Ups r12000 xr models installation instructions

Quick Links

hp uninterruptible
power system r12000
xr models

installation instructions

Read instructions completely before beginning

installation procedure.

© 2003 Hewlett-Packard Development Company, L.P.
Hewlett-Packard Company shall not be liable for technical or editorial errors or
omissions contained herein. The information in this document is provided "as is"
without warranty of any kind and is subject to change without notice. The warranties
for HP products are set forth in the express limited warranty statements
accompanying such products. Nothing herein should be construed as constituting an
additional warranty.
hp uninterruptible power system r12000 xr models installation instructions
Second Edition (December 2002)
Part Number 146305-002
146305- 002
Overview
These instructions show how to install an uninterruptible power
system (UPS). For detailed information about the UPS, refer to the
UPS user guide on the Power Products Documentation CD.
These instructions assist qualified personnel with the installation of
the HP UPS. Save these instructions for future reference.
Use the UPS R12000 XR Installation and Startup Package to
facilitate the installation and startup of the UPS.
Table 1: Installation and Startup Package Numbers
Location
United States
Worldwide

Important Safety Information

Before installing this product, read the Important Safety
Information guide included with the UPS kit.
Regulatory Compliance
Information Numbers
For regulatory compliance certifications and identification
purposes, the UPS models are assigned a series number, also
identified on the Regulatory Compliance label located on the side
of the UPS. For certification information, always refer to the series
number EO3002 and PDU series number EO3024.
NOTE: The rating label on the device provides the class (A or B) of the
equipment. Class B devices have a Federal Communications Commission
(FCC) logo or FCC ID on the label. Class A devices do not have an FCC logo
or FCC ID on the label. After you determine the class of the device, refer to
the UPS user guide for complete regulatory compliance notices.

Installation Considerations

Weight
WARNING: To reduce the risk of personal injury or
damage to the equipment:
Have the floor-loading requirements evaluated by a
190 kg
facilities engineer before installation.
420 lb
Observe local occupational health and safety
requirements and guidelines for manual material
handling.
Obtain adequate assistance to lift and stabilize the
product during installation or removal. The UPS
will be unstable when not fastened to the rails.
Remove all batteries and electronics modules to
reduce the overall weight of the UPS chassis.
Use three people to lift and place the UPS in the
rack.
Table 2: Component Weights
Component
Chassis
Electronics modules (4)
Battery modules (4)
Fully assembled UPS
Package Number
FM-BPINS-IN
FP-UPSXR-IN
Weight
43 kg (95 lb)
9.5 kg (21 lb) each
27 kg (60 lb) each
190 kg (420 lb)
Table of Contents
loading

Summary of Contents for HP R1500 - UPS XR

  • Page 1: Installation Instructions

    Remove all batteries and electronics modules to reduce the overall weight of the UPS chassis. Hewlett-Packard Company shall not be liable for technical or editorial errors or omissions contained herein. The information in this document is provided “as is” •...
  • Page 2: Preparing The Site

    Position Kit Contents WARNING: To reduce the risk of personal injury or damage Documentation to the equipment, take the following precautions when • International Regulatory Compliance guide installing the equipment: • Important Safety Information guide • The UPS must be installed at the bottom of the rack. If placed in the rack with existing equipment, the rack •...
  • Page 3: Unpacking The Ups

    2. Use the rack template tool to measure and mark the screw Unpacking the UPS locations for the rails on the front and rear of the rack. WARNING: To reduce the risk of personal injury or damage to the equipment: •...
  • Page 4 5. Insert the back screws into the cage nuts that were installed in 5. Attach the hold-down bracket (1) to the left rail using the step 3. screws in the hardware kit. Attach the hold-down bracket to the UPS using the nuts (2) supplied with the hardware kit. Installing the UPS in the Rack Before attempting to install the UPS, review and adhere to all WARNING: Do not block the exhaust air vents.
  • Page 5: Connecting The Repo Port

    WARNING: To avoid risk of personal injury or electric shock, 8. Attach the hold-down bracket to the rack rail with the screws verify that the main breaker switch is in the Off position before included in the hardware kit. wiring the REPO port. To connect the REPO port to the EPO circuit: 1.
  • Page 6: Connecting The Ups

    Connecting the UPS to the AC Branch Connecting the UPS Circuit To connect the UPS to the AC branch circuit: 1. Locate the input/output terminal block cover. Risk of Fire Notice 2. Remove the terminal block cover. Remove the screws (1), release the cover (2), and remove the cover (3).
  • Page 7 9. Following the diagram on the back of the UPS below the Completing the UPS Assembly terminal block: a. Connect the input wires to the ground and the input Inserting the Electronics Modules terminal block connections (1). 1. Insert the four electronics modules, bottom to top. b.
  • Page 8 3. Snap the remaining bezels into place. Verify that the ventilation Inserting the Batteries holes are over the electronics modules. Slide the batteries into the chassis (1), bottom to top, and tighten the screws (2). Connecting the Communication Ports to Attaching the Bezels Other Devices 1.
  • Page 9: Turning On The Main Circuit Breaker

    Turning on the Main Circuit Placing the UPS in Operate Mode Breaker NOTE: On initial utility startup, you may receive an Inverter Uncalibrated After a qualified electrician has properly wired the UPS to utility alarm. Press the On button to start the autocalibration process, which lasts power and has installed all electronics modules, turn on the AC approximately 2 to 4 minutes.

This manual is also suitable for:

3 phase series

Table of Contents