Siemens Sivacon S8 Planning Information page 81

Hide thumbs Also See for Sivacon S8:
Table of Contents
Tab. 8/4:
Special service conditions for SIVACON S8 switchboards
Environmental
Class
conditions
Chemically
active
3C2
substances
3Z1
3Z7
Additional
climatic
3Z9
environmental
conditions
3B2
3S1
Mechanically
active
substances
3S2
Conditions for transport, storage and installation
If the ambient conditions for transport, storage or switch-
board installation deviate from the normal service condi-
tions listed in Tab. 8/4 (for example an excessively low or
high value for temperature or air humidity), the measures
78
SIVACON S8 Planning Principles – Further planning notes
Environmental parameters including their limit values
(Definition acc. to IEC 60721-3-3)
Sea salt
Sulphur dioxide SO
2
Hydrogen sulphide H
S
2
Chlorine Cl
2
Hydrogen chloride HCl
Hydrogen fluoride
Ammonia NH
3
Ozone O
3
Nitrogen oxides NO
x
Heat radiation is negligible
Dripping water in accordance with IEC 60068-2-18
Splashing water in accordance with IEC 60068-2-18
Flora
Fauna
Sand in air
Dust (suspension)
Dust (sedimentation)
Sand in air
Dust (suspension)
Dust (sedimentation)
Presence of salt mist
Mean value
Limiting value
3
0.3 mg/m
1.0 mg/m
3
0.1 mg/m
0.5 mg/m
3
0.1 mg/m
0.3 mg/m
3
0.1 mg/m
0.5 mg/m
3
0.01 mg/m
0.03 mg/m
3
1.0 mg/m
3.0 mg/m
3
0.05 mg/m
0.1 mg/m
3
0.5 mg/m
1.0 mg/m
Presence of mould, fungus, etc.
Presence of rodents and other animals
harmful to products, excluding termites
-
3
0.01 mg/m
3
0.4 mg/(m
∙h)
3
300 mg/m
3
0.4 mg/m
3
15 mg/(m
∙h)
required for proper treatment of the switchboard must be
agreed upon between manufacturer and client.
Measures
3
3
3
on request
3
3
3
3
3
IPX1
IPX4
≥ IP4X including
protection of the
cable basement
< IP5X
≥ IP5X