Troubleshooting For Sa Indoor Unit; Indoor Unit Pcb Abnormality - Daikin 2MXS40H2V1B Service Manual

Inverter multi for 2 rooms h-series / g-series
Hide thumbs Also See for 2MXS40H2V1B:
Table of Contents

Troubleshooting for SA Indoor Unit

6. Troubleshooting for SA Indoor Unit

6.1

Indoor Unit PCB Abnormality

A1
Error Code
Method of Error
The system checks the data from EEPROM.
Detection
Error Decision
When data could not be correctly received from the EEPROM
Conditions
EEPROM : Type of nonvolatile memory. Maintains memory contents even when the power
supply is turned off.
Supposed
Causes
Troubleshooting
169
External factor (noise etc.)
Defective indoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn the power supply off
once and then back on.
Return to normal?
NO
YES
SiBE121123_A
Could be other causes
(noise, etc.) than
malfunction.
Replace the indoor unit
PCB.
(R15319)
Service Diagnosis