26
en | Installation
Notice!
Note that the maximum line resistance for the relay outputs is
22.5 Ohm.
3.3.6

Extensions

The extension modules offer four connections activated by
transistors or relay.
Notice!
The relay outputs can switch a maximum of 1 A @ 30 VDC each.
The transistor outputs switch a maximum of 20 mA @ 24 VDC
each. Inductive loads are not permitted.
3.3.7

External power supply

You can use the FPP-5000 as an external power source for the
FPC-500 Fire Panel.
Notice!
Note that the FPP‑5000 housing must be installed in the direct
vicinity (without a space) of the FPC‑500‑x. The connecting line
between the FPP-5000 and the transmission device must not be
exposed, as it is not monitored.
FPC‑500‑2 and FPC‑500‑4
Wire the FPP-5000 as shown in FPC‑500‑2 and FPC‑500‑4, page
26.
Program input 1 to Ext PS Fault (see Input 1, page 48). The
relay is not included in the scope of delivery.
2014.06 | 7.0 | F.01U.172.980
Conventional Fire Panel
Bosch Sicherheitssysteme GmbH