Detector 4000
Table of Contents
18
en | Programming
Temperature
rate-of-rise [K
min
10
20
30
2014.11 | 1.1 | F.01U.283.550
Response time for detectors in the
sensitivity class A1R
]
-1
Lower limiting
value [min/sec]
1 min
30 s
20 s
Upper limiting
value [min/sec]
4 min 20 s
2 min 20 s
1 min 40 s
Operation Guide
AVENAR detector 4000
Response time for detectors in the
sensitivity classes A2R/BR
Lower limiting
Upper limiting
value [min/sec]
value [min/sec]
2 min
5 min 30 s
1 min
3 min 13 s
40 s
2 min 25 s