Honeywell 10260S series Replacement Instructions page 4

Auto-manual switch
Auto-Manual Switch Instruction, continued
Step
8
Connect switch wires:
If adding (not replacing) the switch, remove blue and orange wires from TB1-8 and TB1-9.
Connect blue wire to TB2-13 and orange wire to TB2-12.
If adding or replacing the switch, one at a time connect auto-manual switch wires as follows:
NOTE: Some terminal lugs have dual (piggyback) wires attached; make sure the wires are attached to
the correct terminals. Make sure piggyback wires on outermost terminals are facing the inner
terminals, not facing away from the terminals. For example, TB1-1 should have its piggyback terminal
positioned between TB1-1 and TB1-2.
9
Reinsert the terminal panel back into the actuator case being careful not to pinch any wires. Secure
terminal panel with two screws.
10
Install a new gasket and replace the terminal panel cover. Secure with four screws.
11
Reapply AC power to the actuator.
12
Verify actuator configuration and check AUTO-MANUAL switch for correct function.
13
Return actuator to service.
Page 4 of 5
AUTO-MANUAL
TO: Terminal Panel Lugs
Switch Wires
Black
TB1-1
White
TB1-8
Brown
TB1-9
Green
TB2-12
Violet
TB2-13
Orange
TB2-10
Red
TB2-11
TO: Main PWA Connector
Red (24 AWG)
P6-1
White (24 AWG)
P6-2
Action
62-86-33-26