GE B30 Communications Manual page 377

Universal relay family
Hide thumbs Also See for B30:
Table of Contents
CHAPTER 3: IEC 61850 COMMUNICATION
3.5.3.22 Single pole autoreclose (Rec13p)
This element is instantiated in the following products: C60, D60, L60, L90.
Table 3-159: Single pole autoreclose data objects
LNName: Rec13pRREC1
data obj. data attribute
Type
TrBeh
ENS
stVal
ENUMERATED
RecCyc
INS
stVal
INT32
AutoRecSt
ENS
stVal
ENUMERATED
Ena1
SPS
stVal
BOOLEAN
Disabled
SPS
stVal
BOOLEAN
ArRip
SPS
stVal
BOOLEAN
P1Rip
SPS
stVal
BOOLEAN
P3Rip1
SPS
stVal
BOOLEAN
P3Rip2
SPS
stVal
BOOLEAN
P3Rip3
SPS
stVal
BOOLEAN
P3Rip4
SPS
stVal
BOOLEAN
ArLO
SPS
stVal
BOOLEAN
ArBlk1
SPS
stVal
BOOLEAN
ArBlk1
SPS
stVal
BOOLEAN
OpCls
ACT
general
BOOLEAN
Cls2ndBkr
SPS
stVal
BOOLEAN
P3Tr
SPS
stVal
BOOLEAN
AnyShotCn
SPS
t
stVal
BOOLEAN
ShotCnt1
SPS
stVal
BOOLEAN
ShotCnt2
SPS
stVal
BOOLEAN
ShotCnt3
SPS
stVal
BOOLEAN
UR FAMILY – COMMUNICATIONS GUIDE
LDevice inst: Ctrl
UR element: Autoreclose element
FC UR Name
ST
ST
AUTORECLOSE SHOT COUNT
ST
ST
AR ENABLED
ST
AR DISABLED
ST
AR RIP
ST
AR 1-P RIP
ST
AR 3-P/1 RIP
ST
AR 3-P/2 RIP
ST
AR 3-P/3 RIP
ST
AR 3-P/4 RIP
ST
AR LO
ST
AR BKR1 BLK
ST
AR BKR2 BLK
ST
AR CLOSE BKR1
ST
AR CLOSE BKR2
ST
AR FORCE 3-P TRIP
ST
AR SHOT CNT>0
ST
AR SHOT CNT=1
ST
AR SHOT CNT=2
ST
AR SHOT CNT=3
MODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS)
Description
AR FORCE 3-P TRIP operand
3 if operand AR FORCE 3-P TRIP is On, 2
otherwise.
AUTORECLOSE SHOT COUNT actual value R
Autoreclosing status
AR ENABLED operand
AR DISABLED operand
AR RIP operand
AR 1-P RIP operand
AR 3-P/1 RIP operand
AR 3-P/2 RIP operand
AR 3-P/3 RIP operand
AR 3-P/4 RIP operand
AR LO operand
AR BKR1 BLK operand
AR BKR2 BLK operand
AR CLOSE BKR1 operand
AR CLOSE BKR2 operand
AR FORCE 3-P TRIP operand
AR SHOT CNT>0 operand
AR SHOT CNT=1 operand
AR SHOT CNT=2 operand
AR SHOT CNT=3 operand
R/W/C
R
R
R
R
3
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
3-139

Hide quick links:

Table of Contents
loading

Table of Contents