Routine Zero
Run the conveyor empty for several minutes to warm up the belt and insure that it is
empty. Test weights are not used during a zero calibration.
From the
run mode
Note:
E3 is an indication that the mechanical system is errant. The use of P377,
initial zero
, should be used judiciously and only after a thorough mechanical
investigation has been exercised.
The cause of the increased deviation must be found and rectified. A zero recalibration as
previously described can then be retried.
If the operator deems this deviation to be acceptable, set P377 to 1 to invoke an initial
zero calibration. Further deviation limits are now based on this new initial zero.
Page 32
1
1
1
1
1
Milltronics BW100 - INSTRUCTION MANUAL
initiate zero calibration
current zero count = ####
2
zero calculation,
load value displayed
2
zero deviation calculated
2
2
return to run mode
2
accept deviation
new zero count = ####
7ML19985DJ01