Digital Communicator Operation (7100-D Model); Central Station Reporting; Table 3-5 Ul Listed Receivers Compatible With The 7100 - Honeywell Gamewell 7100 Series Installation & Operating Manual

Fire alarm control
Table of Contents

3.10 Digital Communicator Operation (7100-D Model)

The 7100-D digital communicator model features numerous formats for communication to
a central station. The 7100-D provides the following functions:
• Line seizure - takes control of the phone lines, disconnecting any premises phones
using the same lines.
• Off/On-Hook - perform on and off-hook status to phone lines.
• Listen for dial tone - 440 Hz tone typical in most networks.
• Dialing the Central Station phone number – programmable.
• Discern proper Central Station "ACK" and "Kiss-off" tone.
• Transmit data to the Central Station.
• Verify that data has been accepted by the Central Station.
• Hang-up and release phone lines.
• Communicate in a variety of formats.
3.11

Central Station Reporting

UL Listed receivers compatible with the 7100 are listed in Table 3-5 below:

Table 3-5 UL Listed Receivers Compatible with the 7100

Manufacturer
Silent Knight
Silent Knight
Ademco
Sur-Gard
(Ver. 1.64 or higher)
Osborne Hoffman
† If you are using the Model 9000 and the message "HELP" appears on the printer after
attempting to download, the 9000 software must be upgraded.
The Model 9000 must have the Model 9307 software package, Revision 900501 or later,
to print the PROGRAMMING PASS and PROGRAMMING FAIL messages.
9000-0447 Rev. I
Receiver Model
Model 9000†
Model 9800/9500
Model 685
SG-MLR2-DG
Quickalert
Page 19 of 42
Formats
SIA-8
SIA-20
SK4/2
3/1 14
3/1 23
SIA-8
SIA-20
SK4/2
3/1 14
3/1 23
Contact ID
3/1 14
3/1 23
SIA-8
SIA-20
SK4/2
3/1 14
3/1 23
Contact ID
SIA-8
SIA-20
Table of Contents