664-1).
Compact 1769-OF8C Analog Output Module System Assembly The module can be attached to the controller or an adjacent I/O module before or after mounting. For mounting instructions, see “Panel Mounting” on page 6, or “DIN Rail Mounting” on page 7. To work with a system that is already mounted, see “Replacing a Single Module within a System”...
Compact 1769-OF8C Analog Output Module 6. To allow communication between the controller and module, move the bus lever fully to the left (4) until it clicks. Ensure it is locked firmly in place. When attaching I/O modules, it is very important that the bus...
Page 6
Compact 1769-OF8C Analog Output Module Panel Mounting Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module. Panel Mounting Using the Dimensional Template For more than 2 modules: (number of modules-1) X 35mm (1.38 in.) 28.5...
Compact 1769-OF8C Analog Output Module DIN Rail Mounting The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Locate the I/O system as close to your sensors or actuators as your application will permit. • Current outputs (Iout 0+ to Iout 7+) of the 1769-OF8C module source current that returns to ANLG COM. Load resistance for a current output channel must remain between 0 and 500 Ω.
Page 9
Compact 1769-OF8C Analog Output Module External Power Switch The 1769-OF8C has an external 24V dc power switch which gives you the option of using an external power supply. The switch is located in on the lower left portion of the module’s circuit board, as shown below. With this switch pressed on the top (default), 24V dc power is drawn from the 1769 system power supply via the 1769 I/O bus.
Page 10
Compact 1769-OF8C Analog Output Module Wiring Output Devices Basic wiring of output devices is shown below. • Miswiring of the module to an AC/DC source will damage the ATTENTION module. • Be careful when stripping wires. Wire fragments that fall into a module could cause damage at power up.
Page 11
Compact 1769-OF8C Analog Output Module Removing the Finger-Safe Terminal Block To remove the terminal block, loosen the upper and lower retaining screws. The terminal block will back away from the module as you remove the screws. When replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
Compact 1769-OF8C Analog Output Module Wire Size and Terminal Screw Torque Each terminal accepts up to two wires with the following restrictions: Wire Type Wire Size Terminal Screw Retaining Screw Torque Torque Solid Cu-90°C (194°F) #14 to #22 AWG 0.68 Nm (6 in-lbs) 0.46 Nm (4.1 in-lbs)
Page 13
Compact 1769-OF8C Analog Output Module Input Data File For each module, slot x, input data file words 3-10 contain the state of the module’s output data (output data echo) file words 0-7. During normal operation, these input words represent the analog values that the outputs are directed to by the control program.
Page 14
Compact 1769-OF8C Analog Output Module Configuration Data File The manipulation of the bits from this file is normally done with programming software (e.g. RSLogix 500, RSNetworx for DeviceNet, etc.) during initial configuration of the system. In that case, graphical screens are provided by the programmer to simplify configuration.
Page 15
Compact 1769-OF8C Analog Output Module Word Description Word Description Channel 2 High Clamp Channel 5 High Clamp Channel 2 Ramp Rate Channel 5 Ramp Rate Channel 2 Spare Channel 5 Spare Word Description Word Description Channel 6 Configuration Word 0...
Page 16
Compact 1769-OF8C Analog Output Module Channel Configuration Words The first two words of each eight word group in the configuration file allow you to change the parameters of each channel independently. For example, words 8 and 9 correspond to channel 1 while words 56 and 57 correspond to channel 7.
Page 17
Compact 1769-OF8C Analog Output Module RSLogix 5000, Version 15, Controller Tags Use the following controller tags with RSLogix 5000, version 15. Channel 0 and 1 Configuration Data Channel 0 and 1 configuration data is shown below. The same information applies to all channels.
Page 18
Compact 1769-OF8C Analog Output Module Local:1:C.Ch1En BOOL Decimal Local:1:C.Ch1Range SINT Decimal Local:1:C.Ch1DataFormat SINT Decimal Local:1:C.Ch1FaultValue Decimal Local:1:C.Ch1ProgValue Decimal Local:1:C.Ch1LClampValue Decimal Local:1:C.Ch1HClampValue Decimal Local:1:C.Ch1RampRate Decimal Tag Name To Select Make These Bit Settings 15-8 Ch#ProgToFaultEn Enable Disable Ch#HoldForInit Enable Disable Ch#ProgMode...
Page 21
Compact 1769-OF8C Analog Output Module Bit Indicates This Name Combined Status Status Status Status Status Status Status Status Status Module Power Status Fail Ch0_1 Status OpenWire InHold Under Over OpenWire InHold Under Over Range Range Range Range Ch2_3 Status OpenWire...
Compact 1769-OF8C Analog Output Module Specifications General Specifications Specification Value Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width) height including mounting tabs is 138 mm 4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in.
Page 24
Compact 1769-OF8C Analog Output Module Output Specifications Specification 1769-OF8C 0 to 20 mA, 4 to 20 mA Analog Normal Operating Ranges 0 to 21 mA, 3.2 to 21 mA Full Scale Analog Ranges Number of Outputs 8 single-ended Bus Current Draw (max.)
Page 25
Compact 1769-OF8C Analog Output Module Specification 1769-OF8C Accuracy Drift with Temperature ±0.0058% FS per °C ±0.05% Output Ripple range 0 to 50 kHz (referred to output range) Non-linearity (in percent full scale) ±0.05% ±0.05% Repeatability (in percent full scale) Output Error Over Full Temperature Current: ±0.55%...
Compact 1769-OF8C Analog Output Module Specification 1769-OF8C System Power Supply Distance The module may not be more than 8 modules away from the system power Rating supply. Optional 24V dc Class 2 Power 20.4 V to 26.4 V dc Supply Voltage Range Recommended Cable Belden™...
Compact 1769-OF8C Analog Output Module Environnements dangereux Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
Compact 1769-OF8C Analog Output Module For More Information Refer to this Document Pub. No. A more detailed description of how to install and MicroLogix 1500 Programmable 1764-UM001A-US-P use your Compact I/O with MicroLogix 1500 Controllers User Manual programmable controller. Detailed information on installing, programming,...
Compact 1769-OF8C Analog Output Module Notes: Publication 1769-IN065B-EN-P - September 2005...
Page 30
Compact 1769-OF8C Analog Output Module Notes: Publication 1769-IN065B-EN-P - September 2005...
Page 31
Compact 1769-OF8C Analog Output Module Notes: Publication 1769-IN065B-EN-P - September 2005...
Page 32
Rockwell Automation Support Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.