Conventional Fire Panel
Notification appliance behavior in zone test
5
1
4
1
4.5.2

Alarm Relay

In the Alarm Relay submenu, you can specify the properties of
the alarm relay. These include the Silencable and Drillable
settings. You can use Silencable to specify whether the relay
can be silenced manually. Drillable specifies whether the alarm
relay is also activated during a manual alarm (Drill/Evac).
Alarm relay can be muted
5
2
1
1
Bosch Sicherheitssysteme GmbH
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 4.
This takes you to the NAC in test submenu.
Press zone keys 1 or 2.
2
1 Activation
...
2=No Activation (default setting)
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 2.
This takes you to the Alarm Relay submenu.
Press zone key 1.
This takes you to the Silencable submenu.
Press zone keys 1 or 2.
2
1 Silencable
...
2=Not Silencable (default setting)
System Configuration | en
2014.06 | 7.0 | F.01U.172.980
51