External Battery Connection - GE LP 33 Series Operating Manual

10 – 20 – 30 kva 400 vac ce / series 4
Hide thumbs Also See for LP 33 Series:
Table of Contents
4.8.3

External battery connection

Before proceeding to an external battery connection, follow the Safety rules concerning the battery.
Make sure that the UPS is not powered, and remove the external battery protections and the fuses F9,
F10, F11 at the front of the UPS cabinet.
WARNING !
Before closing the battery fuses F9, F10 and F11, verify for correct polarity of the
battery connection.
+
F9 (+) = Positive pole
NOTE !
Clamp the input/output cables with the included cable-ties "A".
Modifications reserved
OPM_LPS_33E_10K_30K_4GB_V030.doc
-
+
0
-
0
F10 (0) = Central point of battery blocks
Fig. 4.8.3-1 External battery connection to UPS
-
+
0
F11 (-) = Negative pole
Operating Manual LP 33 Series / 10-20-30 kVA