Input / Output Cable Ratings - GE Digital Energy LP 33 Operating Manual

10 – 20 – 30 kva series 4
Hide thumbs Also See for Digital Energy LP 33:
Table of Contents
g
4.7.3

Input / output cable ratings

Cable sizes indicated below, do not consider eventual line voltage drop.
NOTE !
The values given in the tables below do correspond to European Standards
(EN) and, in brackets, for Swiss standards (SEV/ASE).
In any case the local standards must be respected.
Fig. 4.7.3-1 Common input mains
UPS model
A and B
LP 33 / 10 kVA
5x4 (5x6)
LP 33 / 20 kVA
5x10 (5x16)
LP 33 / 30 kVA
5x10 (5x16)
NOTE !
According to EMC standards, the connection between the UPS and an
external battery must be done using a shielded cable!
OPM_LPS_33E_10K_30K_4CN_V010.doc
Recommended sizing for the lines A, B, C, D, E (mm
According to European Standards EN and Swiss standard SEV/ASE (in brackets)
C
5x4 (5x6)
5x10 (5x16)
5x10 (5x16)
Fig. 4.7.3-1 Separate input mains (option)
D
4x2.5 (4x4)
5x2.5 (5x4)
4x6 (4x10)
5x6 (5x10)
4x10 (4x16)
5x10 (5x16)
Operating Manual LP 33 / 10-20-30 kVA
29/82
GE
)
2
E
K
4x2.5 (4x4)
4x6 (4x10)
4x10 (4x16)