ABB REC670 Product Manual

ABB REC670 Product Manual

Bay control version 2.2
Hide thumbs Also See for REC670:
Table of Contents
R E L I O N ® 670 SERIES
Bay control REC670
Version 2.2
Product guide
Table of Contents
loading

Summary of Contents for ABB REC670

  • Page 1 — R E L I O N ® 670 SERIES Bay control REC670 Version 2.2 Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Application

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Issued: October 2017 Revision: A 1. Application Duplex communication channels for transfer of up to 192 M13637-3 v13 The Intelligent Electronic Device (IED) is used for the control, intertrip and binary signals are available on each remote-end protection and monitoring of different types of bays in power data communication card (LDCM).
  • Page 4 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Description of configuration A30 M15200-3 v7 REC670 A30 – Double busbar in single breaker arrangement 12AI (6I + 6U) Control Control Control S CILO S CSWI S XSWI Control...
  • Page 5 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Description of configuration B30 M15200-12 v5 REC670 B30 - Double breaker arrangement 12AI (6I + 6U) Control Control Control S CILO S CSWI S XSWI WA2_VT Control Control Control...
  • Page 6 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Description of configuration C30 M15200-24 v5 REC670C30 – Complete one-and a half breaker diameter arrangement 24AI (6I + 6U, 6I+6U) Control Control Control S CILO S CSWI S XSWI...
  • Page 7 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Description of configuration D30 GUID-15D86A4C-4D37-432E-8DC2-518814830097 v1 REC670 D30 – Double busbar in single breaker arrangement with PMU functionality 12AI (6I + 6U) Control Control Control S CILO S CSWI...
  • Page 8 The basic IED configuration is provided with the signal matrix, been connected in the special way. On request, ABB is single line diagram and the application configuration prepared available to support the re-configuration work, either directly for the functions included in the product by default.
  • Page 9: Available Functions

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 are not exposed to the user or do not need 2. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 to be configured are not described in this manual. The following tables list all the functions available in the IED.
  • Page 10 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v13 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) Current protection PHPIOC Instantaneous phase overcurrent 1-C51 2-C52 2-C53 1-C51 protection OC4PTOC...
  • Page 11 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) SAPTUF Underfrequency protection 6-E01 6-E01 6-E01 6-E01 SAPTOF Overfrequency protection 6-E01 6-E01 6-E01 6-E01 SAPFRC Rate-of-change of frequency protection...
  • Page 12 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v15 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser 1-H04 2-H05...
  • Page 13 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) CCSSPVC Current circuit supervision FUFSPVC Fuse failure supervision VDSPVC Fuse failure supervision based on voltage difference 1-G03...
  • Page 14 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) TEIGAPC Elapsed time integrator with limit transgression and overflow supervision INTCOMP Comparator for integer inputs REALCOMP Comparator for real inputs Table 2.
  • Page 15 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 3. Number of function instances in APC10 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE...
  • Page 16 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 4. Number of function instances in APC15 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE...
  • Page 17 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 5. Number of function instances in APC30 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE...
  • Page 18 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 7. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC...
  • Page 19 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI...
  • Page 20 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) Metering PCFCNT Pulse-counter logic ETPMMTR Function for energy calculation and demand handling...
  • Page 21 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v15 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON...
  • Page 22 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) OPTICAL103 IEC 60870-5-103 Optical serial communication RS485103 IEC 60870-5-103 serial communication for RS485 AGSAL Generic security application component...
  • Page 23 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 IEC 61850 or ANSI Function description Bay control function name REC670 (Customized) BinSignTrans1_1 Binary signal transfer transmit 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6 BinSignTrans1_2 BinSignTransm2 BinSigRec1_12M Binary signal transfer, 2Mbit receive/...
  • Page 24 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v12 Table 9. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN,...
  • Page 25: Control

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 10. Local HMI functions IEC 61850 or function ANSI Description name LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5...
  • Page 26 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 • Substitution of position and quality indications Each apparatus control function has interlocking modules • Overriding of interlocking functions included for different switchyard arrangements, where each • Overriding of synchrocheck function handles interlocking of one bay.
  • Page 27 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Voltage control includes many extra features such as the Reservation input RESIN possibility to avoid simultaneous tapping of parallel M16501-3 v5 The Reservation input (RESIN) function receives the transformers, hot stand by regulation of a transformer in a reservation information from other bays.
  • Page 28: Differential Protection

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 plays the same role as functions GOOSEBINRCV (for IEC GUID-8DF29209-252A-4E51-9F4A-B14B669E71AB v4 The phasor measurement reporting block moves the phasor 61850) and MULTICMDRCV (for LON). calculations into an IEEE C37.118 and/or IEEE 1344 synchrophasor frame format.
  • Page 29 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 NS4PTOC can also be used to provide a system backup for Instantaneous residual overcurrent protection EFPIOC example, in the case of the primary protection being out of M12701-3 v16...
  • Page 30: Voltage Protection

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 The thermal overload protection estimates the internal heat Normally the own breaker is tripped to correct such a content of the transformer (temperature) continuously. This situation. If the situation persists the surrounding breakers estimation is made by using a thermal model of the should be tripped to clear the unsymmetrical load situation.
  • Page 31: Frequency Protection

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 prepare for system restoration at power outages or as a long- 8. Frequency protection time delayed back-up to the primary protection. Underfrequency protection SAPTUF M13349-3 v13 Underfrequency occurs as a result of a lack of generation in UV2PTUV has two voltage steps, each with inverse or definite the network.
  • Page 32: Multipurpose Protection

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 START signal triggers the individual event timer, which is the with the neutral point current on a separate input taken from continuous time spent within the given frequency band, and another set of cores on the current transformer.
  • Page 33: Scheme Communication

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 12. Scheme communication including a channel transmission time, can be achieved. This short operate time enables rapid autoreclosing function after Scheme communication logic with delta based blocking the fault clearance.
  • Page 34 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 The trip function can collect start and directional signals from • INVERTER function block that inverts the input signal to the different application functions. The aggregated start and output.
  • Page 35 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 • INDEXTSPQT extracts individual signals from a group M15322-3 v12 The Fixed signals function (FXDSIGN) has nine pre-set (fixed) signal input. The value part of single position input is signals that can be used in the configuration of an IED, either copied to SI_OUT output.
  • Page 36: Monitoring

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 value. It is a basic arithmetic function that can be used for The Disturbance report function is characterized by great monitoring, supervision, interlocking and other logics. flexibility regarding configuration, starting conditions, recording times, and large storage capacity.
  • Page 37 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 The event recording information is an integrated part of the SEMOD55713-5 v8 Generic communication function for Single Point indication disturbance record (Comtrade file). (SPGAPC) is used to send one single logical signal to other systems or equipment in the substation.
  • Page 38: Metering

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 The fault locator is an impedance measuring function giving taken through sensors or the one calculated by the function. the distance to the fault in km, miles or % of line length. The...
  • Page 39: Human Machine Interface

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 The values of active and reactive energies are calculated from • Graphical display capable of showing a user defined single the input power values by integrating them over a selected...
  • Page 40: Station Communication

    Route from source to destination through gateway SPA communication protocol SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation automation systems but the main use is for Substation 19.
  • Page 41 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 FunctionType parameter for each block in the include the IEC 60870-5-103 communication protocol private range, and the information number parameter for each SEMOD120137-5 v4 A single glass or plastic port is provided for the IEC input signal.
  • Page 42: Remote Communication

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 21. Hardware description Multiple command and transmit M14791-3 v3 When IEDs are used in Substation Automation systems with Hardware modules IP14529-1 v1 LON, SPA or IEC 60870-5-103 communication protocols, the...
  • Page 43 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Serial and LON communication module (SLM) for SPA/IEC Layout and dimensions 60870-5-103, LON and DNP 3.0 IP14539-1 v1 Dimensions M14933-3 v5 The Serial and LON communication module (SLM) is used for...
  • Page 44 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M15243-12 v9 IEC06000182-2-en.vsd IEC06000182 V2 EN-US Figure 10. A 1/2 x 19” size IED side-by-side with RHGS6. Case size (mm)/(inches) 6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/...
  • Page 45: Connection Diagrams

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 22. Connection diagrams Connection diagram, REC670 2.2, A30X00 1MRK002807-CA GUID-CF4EFFA5-3081-4FC7-9A14-ED127C3C0FDE v6 The connection diagrams are delivered in the IED Connectivity Connection diagram, REC670 2.2, B30X00 1MRK002807-CB package as part of the product delivery.
  • Page 46: Technical Data

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 23. Technical data General M10993-1 v3 IP11376-1 v2 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range...
  • Page 47 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 11. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f...
  • Page 48 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 12. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
  • Page 49 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 15. SFP - Galvanic RJ45 Table 15. SFP - Galvanic RJ45, continued Quantity Rated value Quantity Rated value Connector Type RJ45 Number of Up to 6 single or 3 redundant or a combination of single...
  • Page 50 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M50609-2 v7 Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. Table 18. BIM - Binary input module with enhanced pulse counting capabilities...
  • Page 51 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12318-1 v8 Maximum 176 binary input channels may be activated simultaneously with influencing factors within nominal range. Table 20. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
  • Page 52 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12584-1 v7 BOM/IOM/SOM should be activated continuously due to power dissipation. Table 21. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity...
  • Page 53 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 SEMOD175395-2 v7 BOM/IOM/SOM should be activated continuously due to power dissipation. Table 22. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip...
  • Page 54 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 23. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Number of outputs...
  • Page 55 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 26. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/%...
  • Page 56 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 28. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III...
  • Page 57 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 30. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
  • Page 58 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Differential protection M13081-1 v12 Table 33. High impedance differential protection, single phase HZPDIF Function Range or value Accuracy Operate voltage (10-900) V ±1.0% of I at I ≤ I I=U/R ±1.0% of I at I >...
  • Page 59 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Wide area measurement system GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v4 Table 34. Protocol reporting via IEEE 1344 and C37.118 PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤ 1.0% TVE...
  • Page 60 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Current protection M12336-1 v13 Table 35. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 61 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12342-1 v20 Table 36. Directional phase overcurrent protection, four steps OC4PTOC Function Setting range Accuracy Operate current, step 1-4 (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 62 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M15223-1 v17 Table 38. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 63 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 39. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I £...
  • Page 64 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 SEMOD173350-2 v16 Table 40. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional residual ±1.0% of I at I £...
  • Page 65 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12352-1 v14 Table 41. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F...
  • Page 66 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12353-1 v14 Table 43. Breaker failure protection CCRBRF Function Range or value Accuracy Operate phase current (5-200)% of lBase ±1.0% of I at I £ I ±1.0% of I at I > I Reset ratio, phase current >...
  • Page 67 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 SEMOD175152-2 v11 Table 46. Directional underpower protection GUPPDUP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
  • Page 68 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-6A7DA510-E145-4C5B-A7DC-97BC4258E621 v9 Table 49. Capacitor bank protection CBPGAPC Function Range or value Accuracy Operate value, overcurrent (10-900)% of lBase ±2.0% of I at I ≤ I ±2.0% of I at I > I Reset ratio, overcurrent >95% at (100-900)% of IBase...
  • Page 69 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8 Table 50. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 70 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Voltage protection M13290-1 v15 Table 51. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of...
  • Page 71 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M13304-1 v14 Table 52. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 72 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M13317-2 v14 Table 53. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 - step 2 (1.0-200.0)% of UBase ± 0.5% of U at U ≤...
  • Page 73 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 SEMOD175210-2 v6 Table 55. Loss of voltage check LOVPTUV Function Range or value Accuracy Operate voltage (1–100)% of UBase ±0.5% of U Pulse timer when disconnecting (0.050–60.000) s ±0.2% or ±15 ms whichever is greater...
  • Page 74 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Frequency protection M13360-1 v15 Table 56. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f...
  • Page 75 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M14976-1 v9 Table 58. Rate-of-change of frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz...
  • Page 76 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Multipurpose protection M13095-2 v8...
  • Page 77 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 60. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-phase3, phase3-phase1,...
  • Page 78 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 60. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, overvoltage at (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is greater 0.8 x U...
  • Page 79 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 60. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x...
  • Page 80 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Secondary system supervision M12358-1 v10 Table 61. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90%...
  • Page 81 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5 Table 63. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur Reset ratio <110%...
  • Page 82 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Control M12359-1 v15 Table 64. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase...
  • Page 83 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12379-1 v13 Table 65. Autorecloser SMBRREC Function Range or value Accuracy Dead time: shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms shot 1 “t1 2Ph” whichever is greater shot 1 “t1 3Ph “...
  • Page 84 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 SEMOD175215-2 v14 Table 66. Voltage control TR1ATCC/TR8ATCC , TCMYLTC/TCLYLTC Function Range or value Accuracy Transformer reactance (0.1–200.0) Ω, primary Time delay for lower command when fast step down mode is activated (1.0–100.0) s...
  • Page 85 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 66. Voltage control TR1ATCC/TR8ATCC , TCMYLTC/TCLYLTC , continued Function Range or value Accuracy Time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms...
  • Page 86 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Scheme communication M16038-1 v14 Table 67. Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR...
  • Page 87 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-CC9A02C2-AAE8-4B8C-A091-D4ED584A2EA7 v1 Table 70. Local acceleration logic ZCLCPSCH Function Range or value Accuracy Operate current, LoadCurr (1–100)% of IBase ±1.0% of I Operate current, MinCurr (1–100)% of IBase ±1.0% of I Delay time on pick-up for current release (0.000–60.000) s...
  • Page 88 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Logic M12380-1 v12 Table 72. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
  • Page 89 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v2 Table 79. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v2 Table 80. Number of GATE instances Logic block...
  • Page 90 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-C6C98FE0-F559-45EE-B853-464516775417 v2 Table 87. Number of TIMERSET instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms TIMERSET (0.000–90000.000) s ±0.5% ±10 ms GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1 Table 88.
  • Page 91 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1 Table 95. Number of PULSETIMERQT instances Logic block Quantity with cycle time Range or Value Accuracy 3 ms 8 ms 100 ms (0.000–90000.000) s ±0.5% ±10 ms...
  • Page 92 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v7 Table 100. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms 8 ms 100 ms SLGAPC VSGAPC PULSETIMER GATE —...
  • Page 93 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3 Table 105. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC Function Cycle time (ms) Range or value Accuracy Elapsed time integration 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is...
  • Page 94 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Monitoring M12386-1 v15 Table 109. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U>...
  • Page 95 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 112. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V...
  • Page 96 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12760-1 v10 Table 116. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
  • Page 97 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v7 Table 118. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value Temperature alarm level -40.00-200.00...
  • Page 98 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-F6B6ED6B-2488-483C-B068-3F4631F34DC8 v1 Table 121. Transformer loss of life LOLSPTR Function Range or value Accuracy Service value, hot spot – ±2.0% of expected value temperature Service value, top oil –...
  • Page 99 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12384-1 v7 Table 126. Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Maximum number of disturbance reports Maximum total recording time (3.4 s recording time and maximum number...
  • Page 100 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Metering M13404-2 v5 Table 129. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value SEMOD153707-2 v5 Table 130.
  • Page 101 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Station communication M15031-1 v8 Table 131. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
  • Page 102 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12589-1 v4 Table 136. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *)
  • Page 103 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 M12756-1 v10 Remote communication Table 140. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber...
  • Page 104 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Hardware M11778-1 v6 SEMOD53385-1 v1 Table 141. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v4 Table 142.
  • Page 105 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2 connections, one blank slot is necessary between two adjacent IO modules. Please refer to the ordering particulars for details. Table 147. NUM: Communication ports 4 Ethernet ports...
  • Page 106 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Basic IED functions M11963-1 v5 Table 149. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v8 Table 150.
  • Page 107 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 SEMOD141136-2 v8 Table 154. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 108 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Inverse characteristic M12388-1 v21 Table 155. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms...
  • Page 109 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 156. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is...
  • Page 110 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v3 Table 158. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 2.00 ANSI/IEEE C37.112 , 1.5 x I...
  • Page 111 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 159. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I...
  • Page 112 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v1 Table 161. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , ±...
  • Page 113 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 SEMOD116978-2 v10 Table 163. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 114 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 164. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 115 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 165. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01...
  • Page 116: Ordering For Customized Ied

    The selected qty of each table must be filled in, if no selection is possible the code is 0. Example of a complete code: REC670*2.2-F00X00 - A000006000000000 - B00000000000000000000000000 - C6600666666660036221300300 - D22206020 - E6662 - F9 - S6 - G642 - H26461114444 - K10101110 - L1100 - M614 - P11100000000000100 - B1X0 - AC - CA - B - A3X0 - CD1D1ARGN1N1XXXXXXX -...
  • Page 117 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 171. Differential functions Function Function Ordering no Position Available Selected Notes and rules identification High impedance differential protection, single phase HZPDIF 1MRK005904-HB Table 172. Impedance protection Position Table 173. Current protection Position Table 174.
  • Page 118 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 178. Frequency functions Function Function Ordering no Position Available Selected Notes and rules identification Underfrequency protection SAPTUF 1MRK005914-AC Overfrequency protection SAPTOF 1MRK005914-BB Rate-of-change of frequency protection SAPFRC 1MRK005914-CB...
  • Page 119 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 186. Control functions Function Function Ordering no Position Available Selected Notes and rules identification Synchrocheck, energizing check and synchronizing SESRSYN 1MRK005917-AC Can only be ordered with Apparatus control APC10/...
  • Page 120 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 192. Monitoring functions Function Function Ordering no Position Available Selected Notes and rules identification Circuit breaker condition monitoring SSCBR 1MRK005924-HA 00-18 Fault locator LMBRFLO 1MRK005925-XB Transformer insulation loss of life monitoring...
  • Page 121 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 198. Power supply module selection Power supply module Ordering no Selection Notes and rules Compression terminals 1MRK002960-GA Ringlug terminals 1MRK002960-HA Power supply module 24-60 VDC 1MRK002239-AB Power supply module 90-250 VDC...
  • Page 122 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 200. Analog system selection Analog system Ordering no Selection Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug).
  • Page 123 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 201. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
  • Page 124 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 203. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █ █ █ These black marks...
  • Page 125 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 203. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, 1MRK000173-BE 10+2 outputs, RL110, 110-125VDC, 50mA IOM 8 inputs,...
  • Page 126 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Table 204. Station communication, remote end serial communication and time synchronization selection Station communication, remote end Ordering no Selection Notes and rules serial communication and time synchronization Slot position (front view/rear view)
  • Page 127: Ordering For Pre-Configured Ied

    Example code: REC670 *2.2-A30X00- A02H02-B1A3-AC-CA-B-A3X0-CDAB1RGN1N1XXXXXXX-KKKXXHKKLAGXSY. Using the code of each position #1-11 specified as REC670*1-2 2-3 3-4 4-5 6-7 7-8-9 9 9-10 10 10 10 10 10 10 10-11 11 11 11 11 11 11 11 11 11 11 REC670*...
  • Page 128 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Software options Ordering no Notes and rules No option All fields in the ordering form do not need to be filled in. High impedance differential protection - 3 blocks...
  • Page 129 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Mounting details with IP40 of protection from the front Ordering no Notes and rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case or 2xRHGS6 or RHGS12...
  • Page 130 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Binary input/output Ordering no Notes and rules module and mA input module For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
  • Page 131 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Binary input/output Ordering no Notes and rules module and mA input module For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
  • Page 132 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 Station communication, remote end Ordering no Notes and rules serial communication and time synchronization Slot position (front view/rear view) The maximum number and type of LDCM modules supported depend on the total...
  • Page 133: Ordering For Accessories

    1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 26. Ordering for Accessories Accessories IP15151-1 v1 GPS antenna and mounting details M12374-3 v5 GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA Cable for antenna, 20 m (Appx. 65 ft)
  • Page 134 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 External resistor unit SEMOD120228-4 v8 High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 1ph Quantity: RK 795 101-MA High impedance resistor unit with resistor and voltage dependent resistor 20-100V, 3ph...
  • Page 135 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 511 401-UEN ANSI Quantity: 1MRK 511 401-UUS Technical manual Quantity: 1MRK 511 402-UEN ANSI Quantity:...
  • Page 136 1MRK 511 404-BEN A Bay control REC670 2.2 Product version: 2.2.1 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data:...
  • Page 138 — ABB AB Grid Automation Products 721 59 Västerås, Sweden Phone: +46 (0) 21 32 50 00 abb.com/protection-control © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.

Table of Contents