Installing Multiple Liebert IntelliSlot Unity Cards in a System

More than one Liebert IntelliSlot card may be installed in a system, but circular routes and duplicate
node ID's must be avoided during installation. The instructions below apply if the second card to be
installed is a Liebert IntelliSlot Unity card. If the second card is not a Liebert IntelliSlot Unity card,
follow instructions in the user manual for that card.
Before beginning installation of a second Liebert IntelliSlot card, verify that the first card functions
properly.
If the first card is a Liebert IntelliSlot card, but not a Liebert IntelliSlot Unity card, and if both cards
connect to the same Ethernet network, then you should disable the router function on the first card.
This will avoid circular routes. Follow instructions in the user manual for the first card.
If the first and second cards are both Liebert IntelliSlot Unity cards, steps must be taken to avoid
duplicate Emerson Protocol MSTP node ID's. By default, the two cards would use the same node ID,
and one or both cards would report a duplicate node error and fail to communicate with the system.
The default node ID for a Liebert IntelliSlot Unity card is 0, so the second card should use 1 or 2
preferably, or 127 if necessary. Contact your system administrator about the proper node ID for the
second card, then perform the steps below.
1. Open a Web browser and navigate to the second Liebert IntelliSlot Unity card.
2. Click on Unity Tab > Configuration > Emerson Protocol > MSTP.
3. Click on Edit and enter a password and username, if required.
4. Enter the new node ID.
5. Click Save to confirm the changes or click Cancel to discard them.
6. Restart the card as follows.
a. Select the Unity Tab > Support.
b. Click on Enable.
c.
Click on Restart.