Cycle Part - LG Single "A" Service Manual

Single "a" air conditioner, -inverter type
Hide thumbs Also See for Single "A":
Table of Contents

5. Cycle Part

Trouble analysis
1. Check temperature difference between intake and discharge air, and check for the operating current too.
Case
Temp. difference : approx. 0°C
Case 1
Current : less than 80% of rated current
Temp. difference : approx. 8°C
Case 2
Current : less than 80% of rated current
Temp. difference : less than 8°C
Case 3
Current : over the rated current
Case 4
Temp. difference : over 8°C
NOTICE
Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is rela-
tivery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle in cooling mode.
Suction pressure
Discharge Air (Compared
(Compared with
with the normal valve)
the normal value)
Higher
Lower
NOTICE
1. The suction pressure is usually 8.5~9.5kg/cm2G(Cooling) at normal condition.(R410A)
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.
Be sure to disconnect the power cable plug from the plug socket before disassembling the
equipment for a repair. Internal components and circuit boards are at main potential when the
equipment is connected to the power cables. This voltage is extremely dangerous and may
cause death or severe injury if come in contact with it.
Be sure to turn off power switch before connect or disconnect connector, or parts damage may
be occurred.
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Symptom
Temperature of
Cause of Trouble
Defective compressor
High
Defective 4-way reverse valve
Excessive amount of
Normal
refrigerant
Insufficient amount of
Higher
refrigerant (Leakage)
Clogging
All amount of refrigerant leaked out.
Check refrigeration cycle.
Refrigerant leakage Clog of refrigeration cycle
Defective Compressor.
Excessive amount of refrigerant
Normal
- 83 -
5. Trouble Shooting
Supposed Caused
Description
Current is low.
High pressure does not quickly
rise at the beginning of
operation.
Current is low.
LGE Internal Use Only