Configuration with TIA Portal

TIA Portal - Hardware configuration - PG/OP via PROFINET

10.5
TIA Portal - Hardware configuration - PG/OP via PROFINET
Overview
Assembly and commis-
sioning
"Initialization" via Online
functions
156
Device overview:
Module
PLC...
...
DI...
DO...
DIO...
AI...
AO...
CP 343-1
The CPU has an Ethernet interface X8 integrated for PROFINET. Besides the connection
to PROFINET this interface allows you to program and remote control your CPU.
n
At the first commissioning respectively after a factory reset the PROFINET interface
has no IP address.
For online access to the CPU via the PROFINET interface, valid IP address parame-
n
ters have to be assigned to this. This is called "initialization".
n
This can be done with the Siemens TIA Portal.
1.
Install your System 300S with your CPU.
2.
Wire the system by connecting cables for voltage supply and signals.
3.
Connect the Ethernet jack (X8) PROFINET to Ethernet.
4.
Switch on the power supply.
ð After a short boot time the CP is ready for communication. He possibly has no
IP address data and requires an initialization.
The initialization via the Online functions takes place with the following proceeding:
Determine the current Ethernet (MAC) address of your PROFINET interface. This
always can be found as 2. address under the front flap of the CPU on a sticker on
the left side.
...
Slot
2
...
3
4
5
6
7
8
9
HB140 | CPU | 317-4PN23 | en | 18-01
VIPA System 300S
...
Type
CPU ...
...
DI...
DO...
DIO...
AI...
AO...
CP 343-1
+
...