7.3

MENU SCREENS (Menu)

Pressing the menu keypad a series of screens will be displayed, permitting the user to set some
functions of the UPS, to restore the command total off, to perform the LEDs TEST, and to switch
the inverter ON/OFF.
LP 33
20kVA P1
UPS ON
> INVERTER ON
INVERTER OFF
LAMP TEST
> RESET TOTAL OFF ‫٭‬
> LEVEL 1: USER
LEVEL 2: SERVICE
UPS FAILURE
CALL SERVICE
OPM_LPS_33E_10K_30K_4CN_V010.doc
1.
UPS family, nominal rating and for RPA: P + No. UPS.
2.
The operating mode of the UPS (UPS ON/OFF).
1.
Screen inverter command: Inverter ON.
‫٭‬
2.
Screen inverter command: Inverter OFF.
(The visualisation of
1.
Signalling LEDs test and buzzer test.
2.
Restore the output supply following the command total off
(the asterisk
total off has been activated with Q1 closed).
1.
Level 1: this first level not protected by password allows the
user to modify some parameters of the UPS (see
Section 7.3.1).
2.
Level 2: access protected by password reserved for service
engineers.
1.
Screen indicating the presence of alarm condition and the
consequent operation mode.
UPS status: UPS shutdown due to UPS FAILURE (fuse
blown)
(OVERTEMPERATURE or MAINS FAILURE).
2.
Action needed following the alarm condition CALL
SERVICE or
output statement which can be APPLIC.ON UTILITY if the
output is powered by mains or
APPLIC. PROTECTED when the load is normally powered
by the inverter.
51/82
‫٭‬
, indicates the Inverter status).
‫٭‬
beside the text means that the command
or
abnormal
conditions