Haier HR18D2VAR Installating And Operation Manual

Haier HR18D2VAR Installating And Operation Manual

13 seer 1.5 to 3.0 ton heat pump
Hide thumbs Also See for HR18D2VAR:
13 SEER 1.5 to 3.0 Ton
HR18D2VAR
HR24D2VAR
HR30D2VAR
HR36D2VAR
No.0010578573
Table of Contents
loading

Summary of Contents for Haier HR18D2VAR

  • Page 1 13 SEER 1.5 to 3.0 Ton HR18D2VAR HR24D2VAR HR30D2VAR HR36D2VAR No.0010578573...
  • Page 2 ! WARNING These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
  • Page 3: Table Of Contents

    9.3.Wiring diagram ----------------------------------------------------------------------------- 1.INTRODUCTION This manual contains the installation and operating instructions for your new Heat Pump. Improper installation can result in unsatisfactory operation or dangerous conditions. Carefully read this manual and any instructions packaged with separate equipment required to make up the system prior to installation.
  • Page 4: Specification

    The dimensions for the condensing unit are illustrated in Figure 1. Physical and electrical specifications are provided in Table 1 for 13 SEER systems respectively. The Figure 2 show a schematic of a heat pump on the cooling cycle and the heating cycle. Table 1: Model:HR18-36D2VAR...
  • Page 5 Figure 1 Table 2: System Capacity cooling Indoor fan Outdoor Indoor speed HR18D2VAR HB2400VD1M20 HR24D2VAR HB2400VD1M20 HR30D2VAR HB3600VD1M22 HR36D2VAR HB3600VD1M22 heating Indoor fan Outdoor Indoor speed HR18D2VAR HB2400VD1M20 HR24D2VAR HB2400VD1M20 HR30D2VAR HB3600VD1M22 HR36D2VAR HB3600VD1M22 ARI data of indoor Capacity SEER CFM...
  • Page 6 DISTRIBUTOR !Warning - The Bi-flow drier is strongly recommended to be installed by installer and replaced once two years. This will give your equipment great help in long life. Heat Pump Refrigerant Circuit DISCHARGE TEMP. SENSOR SERVICE PORT HIGH PRESSURE...
  • Page 7: Unit Inspection

    4.UNIT INSPECTION This product has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully. If damage is found, report immediately to the transportation agency. 5.EQUIPMENT PROTECTION FROM ENVIRONMENT The metal parts of the unit may be subject to rust or corrosion in adverse environmental conditions.
  • Page 8: Unit Clearances

    Provide a level concrete slab. To prevent transmission of noise or vibration, slab should not be connected to building structure. Some sort of sound-absorbing material should be placed between the condenser and the slab. A good material to use is rubber and cork pad. For rooftop application, make sure the building construction can support the weight and that proper consideration is given to the weather-tight integrity of the roof.
  • Page 9 PITCH SUCTION LINE TOWARD OUTDOOR UNIT 1/2" FRO EVERY 10' OF LINE OUTDOOR UNIT LIQUID LINE INVERTED LOOP LIQUID LINE OUTDOOR UNIT SUCTION LINE Only refrigeration-grade copper piping (dehydrated and sealed) should be used. Take extreme care to keep the refrigerant tubing clean and dry prior to and during installation. If in doubt, blow out the tubing with dry nitrogen to remove any chips or debris before connection.
  • Page 10 A fitting is on the liquid line to remove pressure. ! CAUTION - Heat Pumps are charged with refrigerant. Heat Pump liquid and suction valves are closed to contain the charge within the unit. Do not force the valve stem against the retaining ring. If the valve stem is backed out past the retaining ring, system pressure could force the valve stem out of the valve body and possibly cause personal injury.
  • Page 11: Refrigerant Metering Devices

    Refrigerant Metering Devices Replace the existing indoor unit fixed orifice with the orifice supplied with the outdoor unit. See table 4 for the fixed orifice size for each unit. Table 4 outdoor model HR18D2VAR HR24D2VAR HR30D2VAR HR36D2VAR Fixed orifice size...
  • Page 12 Evacuation All new installations must be evacuated to a deep vacuum in order that all noncondensible gases and moisture are removed prior to charging the system. Air in a system causes high condensing pressure, which increases power consumption and reduces performance. The presence of moisture in a system can render it inoperable in a very short time.
  • Page 14: System Startup

    The condensing unit rating plate and the tables of "Physical and Electrical Specifications / Outdoor Units" (Table 1) provide pertinent data necessary for the selection of proper size electrical service and over-current protection devices. Table 6 provides data on the minimum copper wire size as a function of supply wire length and circuit ampacity.
  • Page 15: Operation

    11.If checking the unit on the heating cycle in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts properly. 12.Check the refrigerant charge (see Instructions under "Charging the System"). 13.Replace service port caps.
  • Page 16 Symptom Possible Cause Defective four way valve Power off or loose electrical connection Incorrect thermostat setting No cooling/heating Defective contactor Open circuit breaker of blown fuses Defective transformer Interconnecting low voltage wiring damage Replace thermostat wiring Dirty filters Indoor air blockage Blocked outdoor coil Improperly sized unit Insufficient Cooling Improper airflow...
  • Page 17 HR18-36D2VAR YL/GR...
  • Page 18 Made in P.R.C.

This manual is also suitable for:

Hr24d2varHr30d2varHr36d2var

Table of Contents