Bosch AVENAR 4000 FAP-425-O User Manual

Bosch AVENAR 4000 FAP-425-O User Manual

Hide thumbs Also See for AVENAR 4000 FAP-425-O:
AVENAR detector 4000
FAP‑425‑O|FAP‑425‑O‑R|FAP‑425‑OT|FAP‑425‑OT‑R|FAP‑425‑DO‑R|
FAP‑425‑DOT‑R|FAP‑425‑DOTC‑R|FAH‑425‑T‑R
en
User manual
Table of Contents
loading

Summary of Contents for Bosch AVENAR 4000 FAP-425-O

  • Page 1 AVENAR detector 4000 FAP‑425‑O|FAP‑425‑O‑R|FAP‑425‑OT|FAP‑425‑OT‑R|FAP‑425‑DO‑R| FAP‑425‑DOT‑R|FAP‑425‑DOTC‑R|FAH‑425‑T‑R User manual...
  • Page 3: Table Of Contents

    Test Instructions for LSN improved version Fire Detectors 7.2.1 Test Instructions for All Fire Detectors With Optical Sensor 7.2.2 Test Instructions for FAP‑425‑DOTC‑R / FAP‑425‑DOT‑R / FAP‑425‑OT‑R / FAP‑425‑OT Diagnostic data Warranty Repair Disposal Technical Data Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 4: Product Description

    FAP-425-DOTC-R Combined dual-optical, thermal and Multi-sensor chemical smoke detector, automatic and manual address setting FAH-425-T-R Thermal detector, automatic and manual Single sensor address setting 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 5: System Overview

    Depending on the specified detector class, the thermal sensor triggers the alarm status when the maximum temperature of 54 °C or 69 °C is exceeded (thermal maximum), or if the temperature rises by a defined amount within a specified time (thermal differential). Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 6: Chemical Sensor (Gas Sensor)

    Individual detector identification on the fire panel in the event of an alarm. Alarm indication on the detector with a flashing red LED. – Programmable, i.e. can be adjusted to the area of operation. 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 7: Accessories

    Compliant with EN 54, EN 50131 and VdS guidelines. For DO detectors, note: Notice! The device cannot be used with the FPA-5000 type A panel controller. Accessories FLM-420-EOL4W-S The FLM-420-EOL4W-S is a 4 wire EOL module. Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 8 TP8 400 Support Plate The TP8 400 Support Plate is intended for an installation height up to 8 m and is designed for labels up to a size of approx. 97 x 44 mm. 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 9: Detector Base Sounders

    2.5.1 Detector Base Sounders Detector base sounders are used if acoustic alarm signaling is required directly at the fire source. Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 10: Remote Indicators

    For applications where the automatic detector is not visible, or mounted in false ceilings/floors. FAA‑420‑RI‑DIN For applications where the automatic detector is not visible, or mounted in false ceilings/floors. This version complies with DIN 14623. 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 11: Planning

    FAP-425-O FAH-425-T-R FAP-425-DO-R FAP-425-DOT-R FAP-425-DOTC-R Notice! Planning should take the anticipated total current and line resistance into account to ensure each detector has an operating voltage of at least 15 V DC. Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 12: Programming

    Low (BR) Medium High diff EDP room O, T High (A2R) High High diff Production location O, T Low (BR) Low* Medium diff Garage O, T High (A2R) Low* diff 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 13: Fap-425-Dot-R / Fap-425-Ot-R / Fap-425-Ot

    Office (after hours) O, T High (A2R) High diff Office (smoker)/waiting room/ O, T High (A2R) diff restaurant/meeting room Office (day mode) O, T Low (BR) Medium diff = default setting Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 14: Fap-425-Do-R / Fap-425-O-R / Fap-425-O

    "Medium". For a list of possible installation locations and corresponding sensitivity settings, see the below table. Installation locations Selectable sensitivity Theater/concert hall Medium Warehouse with vehicle traffic Office (smoker)/waiting room/restaurant/meeting room Conference hall/waiting room/fairground Office (after hours) High School/kindergarten Medium 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 15: Fah-425-T-R

    Lower limiting Upper limiting value [min/sec] value [min/sec] value [min/sec] value [min/sec] 1 min 4 min 20 s 2 min 5 min 30 s 30 s 2 min 20 s 1 min 3 min 13 s 20 s 1 min 40 s 40 s 2 min 25 s Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 16: Connection

    The MS 400 is the standard detector base. It has seven screw terminals. MS 400 B MS 400 standard detector base with Bosch-branding. FAA-420-SEAL For using the FAP/FAH detectors in damp environments you can supplement the MS 400, MS 400 B and FAA-MSR 420 detector bases with the FAA-420-SEAL damp room seal.
  • Page 17: Installing The Base

    Cables can be fed in and out on the same side. On the FAA-420-SEAL and MSC 420, punch out the integrated seal with a sharp tool. Do not cut with a knife. Ø 120 Ø 100 Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 18: Connection

    3m. No limitation when using shielded cables. 5.3.2 Connecting the FAA‑MSR 420 Maximum contact load (resistive load) of the change-over contact relay: – 62.5 VA: 0.5 A at 125 V AC – 30 W: 1 A at 30 V DC 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 19: Installation Of The Detector Module

    (X) out of the base and pushing it into the corresponding guide, as shown in , page 19 . Figure 5.1: Activation of the removal protection mechanism Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 20: Detector Removal

    Move the rotary switches to the required position using a slotted-head screwdriver. Automatic address allocation If addresses are automatically allocated by a fire panel with LSN improved version technology, all detectors must have the address "0 0 0" (delivery status). 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 21: Installing Remote Indicators

    Ensure, that the maximum current feed of 30 mA is not exceeded b) Use point‑type automatic Bosch detectors, which have an internal resistor that limits the current consumption. Before assembly remove the cap from the base plate Unlock the snap‑fit hook by pressing on it with a flat object and lift the cap carefully...
  • Page 22 Secure the cable with a zip tie on the base plate. Technical specifications FAA‑420‑RI‑ROW FAA‑420‑RI‑DIN Operating Voltage depends on current feed – Operating mode 1: depends on current feed – Operating mode 2: 8,5 to 33 V DC 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 23 The remote indicator shows steady red light. The remote indicator shows steady red light. The remote indicator shows flashing red light. Operate in mode 1 and 3 only, when connected to LSN detectors. Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 24 Place the cap on the base plate in such a way that the two hooks are inserted into the slits. Press the cap lightly onto the base plate until the snap‑fit‑hook engages. 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 25: Order Information

    Standard detector base, for surface-mount and flush- 4.998.021.535 mount cable insertion MS 400 B Standard detector base, for surface-mount and flush- F.01U.215.139 mount cable insertion, Bosch-branded FAA-MSR 420 Detector Base with Relay F.01U.508.658 FAA-420-SEAL Damp room seal for MS 400 and MS 400 B detector F.01U.215.142...
  • Page 26: Installation Accessories

    12 pieces) FME-TEST-CO CO Testing gas (250 ml) F.01U.301.469 SOLO461 Heat Detector Test Kit F.01U.363.162 SOLO770 Spare battery baton F.01U.363.163 FME-TESTIFIRE Multi-Stimulus Testing Tool F.01U.143.407 FME-TS3 Smoke Capsule F.01U.143.404 FME-TC3 CO-Capsule F.01U.143.405 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 27 AVENAR detector 4000 Order Information | en Type number Designation Product ID SOLO100 Telescopic Access Pole 4.998.112.069 SOLO101 Fixed Extension Pole 4.998.112.070 SOLO610 Test Equipment Bag 4.998.112.073 Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 28: Maintenance And Service

    DIN VDE 0833; these regulations stipulate reference to the manufacturer’s instructions for maintenance intervals. – Maintenance and inspection work should be carried out regularly and by trained personnel. – BOSCH ST recommends carrying out a functional and visual inspection at least once a year. Testing Detector Type FAP-425-DO-R, FAH-425-T-R...
  • Page 29: Test Instructions For Lsn Improved Version Fire Detectors

    All other detector variants: Trigger the T-piece. 7.2.2 Test Instructions for FAP‑425‑DOTC‑R / FAP‑425‑DOT‑R / FAP‑425‑OT‑R / FAP‑425‑OT Sequential walktest On the fire panel, in the Walktest menu, select Sequential walktest. Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 30: Diagnostic Data

    0 - 230 Initial set-up value for a new detector 0 - 350 Normal working range 350 - 450 Slight pollution: Exchange detector soon 450 - 510 Heavy pollution: Exchange detector immediately 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 31 – The 10-digit unique number to identify the detector through diagnostic screen or Remote Services when connected to the panel. – EMC value The EMC value indicates the EMC level. Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 32: Warranty

    The packaging bag used for multisensor detectors with C sensor consists of tear-resistant PE- ALU laminated film and may be disposed of with the household refuse. Defective detectors are exchanged and should be disposed of in accordance with legal regulations. 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 33: Technical Data

    EN 54‑5 EN 54‑5 EN 54‑5 unit Thermal maximum > 54 °C / > 54 °C / > 54 °C / > 54 °C / unit > 69 °C > 69 °C > 69 °C > 69 °C Chemical Sensor range Max. monitoring area 120 m² 40m² (observe VdS guidelines) Bosch Sicherheitssysteme GmbH 2021-11 | 4 | F.01U.283.550 User manual...
  • Page 34 Approx. weight with 135 g 125 g 115 g packaging The FAP-425-O and the FAP-425-OT have the same technical data as the FAP-425-O-R and FAP-425-OT-R, but are not fitted with rotary switches. 2021-11 | 4 | F.01U.283.550 Bosch Sicherheitssysteme GmbH User manual...
  • Page 36 Bosch Sicherheitssysteme GmbH Robert-Bosch-Ring 5 85630 Grasbrunn Germany www.boschsecurity.com © Bosch Sicherheitssysteme GmbH, 2021 Building solutions for a better life. 202111231948...